Maintenance instructions
29/38
0175-168 - ENG
Rev. 2005.09
Operating Manual - SAB 202
Checking the oil
Note:
It is not advisable to reuse oil drained from compressor or plant. This oil has absorbed the moisture in the
air and is likely to cause operating problems.
Always turn off the power to the heating rod before draining off oil.
Operating hours between main inspections
See chart for main inspections
Service schedules
Number of operating hours from initial
start-up and after each main inspection
(see footnote)
20,000h
30,000h
40,000h
HCFC
R717
HCFC
R717
HCFC
R717
50
●
●
●
●
●
200
●
●
●
●
●
●
1,000
●
●
●
●
●
●
2,500
●
●
●
●
●
●
5,000
●
X
●
X
●
X
10,000
X
●
X
●
X
●
15,000
✡
✡
●
X
●
X
20,000
●
●
●
●
25,000
✡
✡
X
X
30,000
●
●
35,000
✡
✡
40,000
●
It is advisable to assess the oil as described in the section “Activities during service inspection” in the
Service manual.
X
It is advisable to assess the oil as described in the section “Activities during service inspection” in the
Service manual.
If this assessment is not made, the oil charge
must
be replaced with fresh oil.
✡
The oil charge must be replaced with fresh oil.
Service schedules after initial start-up of compressor.
Service schedules after each main inspection.