LOW VOLTAGE WIRING (Refer to Fig. 3 & Schematic drawings on Page  6)
6.

Connect Supervisory Module 

Connect EOL device (not included) between

pins 1 and 2 of low voltage terminal block.  Pins 1 and 2 should then be
connected to the fire alarm supervisory control module.

Note:

Fire alarm supervisory control module must be of the latching type only.

Pin 1

Alarm Supervisory

Pin 2

Control Module

7.

Connect Fan Power
Note:

Fan  will  not  operate  if  polarity  is  reversed.    Refer  to  low  voltage

schematic on page 6.
Pin 3

-24 VDC

Pin 4

+24 VDC

8.

Connect strobe appliance power

Pin 5

- 16-33 VDC

Pin 6

+16-33 VDC

9.

Attach  heater  assembly  to  back  box  using  (4)  #8-32  x  3/8”  flat  head
screws into heater assembly mounting bosses on back box (see Fig. 1).
Make sure all service wiring is gathered away from the heater and be
careful not to pinch wire under heater assembly. Fan must be mounted
toward 

top 

of

enclosure.  

10.

Wire  strobe  using
Teflon  coated  wire
provided.    (White-
P o s i t i v e / B l a c k -
Negative)

and

attach to the strobe
mounting bosses on
heater assembly.

11.

Record  installation
date on label and in
manual (page 2).

12.

Install  cover  and
gasket with (6) #8-
32 x 3/4” socket cap screws and  (6) flat washers as shown in Fig. 4. 

13.

Turn all power to “ON” position.

Note:

Fan runs continuously.  This system requires three sources of power:

1.  110 or 240 VAC heater on the load side of the fuse holder.
2. 24  VDC  power  source  for  the  circulating  fan.  Check  fan  to  see  if

operating; if not check polarity and reverse then try again

3.  16-33 VDC fire alarm notification circuit for strobes and temperature

warning monitor.

EOL
DEVICE

 

 

 

 

 

   

 

 

HEATER ASSEMBLY

FAN

LOW VOLTAGE

TERMINAL BLOCK

LOW TEMP

WARNING

FAN POWER

STROBE

POWER

LOW TEMP WARNING

THERMOSTAT

 STROBE

(NOT PROVIDED)

STROBE HOOK-UP
WIRE

HEATER ASSEMBLY
MOUNTING SCREW

STROBE MOUNTING BOSS

     

 

1

2

3

4

5

6

-

+

+

-

1

2

WARNING LABEL

 

 

 

 

 

  

 

 

 

 

 

 

 

 

   

 

 

FIGURE 3

Summary of Contents for STI-1229HTR-HAZ

Page 1: ...mperature or environmental conditions exceed the operating range of fire strobe signaling devices Unit requires 24 VDC continuous for fan operation and 110 VAC or 240 VAC for heater as well as power f...

Page 2: ...ng appliances indoors and outdoors and in areas of direct weather exposure 2 When covering fire signaling appliances with the enclosure some light loss occurs Please follow the guidelines listed durin...

Page 3: ...ecognized Component Life 5 Years Continuous Duty WARNING The polarity of the circulating fan is important as it only rotates in one direction with red lead being positive Gasket Material Neoprene Life...

Page 4: ...naling wires must enter thru top conduit and remain separated per NFPA 70 NEC and local codes HIGH VOLTAGE WIRING Refer to Fig 2 5 Connect high voltage Make sure 110 or 240 VAC power is OFF Refer to h...

Page 5: ...h wire under heater assembly Fan must be mounted toward top of enclosure 10 Wire strobe using Teflon coated wire provided White Positive Black Negative and attach to the strobe mounting bosses on heat...

Page 6: ...E PWR FAN PWR TEMP WARNING SUPERVISOR _ _ FAN LOW TEMP WARNING STROBE 16 33VDC 600mA S LOW VOLTAGE CIRCUIT HIGH VOLTAGE CIRCUIT TERMINAL BLOCK TERMINAL BLOCK CHASSIS HEATER EOL DEVICE SUPPLIED BY CUST...

Page 7: ...T 1 PROVIDED SOLID CLEAR COVER WASHER 6 PROVIDED 8 32 x 3 4 in SOCKET CAP SCREW 6 PROVIDED LOW VOLTAGE ELECTRICAL ENTRY IN AREAS WHERE FREQUENT WASH DOWNS OCCUR WASHERS MAY BE USED TO STAND OFF ENCLOS...

Page 8: ...International Europe Ltd Unit 49G Pipers Road Park Farm Industrial Estate Redditch Worcestershire B98 0HU England Tel 44 0 1527 520 999 Fax 44 0 1527 501 999 Freephone 0800 085 1678 UK only E mail in...

Reviews: