BREAK WIRE AS SHOWN FOR

SUPERVISION OF CONNECTIO N.

DO NOT ALLOW STRIPPED WIRE

LEADS TO EXTEND BEYOND

SWITCH HOUSING. DO NOT

LOOP WIRES.

W0177-00

WARNING

To prevent ignition of hazardous atmospheres, disconnect cir-

cuits before removing cover. Keep cover closed while circuits are 

live. Conduit runs must have sealing fittings connected within 

18” of the enclosure.

Installation

1.  Back out cover tamper set screw and remove cover (Fig. 1). 

2.  Mounting the Switch

  The device is designed to be mounted in the upright position; 

side mounting is also acceptable. Locate it where vibration, 

shock, and mechanical loading are minimal. Refer to piping 

diagram above (Figures 2 and 3).

  a.  Mount the device directly to the line via the 1/2

 NPT pres-

sure connection. The use of teflon pipe sealant tape is rec-

ommended. Be sure the fitting is tight enough to prevent 

leaks.

  b. Apply tightening torque to the brass hex portion of the 

device.

W0180-00

Figure 3. Typical piping diagram for EPS120EXP

DRY

PIPE

VALVE

OS & Y

VALVE

WATER

BY-PASS

TEST

VALVE

LOCAL ALARM

SHUT OFF

VALVE

WATER

MOTOR

GONG

CHECK

VALVE

EPS40EXP

CHECK

VALVE

AIR LINE

SHUT-OFF

VALVE

INSTALL

BLEEDER

VALVE FOR

TESTING

EPS10EXP

DRY SYSTEM

WIRE TO SUPERVISORY

CIRCUIT OF FIRE ALARM

CONTROL PANEL

WIRE TO ALARM

INDICATING CIRCUI

OF FIRE ALARM

CONTROL PANEL

TO

SPRINKLER

SYSTEM

Table 1. Electrical connections (referenced at  
factory settings):

CAUTION

High voltage. Electrocution hazard. Do not handle live AC wir-

ing or work on a device to which AC power is applied. Doing so 

may result in severe injury or death.

3. Wire the device in accordance with the National Electrical 

Code. Two 1/2

 NPT conduit entry holes have been provided 

in the mounting base to accept explosion proof conduit fit-

tings. If necessary, remove conduit entry plug with 3/8” 

square wrench.

4.  Connect wiring to terminals (see Figure 4 and Table 1).

Adjustments To Factory Settings

WET

SYSTEM

ALARM

CHECK

VALVE

OS & Y

VALVE

OS & Y

VALVE

WATER

BY-PASS

VALVE

AIR

PRESSURE

SUPPLY

BLEEDER

TEST

VALVE

EPS120EXP

LOCAL ALARM

SHUT OFF

VALVE

RETARD

WATER

MOTOR

GONG

W0181-00

Figure 4. Switch location:

Figure 2. Typical piping diagram for EPS40EXP

SW2

SW1

SWITCHES AT NORMAL SYSTEM PRESSURE

SWITCHES AT LOW TRIP POINT

SW1

SW2

MODELS EPS40EXP, EPS120EXP

SWITCHES AT HIGH TRIP POINT

SW1

SW2

B

COM

A

B

COM

A

B

COM

A

A

COM

B

A

COM

B

A

COM

B

SWITCH # 1

COMMON 

TERMINALS

TERMINAL

"A"

TERMINAL

"B"

SWITCH #2

GROUND

SCREW

(GREEN)

W0175-00

(HIGH SWITCH)

W0179s-00

  