background image

WIRING METHOD A: 

SAME POWER SOURCE FOR CONTROL AND BURNER CIRCUIT.

WIRING METHOD B: 

SEPARATE POWER SOURCE FOR CONTROL AND BURNER CIRCUIT.

BURNER

POWER

SOURCE

24VAC

60HZ

NEUTRAL

HOT

DISCONNECT

SWITCH

BURNER

POWER

SOURCE

24VAC

60HZ

BURNER

POWER

SOURCE

24VAC

60HZ

NEUTRAL

HOT

+

0

LIMIT

CONTROLS

BURNER

POWER

SOURCE

24VAC

60HZ

+

0

FEEDER VALVE

CONTROL

POWER

SOURCE

24VAC

60HZ

NEUTRAL

HOT

DISCONNECT

SWITCH

CONTROL

POWER

SOURCE

24VAC

60HZ

NEUTRAL

HOT

BURNER
CIRCUIT

DISCONNECT

SWITCH

CONTROL

POWER

SOURCE

24VAC

60HZ

+

0

LIMIT

CONTROLS

BURNER
CIRCUIT

CONTROL

POWER

SOURCE

24VAC

60HZ

+

0

LIMIT

CONTROLS

BURNER
CIRCUIT

FEEDER VALVE

A1

Connect input voltage (24 VAC, 60HZ)
to terminals 2 and 1. 24 VAC, 60HZ 

must be supplied to terminals 2 and 1 for internal
operation of the control.

Install a jumper between terminal 1       

A2

and terminal P1. Power from terminal 
P1 is supplied to terminal P2 when water reaches
the upper probe. Power to terminal P2 is removed
when water falls below the bottom probe.

A3

Connect terminal 2 to burner circuit
neutral. Connect terminal P2 to 

burner circuit in series with other limit controls.
Consult boiler manufacturer’s instructions for
proper terminal connections. NOTE: Control is
wired in series with and before other limits.

Feeder Connection: Connect feeder   

A4

common to terminal 2. Connect feeder 
hot to terminal A. Whenever water falls below the
lower probe, power is supplied to the feeder ter-
minal A. When water reaches the upper probe,
power to the feeder is removed.

B1

Connect input voltage (24 VAC, 60HZ)
to terminals 2 and 1. 24 VAC, 60HZ 

must be supplied to terminals 2 and 1 for internal
operation of the control.

Connect hot lead from burner   

B2

control circuit to terminal P1. 
This terminal supplies power to terminal P2 in
normal operating conditions when water is at the
probe. Connect neutral to burner circuit. 
NOTE: Consult boiler manufacturer’s instructions
for proper terminal connections.

B3

Connect terminal P2 to burner circuit
in series with other limit controls. 

Consult boiler manufacturer’s instructions for
proper terminal connections. NOTE: Control is
wired in series with and before other limits.

Feeder Connection: Connect feeder   

B4

common to terminal 2. Connect
feeder hot to terminal A. Whenever water falls
below the lower probe, power is supplied to the
feeder terminal A. When water reaches the upper
probe, power to the feeder is removed.

NOTE:

All schematic diagrams show all systems in

the off position. No power applied.

A1

A3

A4

B1

B2

B3

B4

A2

3

Reviews: