1.  Waterflow detectors may not work or operate properly if sprinkler piping being monitored is 

plugged with pipe scale, mud, stones or other foreign material. Sprinkler systems should be 

checked regularly for such blocking material, following the instructions in Chapter 5 of NFPA 

Standard 13A.

2.  Alarms generated by the activation of waterflow detectors may not be received by a central 

station if telephone or other communication lines to the detector are out of service, disabled, 

or open.

WARNING

THE LIMITATIONS OF WATERFLOW ALARM DEVICES

3.  Vane-type waterflow detectors have a normal service life of 10-15 years. Hard water systems, 

however, may substantially reduce waterflow detector service life.

4.  Waterflow detectors are not a substitute for insurance. Building owners should always insure 

property and lives being protected by sprinkler systems.

5.  If valves controlling the water supply to a sprinkler system are closed, vane-type waterflow 

detectors will not work. All valves controlling a sprinkler water supply should be sealed or 

locked in the normally open position. The normally open position should be monitored by a 

sprinkler supervisory switch.

FIGURE 6. DIRECTIONAL COVER

NOTCHED COVER INDICATES FLOW DIRECTION AT A

DISTANCE FROM MULTIPLE VIEWING ANGLES

W0382-00

UL-LISTED
COMPATIBLE
CONTROL PANEL

POWER
24VDC OR
120 VAC

SUGGESTED EOL
RESISTOR

SSM24-X
SSV120-X

NOTE: COMMON AND B-NO
CONNECTIONS WILL CLOSE
WHEN VANE IS DEFECTED, 
I.E.,WHEN WATER IS FLOWING. 
DUAL SWITCHES PERMIT 
APPLICATIONS TO BE COMBINED 
ON A SINGLE DETECTOR.

CONTACT RATINGS

SCHEMATIC OF
INDIVIDUAL
SWITCH IN
“NO WATERFLOW”
CONDITION

A-NC

COM

B-NO

BREAK WIRE AS
SHOWN FOR 
SUPERVISION OF
CONNECTION. DO
NOT ALLOW
STRIPPED WIRE
LEADS TO EXTEND
BEYOND SWITCH
HOUSING. DO NOT
LOOP WIRES.

125 / 250 VAC

24 VDC

10 AMPS

2.5 AMPS

INITIATING

LOOP

W0393-02

FIGURE 7. WFDN WIRING

THREE-YEAR LIMITED WARRANTY

SAFE SIGNAL warrants that the equipment herein shall conform to said descriptions as to all af-

firmation of fact and shall be free from defects of manufacture, labeling, and packaging for a pe-

riod of three (3) years from the invoice date to the original purchaser, provided that representative 

samples are returned to SAFE SIGNAL for inspection. Upon a determination by SAFE SIGNAL 

that a product is not as warranted, SAFE SIGNAL shall, at its exclusive option, replace or repair 

said defective product or parts thereof at its own expense except that Purchaser shall pay all   

shipping, insurance, and similar charges incurred in connection with the replacement of the 

defective product or parts thereof. This Warranty is void in the case of abuse, misuse, abnormal 

usage, faulty installation, or repair by unauthorized persons, or if for any other reason SAFE 

SIGNAL determines that said product is not operating properly as a result of causes other than 

defective manufacture, labeling, or packaging.

  

I56-4045-E 

 

 

  4/21

Summary of Contents for WFDN

Page 1: ...ow Shipping Weight 3 to 6 lbs according to size Enclosure Rating NEMA Type 4 as tested by Underwriters Laboratories Inc U S Patent Numbers 5 213 205 CAUTION Do NOT use any of the WFDN models on copper pipe The clamping forces of the mounting bolts may collapse the pipe sufficiently to prevent the detector from func tioning properly Do NOT install steel or iron pipe sections in copper piping for mo...

Page 2: ... drain the system and remove the detector refer to Maintenance Check for dirt or foreign objects under the gasket and make sure that the pipe surface is not dented Reinstall the detector and check again for leaks Do not proceed until all leaks have been stopped 2 Connect an ohmmeter or continuity tester across the COM and B NO switch terminals The ohmmeter should indicate an open circuit 3 Deflect...

Page 3: ...rational Testing to ensure proper operation Test more often if required by the authority having jurisdiction Under normal conditions Safe Signal waterflow detectors should provide years of trouble free service However if the delay mechanism becomes faulty a replacement kit is available To replace the delay mechanism request Part No FS RT Complete instructions are enclosed with replacement parts Th...

Page 4: ...ESTED EOL RESISTOR SSM24 X SSV120 X NOTE COMMON AND B NO CONNECTIONS WILL CLOSE WHEN VANE IS DEFECTED I E WHEN WATER IS FLOWING DUAL SWITCHES PERMIT APPLICATIONS TO BE COMBINED ON A SINGLE DETECTOR CONTACT RATINGS SCHEMATIC OF INDIVIDUAL SWITCH IN NO WATERFLOW CONDITION A NC COM B NO BREAK WIRE AS SHOWN FOR SUPERVISION OF CONNECTION DO NOT ALLOW STRIPPED WIRE LEADS TO EXTEND BEYOND SWITCH HOUSING ...

Reviews: