safgard 1100 Instructions Download Page 4

LIMITED MANUFACTURER’S WARRANTY

We warrant products manufactured by Hydrolevel Company to
be free from defects in material and workmanship for a period
of  two  years  from  the  date  of  manufacture  or  one  year  from
the date of installation, whichever occurs first. In the event of
any claim under this warranty or otherwise with respect to our
products  which  is  made  within  such  period,  we  will,  at  our
option, repair or replace such products or refund the purchase
price  paid  to  us  by  you  for  such  products.  In  no  event  shall

Hydrolevel  Company  be  liable  for  any  other  loss  or  damage,
whether direct, indirect, incidental or consequential. This war-
ranty  is  your  EXCLUSIVE  remedy  and  shall  be  IN  PLACE  OF
any  other  warranty  or  guarantee,  express  or  implied,  includ-
ing, without limitation, any warranty of MERCHANTABILITY or
fitness  for  a  particular  purpose.  This  warranty  may  not  be
assigned  or  transferred  and  any  unauthorized  transfer  or
assignment thereof shall be void and of no force or effect.

126 Bailey Road, North Haven, CT 06473 • Phone (203) 776-0473 • FAX (203) 764-1711 • 

www.hydrolevel.com

OPERATIONAL TEST PROCEDURE

IMPORTANT: Do not run boiler unattended until the following procedure is completed

1. 

Before raising the water level above the Model 1100, turn on power to the boiler and set the thermostat to call for heat. Both the green

“POWER” LED and amber “LOW WATER” LED should illuminate. The burner should not fire. IMPORTANT: If the burner fires with no water

at the probe, immediately shut down power to the boiler and refer to the Trouble Shooting instructions below.

2. 

Proceed to fill the boiler with water. When water reaches the LWCO position, the burner should fire. If the burner does not fire, refer to the

Trouble Shooting instructions below.

3. 

Turn off the power to the boiler and finish filling the system.

4. 

Before leaving the job, power up the system and push the TEST button on the Model 1100 to simulate a low water condition. The amber

“LOW WATER” LED should illuminate and the burner should shut down.

SERVICE & MAINTENANCE

EVERY YEAR

Check control operation annually by pressing the TEST button. The amber “LOW WATER” LED should illuminate and the

burner should shut down.

5 YEARS

Remove the low water cut-off every five years and clean all surfaces in contact with water.

IF AMBER LED

If the amber “LOW WATER” LED is blinking, the control should be removed and all surfaces in contact with water should be 

IS BLINKING

cleaned. The blinking LED indicates that the sensor may be getting coated with oil or other residues in the system. If left 

unchecked, this could result in a nuisance low water shutdown.

TROUBLE SHOOTING

IF THE BURNER DOES NOT SHUT DOWN 

(when water is below the probe or 
when the TEST button is pressed)

1. 

Turn off boiler power immediately and re-check wiring.

2. 

Turn off boiler power and drain system. Remove low water cut-

off and check for adequate clearance – no metal should be in

contact with the control’s metal probe tip.

IF THE BURNER DOES NOT FIRE

1.  

Make sure water has reached the level of the control.

2. 

Check green wire for proper ground. Make sure the wire is

attached to an unpainted surface that is electrically common to

the boiler.

3. 

Check to ensure the control’s metal probe tip is not surrounded

by an air pocket. Shut down power to the boiler and slowly

loosen, but do not remove, the control. Allow any air to escape.

When water begins to seep past threads, retighten the control.

4. 

Re-check wiring and check for correct incoming voltage.

DIMENSIONS

SPECIFICATIONS

VOLTAGE

24 VAC

POWER CONSUMPTION

1 VA

SWITCHING CAPACITY

50 VA

MAX LOAD

5  Amps

MAX PRESSURE

160 PSI (11.25 kg/cm

2

)

MAX WATER TEMPERATURE

250°F (121°C)

MAX AMBIENT TEMPERATURE

170°F (77°C)