Installation Instructions

MOUNT BACKBOX TO WALL 

(Refer to Fig. 1)

1.

Remove appliance heater assembly from back box and set aside.

2.

Mount back box in desired location (wall mount only) using the four #10
x 1-1/2” screws and anchors (provided).  Drill a 1/4” diameter pilot hole
for plastic anchors at spacing in Fig. 1. 

3.

Attach conduit hub to a 3/4” NPT nipple and conduit seal fitting to the back
box, top and bottom.

Note:

A  conduit  seal  fitting  must  be  used  on  both  top  and  bottom

conduit entries as close to the unit as possible.  Use conduit seal Crouse-
Hinds 3/4” EYSX 21 or equivalent. Conduit should be installed according
to applicable NEC and local codes.

4.

Pull wiring into back box.

Note:

High  Voltage  (110  or  240  VAC)  wiring  must  enter  thru  bottom

conduit and low voltage and signaling wires must enter thru top conduit
and  remain  separated  per  NFPA
70, NEC, and local codes.

HIGH VOLTAGE WIRING 

(Refer to Fig. 2)

5. 

Connect high voltage:

Make sure

110  or  240  VAC  power  is  “OFF”.
Refer  to  high  voltage  schematic
diagram on page 6.

110 VAC

240 VAC

Pin 6

AC HOT

L-1

Pin 5

Neutral

L-2

Pin 4

Ground  

Ground

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   

 

 

 

 

 

 

 

 

 

 

   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

     

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

   

 

 

 

 

 

 

 

 

 

 

   

 

 

 

 

 

 

 

    

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

     

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

    

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

3/4 in.(25mm) NPT NIPPLE
(NOT PROVIDED)

  

ENCLOSED BACKBOX

HEATER ASSEMBLY

HIGH VOLTAGE TERMINAL BLOCK

SCREW #8-32 x 3/8 in. 

(4) PROVIDED

STROBE APPLIANCE

GASKET (1) PROVIDED

SOLID CLEAR COVER

WASHER (6) PROVIDED

#8-32 x 3/4 in. SOCKET
CAP SCREW (6) PROVIDED

LOW VOLTAGE

ELECTRICAL ENTRY

1/4 in. (6.3mm)

DIA. HOLE

ANCHOR

(4) PROVIDED

 

SCREW #10 x 1 1/2 in.

(4) PROVIDED

LOW VOLTAGE TERMINAL BLOCK

 

3/4 in. NPT. NIPPLE

(NOT PROVIDED)

HIGH VOLTAGE

ELECTRICAL ENTRY

APPLIANCE

WIRE

3/4 in. NPT HUB (2) PROVIDED (WITHOUT HEATER (1) PROVIDED)

   

 

 

 

 

 

   

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

 

     FIGURE 3

1

 

 

 

 

 

 

  (6.4

 

HEATER ASSEMBLY

HEATER

OVERTEMP SAFETY
THERMOSTAT

HIGH VOLTAGE
TERMINAL BLOCK

PIN 6

PIN 5

PIN 4

2 A FUSE

CONTROL THERMOSTAT

F

 

1

2

3

4

5

6

1

2

FIGURE 1

FIGURE 2

Summary of Contents for STI-1229HTR-HAZ

Page 1: ...mperature or environmental conditions exceed the operating range of fire strobe signaling devices Unit requires 24 VDC continuous for fan operation and 110 VAC or 240 VAC for heater as well as power f...

Page 2: ...ng appliances indoors and outdoors and in areas of direct weather exposure 2 When covering fire signaling appliances with the enclosure some light loss occurs Please follow the guidelines listed durin...

Page 3: ...ecognized Component Life 5 Years Continuous Duty WARNING The polarity of the circulating fan is important as it only rotates in one direction with red lead being positive Gasket Material Neoprene Life...

Page 4: ...naling wires must enter thru top conduit and remain separated per NFPA 70 NEC and local codes HIGH VOLTAGE WIRING Refer to Fig 2 5 Connect high voltage Make sure 110 or 240 VAC power is OFF Refer to h...

Page 5: ...h wire under heater assembly Fan must be mounted toward top of enclosure 10 Wire strobe using Teflon coated wire provided White Positive Black Negative and attach to the strobe mounting bosses on heat...

Page 6: ...E PWR FAN PWR TEMP WARNING SUPERVISOR _ _ FAN LOW TEMP WARNING STROBE 16 33VDC 600mA S LOW VOLTAGE CIRCUIT HIGH VOLTAGE CIRCUIT TERMINAL BLOCK TERMINAL BLOCK CHASSIS HEATER EOL DEVICE SUPPLIED BY CUST...

Page 7: ...T 1 PROVIDED SOLID CLEAR COVER WASHER 6 PROVIDED 8 32 x 3 4 in SOCKET CAP SCREW 6 PROVIDED LOW VOLTAGE ELECTRICAL ENTRY IN AREAS WHERE FREQUENT WASH DOWNS OCCUR WASHERS MAY BE USED TO STAND OFF ENCLOS...

Page 8: ...International Europe Ltd Unit 49G Pipers Road Park Farm Industrial Estate Redditch Worcestershire B98 0HU England Tel 44 0 1527 520 999 Fax 44 0 1527 501 999 Freephone 0800 085 1678 UK only E mail in...

Reviews: