When automatic functions are running unit will show information icon
Preheater on
1
Bypass open
Defrost mode
2
Icon is displayed when preheater
signal is on. It is automatically
activated when supply air temperature
is lower than 16,5ºC
Icon is displayed when the mechanical damper,
bypass, is open. Open conditions: outdoor
temperature is lower than 25ºC and indoor
temperature is higher than 25ºC.
Icon is displayed when antifrost mode is running. It is
activated when outdoor temperature is lower than -2ºC.
Each hour, the unit will stop supply fan 5 minutes, while
the exhaust fan is continue working at maximum speed
Under power off state, push the 4 buttons at the same time to enter
into airflow setting menu.
Use to select the mode that fits better with the air demand of the facility
“Custom Num: 01”---- fan mode 1
“Custom Num: 02”---- fan mode 2
“Custom Num: 03”---- fan mode 3
“Custom Num: 04”---- fan mode 4
Standard With ---- fan mode 1
Push to save setting and back to personalized setting interface
7.10. Additional icon information
7.11. Airflow settings (for installer only)
airflow table (model 200)
Boost
(M3/h)
High
(M3/h)
Middle
(M3/h)
Low
(M3/h)
Travel mode
(M3/h)
Custom Num: 01 fan mode 1
150
140
100
75
30
Custom Num: 02 fan mode 2
140
120
75
60
30
Custom Num: 03 fan mode 3
120
100
75
50
30
Custom Num: 04 fan mode 4
100
80
60
50
30
airflow table (model 300)
Boost
(M3/h)
High
(M3/h)
Middle
(M3/h)
Low
(M3/h)
Travel mode
(M3/h)
Custom Num: 05 fan mode 1
300
245
180
130
100
Custom Num: 06 fan mode 2
245
180
130
100
80
Custom Num: 07 fan mode 3
210
180
130
100
60
Custom Num: 08 fan mode 4
180
130
100
80
60
8. Start-up
• Once the installation is completed, make sure the unit is properly connected prior to turning it on.
•
Carry out a first start-up of the unit to check that it is operating properly without vibrations or abnormal noises.
•
Check that the actual consumption of the motors does not exceed what is indicated on the equipment label and ensure it is not
overheating
• Always disconnect the unit from the electrical power grid prior to conducting any checks on the unit.
1. The unit only provides the activation signal, it does not include the supply terminals fot the preheater.
2. To prevent ice deposits inside the equipment, the unit will work automatically under antifrost mode and can not be operated by the user.
Summary of Contents for SENSE-200
Page 1: ...SENSE 200 SENSE 300 Manual del Usuario User Manual www sach air com ESPA OL ENGLISH...
Page 8: ...P1 con la posicion de las bocas de fabrica 6 5 Soportes con dos posibles posiciones...
Page 18: ......
Page 25: ...ENGLISH P1 Factory default installation method 6 5 Support brackets positions...
Page 35: ......