ADDITIONAL FUNCTIONS
Holding down the C button
By keeping pressed the
C
pushbutton for 5 seconds, the measured weight is zeroed. If this
button is pressed for 5 seconds with load inside the car, once the load is removed the
699Plus will show a negative measure. Pressing and holding down the button again, new
zero is stored and the display will show positive load once weight is placed inside the cabin.
Zero is stored into EEprom memory.
Compensation Chain and Relays block function
When doors are closed, feed between
INPUT1
(terminal 5) and
EXGND
(terminal 6 =
GND/common reference) a voltage coming from door relay where:
0 Vac/dc = lift DOOR OPEN
.
+12/24Vdc (9/18 Vac) = lift DOOR CLOSED.
In case of black out, send cabin to lowest floor and reconnect the 699Plus control unit again
to the power supply. 699Plus will automatically re-check and activate the compensation
function.
699 Relay test procedure
Press
+
C
buttons and press RESET until display shows TREL.
Press
to test Relay 1,
to test Relay 2 or
E
to test Relay 3.
Press
Reset
button to return to normal measurement operation.
Er.24 Reset
1.
Reset the unit
(right side push-button) keeping pressed the
+
+
C
buttons, until
display shows
ECLR
2.
Releasing the three front buttons, display shows
CLRA
, to indicate You initiated the
procedure
3.
Press once
E
button to clear Er.24. Display shows
MEMO
to confirm.
4.
Press
C
button to end procedure.
5.
Display shows
SAVE
and then will reset of 699Plus.
6.
ECAL
is displayed to warn that controller is UNCALIBRATED and a NEW CALLIBRATION
MUST BE DONE.
At this moment, the 699 unit
IS UNCALIBRATED
and a NEW CALIBRATION has to be
performed, after having removed the condition that generated the wrong calibration.
Measurement is blinking
, as it is based on the
default calibration parameters (
for
troubleshooting purposes),
to indicate that a new calibration is needed
.
Electrical Connection limits
Power supply
(Terminal 1 and 2):
+ 24 Vdc (-20/+10%) Current 50 mA with inrush current of max 1 A
+ 12 Vdc (-20/+10%) Current 100 mA with inrush current of max 300 mA
Relay
- resistive loads (Terminals from 7 to 15): 1 A 24Vdc / 125 Vac
Digital I/O inputs
(Terminals from 4 to 6): opto-ins12/24 V ac/dc (-20/+10%)
Respect all the relevant safety and electrical regulations.
CE DECLARATION
699 digital conditioner complies with the requirements of the following norms:
EN 61326-1(1997) + A1(1998) + A2(2001) + A3(2003); EN 61000-6-2(2001); EN 61000-3-2(2000) + A2(2005);EN 61000-3-
3(1995) + A1(2001); EN 61000-4-2 (1995) + A1(1998) +A2(2001); EN 61000-4-3(2002) + A1(2002); EN 61000-4-4(1995) +
A1(2001) + A2(2001); EN 61000-4-5(1995) + A1(2001); EN61000-4-6(1996) + A1(2001); EN 61000-4-8(1993)+A1(2001); EN
61000-4-11(2004)
Notice:
The information in this manual is subject to change without notice.S2Tech shall not be liable for technical or editorial
errors or omissions contained herein, nor for incidental or consequential damages resulting from the furnishing, performance,
or use of this material. This manual contains information protected by copyright. No part of this manual may be photocopied,
or reproduced in any form, or translated without prior written consent from S2Tech.
Z:\Manuali\699 Plus Load Sentry MANU\699Plus LoadSentry MANU UK 050517.docx
Document history
3.3
050517
1.38
5.1
SP/CF
CF/CM
Rev
Date
Description
FW
HW
Writer
Check