• ADVANCED SOLID STATE DESIGN

• TEST BUTTON FOR EASY DIAGNOSTICS

• POWER, LOW WATER AND SERVICE-NEEDED INDICATORS

• MOLEX CONNECTOR FOR EASY WIRING

• COMPACT SIZE ALLOWS FOR MOUNTING IN TIGHT SPACES

Step 

���

Step 

���

Step 

���

Step 

���

Low Water Cut-Off
For Residential 
Hot Water Boilers

24 VAC Operating Voltage

Model 1100

Determine Mounting Location

The Safgard 1100 must be installed at or above the
minimum safe water level established by the boiler
manufacturer. The 1100 can be installed directly into
the boiler if a suitable tapping is available 

. The

1100 can also be installed in the boiler piping using a
standard 3/4" tee 

Note: 

When installing in piping, select a location

close to the boiler to ensure the 4' wiring harness will
reach the 24-Volt transformer. The cut-off should be
installed on the boiler side of the circulator or shut-off
valves.

IMPORTANT: Check for adequate clearance 
(minimum 1/4") from metal probe sensor to any
surface inside the boiler or pipe. 

Do not install in a location that could hold or trap
water in the event of a low water condition.

Apply Teflon

®

tape to

the threads of the
Model 1100. Do not
use pipe dope or
other pipe sealants.

Hand tighten the
control into boiler
tapping or pipe tee.
Be careful not to
cross thread. 

Note: 

Do not use a

wrench. Hand tighten
only.

Plug wire harness
into connector on
face of control.

WARNING

Electrical shock hazard.

To prevent electrical shock, death or

equipment damage, disconnect power supply before

installing or servicing control. Only qualified personnel may install or service this control in
accordance with local codes and ordinances. Read instructions completely before proceeding.

CAUTION

To prevent serious

burns, boiler

should be thoroughly cooled before installing or
servicing control.

WARNING

Frozen pipes/water damage.

Central heating systems are prone to shut down as a result of power or fuel outages, 

safety related fault conditions or equipment failure. Installation of freeze protection monitoring or other precautions

is recommended for unattended dwellings in climates subject to sustained below-freezing temperatures.