Sacred Sun OPzV Series Technical Manual Download Page 9

 

Performance Data 

 

Constant current discharge data 

Table 2-1 OPzV Battery Constant Current Discharge Data Sheet (Amperes, 25 

 

Constant Current Discharge Data Sheet (25

)-------Amperes(A) 

Battery Type 

End Voltage 

(V/cell) 

Discharge Time 

5min 

10min 

15min 

20min 

30min 

1 h 

2 h 

3 h 

5 h 

6 h 

8 h 

10 h 

20 h 

24 h 

48 h  100 h  120 h  240 h 

4 OPzV 200 

1.65 

302   

270   

236   

205   

174   

115   

75.3 

58.9 

40.5 

34.3 

26.5 

22.6 

11.8 

9.97    5.40    2.80    2.37    1.21   

1.70 

283   

253   

219   

195   

169   

110   

71.3 

55.7 

38.3 

32.4 

25.5 

21.8 

11.5 

9.71    5.33    2.77    2.35    1.20   

1.75 

270   

242   

212   

184   

160   

105   

67.3 

52.8 

36.3 

31.2 

24.5 

21.0 

11.2 

9.49    5.26    2.75    2.33    1.19   

1.80 

255   

230   

203   

177   

154   

100   

63.6 

50.0 

34.0 

29.1 

23.5 

20.0 

10.9 

9.31    5.20    2.71    2.31    1.17   

1.85 

240   

217   

192   

167   

145   

95   

60   

47.3 

32.6 

28.1 

22.3 

18.9 

10.6 

9.1 

5.13    2.67    2.27    1.15   

5 OPzV 250 

1.65 

378   

338   

295   

257   

218   

144   

94.2 

73.6 

50.7 

42.9 

33.2 

28.3 

14.8  12.47    6.75    3.50    2.97    1.52   

1.70 

354   

317   

274   

243   

212   

138   

89.2 

69.7 

47.9 

40.5 

31.8 

27.3 

14.4  12.13    6.66    3.47    2.94    1.50   

1.75 

338   

303   

265   

230   

200   

132   

84.2 

66.0 

45.4 

39.0 

30.6 

26.3 

14.0  11.86    6.58    3.43    2.92    1.48   

1.80 

319   

288   

254   

221   

193   

125   

79.5 

62.5 

42.5 

36.3 

29.4 

25.0 

13.6  11.64    6.50    3.39    2.88    1.47   

1.85 

300   

272   

240   

209   

182   

119   

75   

59.2 

40.8 

35.1 

27.8 

23.7 

13.2 

11.3 

6.41    3.33    2.84    1.44   

6 OPzV 300 

1.65 

453   

405   

354   

308   

261   

173   

113.0 

88.3 

60.8 

51.5 

39.8 

33.9 

17.7  14.96    8.10    4.20    3.56    1.82   

1.70 

425   

380   

329   

292   

254   

165   

107.0 

83.6 

57.5 

48.6 

38.2 

32.7 

17.3  14.56    7.99    4.16    3.53    1.80   

1.75 

405   

363   

318   

276   

240   

158   

101.0 

79.2 

54.5 

46.8 

36.7 

31.5 

16.8  14.23    7.89    4.12    3.50    1.78   

1.80 

383   

345   

305   

265   

231   

150   

95.4 

75.0 

51.0 

43.6 

35.3 

30.0 

16.3  13.97    7.80    4.07    3.46    1.76   

1.85 

360   

326   

288   

251   

218   

143   

90   

71.0 

48.9 

42.1 

33.4 

28.4 

15.9 

13.6 

7.69    4.00    3.41    1.73   

5 OPzV 350 

1.65 

487   

453   

413   

359   

290   

202   

133.2 

103.0 

70.9 

60.1 

45.5 

36.7 

20.0  17.20    9.45    4.89    4.10    2.10   

1.70 

450   

423   

384   

341   

279   

193   

129.5 

97.5 

67.1 

56.7 

44.6 

36.2 

19.7  16.74    9.32    4.85    4.07    2.06   

1.75 

423   

404   

371   

322   

261   

184   

127.0 

92.4 

63.6 

54.6 

42.8 

35.6 

19.4  16.42    9.21    4.80    4.03    2.03   

1.80 

398   

386   

356   

309   

249   

175   

121.0 

87.5 

59.5 

50.9 

41.2 

35.0 

18.9  16.14    9.10    4.75    3.99    2.01   

1.85 

381   

360   

336   

293   

230   

167   

115   

82.8 

57.1 

49.1 

39.0 

34.1 

18.3 

15.6 

8.97    4.67    3.93    1.98   

6 OPzV 420 

1.65 

584   

544   

496   

431   

348   

242   

159.8 

123.6 

85.1 

72.1 

54.6 

44.0 

24.0  20.64   11.34    5.87    4.92    2.52   

1.70 

540   

508   

461   

409   

335   

231   

155.4 

117.0 

80.5 

68.0 

53.5 

43.4 

23.6  20.09   11.19    5.82    4.88    2.47   

1.75 

508   

485   

445   

386   

313   

221   

152.4 

110.9 

76.3 

65.5 

51.4 

42.7 

23.3  19.70   11.05    5.76    4.84    2.44   

1.80 

478   

463   

427   

371   

299   

210   

145.2 

105.0 

71.4 

61.0 

49.4 

42.0 

22.7  19.37   10.92    5.70    4.79    2.41   

1.85 

457   

432   

403   

351   

276   

200   

138   

99.4 

68.5 

58.9 

46.8 

40.9 

22.0 

18.8  10.77    5.60    4.72    2.38   

 
 
 
 
 
 
 
 
 
 
 
 

Electrical

 Characteristics

 

 

07

 

Summary of Contents for OPzV Series

Page 1: ......

