SAFIRE 3200B AND 3800A FUEL OIL HEATER
INSTALLATION, OPERATION AND MAINTENANCE

WALL SLEEVE INSTALLATION

WALL SLEEVE:

When using wall sleeves, the combustion air must be led through a wall sleeve from the outside as well.

1.5

TANK, TANK CONNECTION, PUMP

December 2014
SF-LÄMMITIN OY Tilhenkatu 1 20610 Turku Finland Tel./Fax 02-2443282

1. Make a ø90 mm hole to the wall, whose 
midpoint is at a height of 225 millimetres from the 
bottom of the heater.
2. 

Stretch the air pipe (2)

 in accordance with

the wall thickness, and install it.
3.  Attach the interface box (3). Flue gas pipe 
height: midpoint 225 mm from the bottom of the 
heater.
4.  Cut the vent pipe (4) to a suitable length and 
fasten it with a clamp (12). 
5.  Install the overlong flue gas pipe (5) with a 
fastener (6).
6.  Install thermal insulation (7) of suitable length 
around the flue gas pipe.
7.  Mount the heater.
8.  Remove the housing (10) and diffuser (9) from 
the frame of the funnel. The housing can be 
removed by lifting its upper part approx. 4 mm. 
Attach the frame (8) of the funnel to the wall. Seal 
with silicone compound in order to keep water 
outside the wall structures. Fasten the topmost 
mounting screws (11) temporarily.
9.  Cut the flue gas pipe to a suitable size (see 
drawing: 12 mm out of the funnel frame)
10. Mount the diffuser (9) of the funnel and the 
housing (10). You will have to loosen the topmost 
mounting screws for this.

1 HEATER
2 THERMOSTAT TEMPERATURE SENSOR
3 FLUE GAS PIPE
6 PUMP
7 TANK
8 FILTER
9 BATTERY
12 FLUE GAS WALL SLEEVE
14 THERMAL INSULATION 

Summary of Contents for 3200B

Page 1: ... preferably be insulated with vermiculite This will avoid the condensation of the flue gas in the cold chimney as well as failures and weathering of the chimney resulting from the condensation 3 Install a piece of thermal insulation cut to a suitable length 4 Mount the heater and tighten the flue gas pipe and a potential air intake pipe with their fasteners 5 The combustion air can be led to the h...

Page 2: ...suitable length and fasten it with a clamp 12 5 Install the overlong flue gas pipe 5 with a fastener 6 6 Install thermal insulation 7 of suitable length around the flue gas pipe 7 Mount the heater 8 Remove the housing 10 and diffuser 9 from the frame of the funnel The housing can be removed by lifting its upper part approx 4 mm Attach the frame 8 of the funnel to the wall Seal with silicone compou...

Page 3: ...mber to replace the original wiring with thicker ones so that the cross sectional area of the wires in mm2 corresponds with the length of the wires in metres e g the area of two 10 metre wires should be at least 10 mm2 In this case cut the original wires at a suitable length behind the heater and attach thicker wires with a suitable connecting piece Be careful not to connect the wires to the batte...

Page 4: ... in a cold cabin for the winter it is recommended to run the heater with kerosene before leaving it unused so that the fuel pump and fuel lines remain filled with kerosene which withstands even colder temperatures 2 1 2 CONTROLS AND INDICATORS 2 1 2 1 CONTROLS The heater is started by turning the switch to the HEAT position The heater is started by turning the switch to the HEAT position Automatic...

Page 5: ...5 3 minutes after start up when the flame sensor has detected a sufficient combustion The ignition process ends after approx 6 5 minutes and the heater is set to the power level of the thermostat or manual setting 2 1 3 1 STARTING WITH A REMOTE START UP DEVICE When enabling the start up device make sure that the heater is ready for use and that air circulation is possible in the heated space Turn ...

Page 6: ...ing shown on the display Please note If you have turned off the heater after the malfunction was shown you can bring up the error code again by turning the switch to the AUTO position WHEN THE AUTO POSITION IS SELECTED THE DISPLAY SHOWS THE LAST ERROR CODE THAT HAS LED TO THE SHUTTING DOWN OF THE HEATER 3 3 ERROR MESSAGES in parentheses the text shown on GENIUS screens No 1 overheating fault indic...

Page 7: ...s paraffin formation which occurs when the fuel is in cold temperatures If the fuel line is not completely blocked the blockage can be removed by adding isopropanol to the fuel gasoline car antifreeze which dissolves the paraffin blockage rapidly Isopropanol can also be forced through the lines by using a syringe or e g a bicycle pump while the heater is on start up phase A small air leak in the s...

Page 8: ...en the burner compartment cover 3 screws force the top of the cover open from the protrusions 5 Remove the glow plug 1 and its mounting plate 6 Remove the burner support spring and the burner 8 If you are unable to remove the burner use a hammer and a suitable piece of wood see picture Remove the topmost centering plate of the spring 11 first in order to remove the burner cylinder without damaging...

Page 9: ...il wires 4 Remove the iron shell 1 of the pump by opening its screws 5 Pull the upper part 3 of the pump out of the coil 4 The piston 9 and spring 10 come loose at the same time 6 The lower end of the pump 5 can be removed by pulling as well 7 Now you can wash the insides of the pump with e g isopropanol There should not be any stiffness between the piston and the cylinder 8 Check the functioning ...

Page 10: ...INSPECTING AND CLEANING THE PUMP 4 4ELECTRICAL CONNECTIONS 3800A ...