5
Hardwired zone connections
Zone 1, Zone 2 and Zone 3 are the EOLR supervised zones that supports both open circuit
and closed circuit devices and has a response time of 300msec . Maximum zone resistance:
11000 ohms,plus EOLR
Connect closed circuit devices in series in the high (+) side of the loop. The EOL resistor
must be connected in series with the devices, following the last device.
Connect open circuit devices in parallel across the loop. The 10000-ohm EOLR must be
connected across the loop at the last device.
Refer to the Hardwired Zones Connections diagram.
Important:
EOLR(End of Line Resistor): If the EOLR is not at the end of the loop, the zone will not be properly
supervised, and the system may not respond to an open circuit on the zone.
Go to
Main Menu>Parts>EOL Zone
on your hub to set the type and mode of three wired zones.
The number of three zones are set as 100, 101 and 102 in default.
NO
NC
Z2 GND
10K
EOLR
NO
NC
Z3 GND
10K
EOLR
NO
NC
Z1 GND
10K
EOLR
the Hardwired Zones Connections Diagram