background image

Maintenance 

1.  Cleaning Notes: 

 

Battery appearance, terminal area and working environment must be kept clean and dry. 

 

In battery cleaning process, avoid use of electrostatic cleaning tools. 

 

Clean the battery with damp cloth. Do not use of gasoline, alcohol or other organic solvents;   

also do not use cloth containing these substances. 

2.  Inspection and Maintenance 

VRLA batteries are not maintenance-free batteries, battery operation process gradually   

changes with time. In order to ensure good battery usage, operational management and   

control are very important. To understand the operation status of batteries and equipment   

and to prevent accidental damage, regular maintenance is required. Periodically check   

and record the measurements using the following method for batteries used in UPS system   

room and base station (including outdoor station) site. 

2.1 Monthly Maintenance Inspection Items 

Item 

Content 

Standard 

Maintenance 

1-Temperature 

Detection 

1-Measure and record 

battery terminal and 

container temperature 

by using infrared 

thermometer. 

2-Use infrared 

thermometer to measure 

ambient temperature. 

1-Ambient Temp:       

-20

~+45

 

2-Recommended 

Temperature:   

25±5

 

1-Check that the battery temperature 

compensation functions are turned on and 

that the battery temperature probe is 

properly installed. 

2-Check that the room temperature 

conditioning equipment such as 

air-conditioning is turned on. 

2-

 

Battery Float 

Voltage 

Measurement 

Measure floating voltage 

on positive and negative 

terminal of the battery 

group with multimeter. 

Measurement and 

control module 

display operating 

voltage differences 

within 0.05V 

If the monitoring module shows 

inconsistency even after adjusting, replace 

or repair it. 

3-Battery 

Appearance 

Inspect the battery 

container for bulging, 

leakage and damage. 

Normal 

Appearance 

Confirm  the  reason  for  any  abnormal 

appearance,  if  it  affects  normal  use, 

replace the battery. 

Check for dirt stains 

Clean Appearance 

Clean dust and dirt with damp cloth 

Inspect the connection 

cables, terminals, etc. 

for oxidation, rust & 

other abnormalities 

No oxidation, rust 

If  you  find  oxidation  or  rust,  replace  the 

connecting  wire,  and  swab  terminal  with 

Vaseline etc.   

 

 

Operati

on 

and

 m

aintenanc

e

 

 

12

 

Summary of Contents for DCS Series

Page 1: ...DCS Series Deep Cycle Solar Battery Technical Manual SHANDONG SACRED SUN POWER SOURCES CO LTD...

Page 2: ...stic Curve 04 2 Charging Characteristic Curve 05 3 Cycle Performance Curve 05 4 Performance Data 06 Chapter III Operation and Maintenance 1 Safety Instructions 07 2 Operation Parameters 08 3 Factors I...

Page 3: ...tive plates Negative plates Separators Container and Lid Posts sealing Terminal posts Electrolyte Vents Plates suspension Inter cell connectors Terminal hardware Product Introduction 01 Thick flat pas...

Page 4: ...age V Nominal Capacity Ah 25 Dimensions mm Weight kg Short Circuit Current A Internal Resistance m 25 Terminal Type Terminal Layout C10 1 80V cell Length Width Height Total Height DCS12 50 12 50 350 1...

Page 5: ...negative plate has not reached fully charged stage the process of active substance in negative plate transformed to spongy lead is not finished oxygen gas generated in positive plate reaches the nega...

Page 6: ...1 describes the discharge curves of DCS Series at different discharge rate at ambient temperature 25 Table 2 1 describes the end voltage at different discharge rate Figure 2 1 Discharge characteristic...

Page 7: ...arged the charge capacity can be as high as the 104 of the discharged capacity Figure 2 2 Charge characteristic curve Cycle Performance Curve At different depth of discharge the battery cycle life is...

Page 8: ...16 0 12 0 9 60 5 60 2 28 1 200 1 056 0 562 1 90V 48 0 34 4 21 8 14 4 10 9 8 72 5 10 2 08 1 126 0 982 0 516 Constant power discharge data Table 2 3 DCS Series Battery Constant Power Discharge Data Shee...

Page 9: ...ed by skilled personnel only Used batteries must be recycled and disposed properly as improper disposal of batteries is harmful to the environment and health Used batteries shall be properly disposed...

Page 10: ...Hour in short is Ah Usually discharge rate is indicated through the suffix of C such as C10 means capacity at 10 hours discharge rate C3 means capacity at 3 hours discharge rate Battery capacity consi...

Page 11: ...rted to C25 according to the following formula In the formula T Discharge temperature CT Capacity at temperature of T k Temperature coefficient k 0 006 at C10 discharge k 0 008 at C3 discharge k 0 01...

Page 12: ...2 35 2 50V When battery float equalizing charge voltage according to the temperature compensation coefficient calculated values over the range according to the corresponding upper limit or lower limi...

Page 13: ...orage temperature Maximum storage times Freshening charge intervals Recommended freshening charge method 20 25 Every 6 months Using constant current 0 1C10A 0 2C10A to charge battery bank till battery...

Page 14: ...tainer temperature by using infrared thermometer 2 Use infrared thermometer to measure ambient temperature 1 Ambient Temp 20 45 2 Recommended Temperature 25 5 1 Check that the battery temperature comp...

Page 15: ...Item Content Standard Maintenance 1 Measurement of each battery s floating voltage Measure each battery s floating voltage by using multimeter Battery floating voltage differential pressure must meet...

Page 16: ...capacity to be maintained must be more than 80 and in energy storage use more than 60 of the reference capacity Recovery test measure and record various parameters specified in the monthly quarterly...

Page 17: ...No 1 Shengyang Road Qufu City Shandong Province 273100 P R China Tel 0086 537 4422313 Fax 0086 537 4411980 E mail sales sacredsun cn...