Page 2: ...Characteristics 1 Discharge Characteristic Curve 06 2 Performance Data 07 Chapter III Operation and Maintenance 1 Security Instruction 17 2 Discharge 18 3 Temperature Effect On Battery Capacity 18 4...

Page 3: ...features Positive plates Negative plates Separators Container and Lid Electrolyte Terminal posts Posts sealing Vents Plates suspension Inter cell connectors Terminal hardware Terminal adaptor Product...

Page 4: ...rage Systems Emergency power UPS and EPS units Transportation Standards IEC60896 21 22 2004 IEC61427 2014 DIN43539 T5 1984 DIN40742 1999 BSEN 61427 2002 YD T1360 2005 GB T 22473 2008 Eurobat guide Ins...

Page 5: ...OPzV 800Ah to 1500Ah OPzV 2000Ah OPzV 2500Ah 3000Ah 12V OPzV 50Ah 100Ah 150Ah Product Introduction 03...

Page 6: ...66 206 471 503 5 37 3 4268 0 50 M10 20 F 7 OPzV 500 2 500 166 206 471 503 5 37 3 4268 0 50 M10 20 F 6 OPzV 600 2 600 145 206 646 678 5 44 5 4606 0 40 M10 20 F 8 OPzV 800 2 800 191 210 646 678 5 60 0 6...

Page 7: ...to lead dioxide but negative plate has not reached fully charged stage the process of active substance in negative plate transforming to spongy lead is not finished oxygen gas generated in positive p...

Page 8: ...e 25 Voltage curve of simulation wind energy system cycle application Figure 2 2 Voltage curve of simulation wind energy system cycle application Charge characteristic curve under different depth of d...

Page 9: ...PzV 300 1 65 453 405 354 308 261 173 113 0 88 3 60 8 51 5 39 8 33 9 17 7 14 96 8 10 4 20 3 56 1 82 1 70 425 380 329 292 254 165 107 0 83 6 57 5 48 6 38 2 32 7 17 3 14 56 7 99 4 16 3 53 1 80 1 75 405 3...

Page 10: ...2 4 52 1 70 1025 893 831 771 644 440 285 3 222 9 153 3 129 6 101 9 87 2 46 3 39 60 21 31 10 35 8 68 4 51 1 75 947 843 777 717 624 421 269 3 211 2 145 3 124 8 97 9 84 0 44 0 38 40 21 04 10 32 8 64 4 48...

Page 11: ...0 836 0 575 0 486 0 382 0 327 0 173 0 145 6 79 90 39 66 33 57 17 18 1 75 3443 3086 2729 2376 2040 1580 1010 0 792 0 545 0 468 0 367 0 315 0 168 0 142 3 78 90 39 18 33 27 17 07 1 80 3251 2933 2588 230...

Page 12: ...315 0 197 3 147 8 120 0 102 5 79 7 69 2 34 9 29 90 16 54 8 65 7 48 3 67 1 70 714 659 590 537 447 300 0 189 8 142 5 114 8 98 0 78 5 67 8 33 5 29 20 16 44 8 52 7 40 3 63 1 75 670 633 570 516 432 291 0...

Page 13: ...07 1 70 1723 1572 1417 1293 1088 765 6 506 0 380 0 310 5 262 9 211 4 174 5 92 0 79 47 42 67 20 70 17 36 9 02 1 75 1639 1509 1366 1245 1056 752 0 494 0 372 0 302 9 255 2 205 7 168 0 90 7 76 76 42 13 20...

Page 14: ...4 3 345 0 291 75 160 00 79 28 67 13 34 35 1 75 5742 5319 4816 4420 3840 2840 0 1864 0 1404 0 1135 7 957 1 771 4 630 0 340 0 284 25 158 00 78 26 66 56 34 11 1 80 5138 4863 4592 4240 3720 2780 0 1832 0...

Page 15: ...ed by skilled personnel only Used batteries must be recycled and disposed properly as improper disposal of batteries is harmful to the environment and health Used batteries shall be properly disposed...

Page 16: ...erature of 25 discharge over 60 DOD is prohibited except protective measure is adopted such as raising temperature Temperature The operation temperature range is 25 60 All the performance data is meas...

Page 17: ...vice life curve Floating Charge and Equalizing charge Floating charge Floating operation is the best operation condition for battery In floating operation the battery keep fully charged state under th...

Page 18: ...tion the battery bank should be supplementary charged The battery is out of work beyond 6 months Running in full floating operation for a long term but not discharge under more than 40 C10 capacity th...

Page 19: ...can be regarded as the fully charged symbol Refer to the required time as table 3 3 In constant voltage case the charge current keep unchanged for 3 hours in the final stage of charge Charge voltage s...

Page 20: ...installation instructions Battery which is separately installed on rack and cabinets should be connected by bolts to the foundation Battery racks or cabinets should be properly installed according to...

Page 21: ...tus of batteries and equipment and to prevent accidental damage regular maintenance is required Periodically check and record the measurements using the following method for batteries used in UPS syst...

Page 22: ...for cleaning 2 If there is crystalline or liquid clean it with a dry cloth Check and tighten the safety valve 2 2 Quarterly Maintenance Inspection Items In addition to the monthly maintenance items a...

Page 23: ...capacity to be maintained must be more than 80 and in energy storage use more than 60 of the reference capacity Recovery test measure and record various parameters specified in the monthly quarterly...

Page 24: ...No 1 Shengyang Road Qufu City Shandong Province 273100 P R China Tel 0086 537 4422313 Fax 0086 537 4411980 E mail sales sacredsun cn...