Powered by Safety
®
43
Installation
01.4IB.77020
3. Turn the racking handle
clockwise until the breaker
position indicator displays “
TEST
”.
4. Remove the racking handle and
verify that the emergency racking
drive shaft shutter has returned to
its normal position.
Note:
This is the Test Position.
b. To remove the circuit breaker from the
Test position out of the circuit breaker
perform the following:
1. Push the secondary disconnect latch
to the left. This will
unlock the secondary disconnect
plug, allowing it to be removed.
Remove the secondary disconnect
plug.
Removal of the secondary disconnect plug will
trip a closed breaker and discharge the main
closing spring.
!
CAUTION
2. Press the anti-rollout latch
to release the circuit
breaker and pull the circuit
breaker out of the circuit breaker
compartment using the handles.
3. Once the circuit breaker has been
removed and service has been
performed, replace the padlock seal.