INSTALLATION INSTRUCTIONS
The first TempLink 3000 must be positioned in a location safely reached by a secured ladder or a manhole access point.
Access to inside the roof space is not required for installation purpose’s.
The building structure must be inspected for integrity and compliance in relation to relevant building codes.
The building construction must meet all requirements in regard to correct fitting and use of materials set by manufacturers.
Inspections must be undertaken of timber and metal structural components for signs of structural damage such as splits, water
damage, pest erosion and fixing issues.
Roof spaces to be accessed must not be over 30 degrees in pitch.
Metal Roof Sheeting with Metal Battens or Timber Battens
It is recommended the TempLink 3000 be installed to the crest of the roof sheeting profile, where this is not practical the
TempLink 3000 may be installed into the pan away from debris.
Metal roof sheet size must be a minimum of 0.42mm.
1.
Remove six (6) of the existing roof screws along the batten line at the appropriate location for the TempLink 3000.
2.
Place the cable section out along the roof sheeting, adjust the tabs to fit the roof profile and to line up with the existing
roofing screw holes.
3.
Replace the six existing roofing screws with six (6) screws Size 14(g) -10(TPI) x 65 Hex Head Screws. Screw through each
tab and existing hole, securing to the batten under the roof sheeting.
DO NOT OVER TENSION SCREWS AS THIS WILL RESULT IN THREAD STRIPPING, TAB / STRUCTURAL DAMAGE.
4.
Ensure the screws are the correct length to engage the batten to eliminate over passing the thread into the blank part of
the screw. Screws must penetrate timber batten by at least 35mm.
Tile Roof with Timber Rafters
1.
Remove existing roof tiles at the appropriate location for the TempLink 3000.
2.
Place the cable section down the rafter and drill a 4.5mm pilot hole, (never attach to battens on tile roofs, always only attach
to suitable rafters).
3.
Screw tabs to the rafter through the tab holes no less than 100mm apart using six (6) x Size 14(g) -10(TPI) x 65, Hex Head
Screws.
DO NOT OVER TENSION SCREWS AS THIS WILL RESULT IN THREAD STRIPPING, TAB / STRUCTURAL DAMAGE.
4.
Screws must penetrate timber batten by at least 35mm.
The SafetyLink TempLink 3000 anchor point is now ready for use, giving you an anchor point to attach to while installing the next
SafetyLink anchor point.
Removal of
TempLink 3000
During removal you must ensure you are safe at all times.
1.
Remove screws from the TempLink 3000 and remove TempLink 3000.
2.
On tiled roofs replace the tiles and ensure a water tight seal is achieved.
3.
On metal roofs replace the six (6) x Size 14(g) -10(TPI) x 65, Hex Head Screws to secure roof sheet and ensure a water
tight seal is achieved.
TIMBER / METAL
TIMBER / TILE