49
CRS–ECM
CRS–ECM
version
Carisma
MIN
MED
MAX
MIN
MED
MAX
MIN
MED
MAX
5
(E)
7
(E)
9
(E)
4
(E)
6
(E)
8
(E)
4,5
(E)
6,5
(E)
8,5
(E)
240
35
1,53
1,14
1,44
8,9
4,4
24
45
52
36
43
280
50
1,73
1,30
1,60
11,1
5,4
32
48
54
39
45
325
65
1,94
1,47
1,78
13,7
6,4
43
52
58
43
49
420
35
2,63
1,99
2,29
9
2,8
30
45
51
36
42
485
50
2,94
2,24
2,53
11
3,3
44
49
55
40
46
560
65
3,27
2,51
2,79
13,4
3,9
64
52
58
43
49
720
35
4,16
3,22
3,48
13,2
4,8
50
50
56
41
47
820
50
4,57
3,57
3,80
15,6
5,6
71
53
60
44
51
950
65
5,06
4,00
4,20
18,8
6,7
102
56
63
47
54
9066363
9069222
9066368
Inverter power
Speed
Air flow
(E)
Available pressure
(E)
Cooling total emission
(E)
Cooling sensible emission
(E)
Heating
(E)
Dp Cooling
(E)
Dp Heating
(E)
Fan
(E)
Sound power outlet
(E)
Sound power radiated
(E)
Sound pressure outlet
(*)
Sound pressure radiated
(*)
Plenum code
(E)
m
3
/h
Pa
kW
kW
kW
kPa
kPa
W
dB(A)
dB(A)
dB(A)
dB(A)
M
odel
CRS−ECM 33+1
CRS−ECM 23+1
CRS−ECM 13+1
(E) = Eurovent certified performance.
(*) = The sound pressure levels are 9 dB(A) lower than the sound power levels
and apply to the reverberant field of a 100 m
3
room and a reverberation time of 0.5 sec.
4 pipe units.
The following standard rating conditions are used:
CRs
−
eCM
units
with
1
Row
additional
Coil
EUROVENT Certification
www.eurovent-certification.com
COOLING
Entering air temperature + 27°C d.b.
+ 19°C w.b.
Water temperature
+ 7°C E.W.T. + 12°C L.W.T.
HEATING
Entering air temperature + 20°C
Water temperature
+ 65°C E.W.T. + 55°C L.W.T.