background image

SDC-620 Multiple door controller 

 

 

 
Copyright© 2016 

– Saflec Systems (Pty) Ltd. 

http://www.saflecsystems.co.za 

Important:

 When driving inductive loads such as strike locks, care should be taken to prevent a 

back-EMF voltage spike. In order to do this a freewheeling diode (also known as flyback diode) 
should be connected across the load as seen in the figure below. 
 
 
 
 
 
 
 
 

Figure 15 

Diagram showing freewheeling diode over an internally powered inductive load (eg. strike lock) 

– normally open. 

Step 8: Connect the Wiegand devices 

The Wiegand devices communicate with the SDC-620 via five signalling lines. 
These lines can be broken into two groups: 

  The data lines (Data 0, Data 1) 

  The control lines (Red LED, Green LED and Buzzer) 

 
Note: 

Make sure that the power is switched off before connecting these cables. 

 
Connect the data and control lines ensuring that the correct cables are used. 
Connect the power to the Wiegand device. 

 

 
 
 
 
 
 
 
 
 
 
 
 
 
 
 
Figure 16 

Wiring configuration for the Wiegand interfaces 

 
The second Wiegand interface can also be wired up in the same way. 
 
NOTE: In the SACS software the two Wiegand readers should be configured to be remote 
address 0, reader 1 and 2. This means that remote address 0 is shared between the RS-485 
slave devices and the Wiegand port. 

Summary of Contents for SDC-620

Page 1: ...ked using a protected RS 485 network The PC can connect to it using either RS 232 or the built in Ethernet connector or through the RS 485 network from another controller It has a reader RS 485 networ...

Page 2: ...SDC 620 Wiegand door controller 2 Copyright 2016 Saflec Systems Pty Ltd http www saflecsystems co za Figure 2 Possible position for an SDC 620 in a SACS access control system...

Page 3: ...wer the panel will be active If the screen is blank it will be in screen saving mode Tapping any button will awaken the screen and allow you to configure the device Figure 3 The configuration and diag...

Page 4: ...ations network Each controller on this network requires a unique address for communications and identification Duplicate addresses will cause communication problems The address of the controller can b...

Page 5: ...n the line by shorting J6 Controllers in the middle of the line must not have the termination jumper inserted as this can cause network problems In the diagram above you will see that the controller o...

Page 6: ...mmunicate with the host system This can be done through either the Ethernet connection or the RS 232 connection The Ethernet cable is a non power over Ethernet cable to an RJ 45 plug The typical wirin...

Page 7: ...oard with the power connector on the top right of the board the inputs are arranged in ascending order from left to right with a shared common between each input pair See the diagram below on how to c...

Page 8: ...for the output relays Figure 12 Example wiring for an externally powered magnetic lock Normally closed Output mode 2 Internally powered outputs To set the output to internally powered mode place two j...

Page 9: ...gand devices communicate with the SDC 620 via five signalling lines These lines can be broken into two groups The data lines Data 0 Data 1 The control lines Red LED Green LED and Buzzer Note Make sure...

Page 10: ...interface front page It shows basic diagnostics information on the main page but the links at the bottom will require a username and password for authentication The default username is root and passwo...

Page 11: ...contact Maximum voltage AC 250Vac Maximum voltage DC 220Vdc Internally powered Outputs Maximum combined current 3 7A Recommended maximums per relay 750mA at 12Vdc Externally powered Outputs Recommende...

Page 12: ...SDC 620 Multiple door controller 12 Copyright 2016 Saflec Systems Pty Ltd http www saflecsystems co za Notes...

Reviews: