ADDITIONAL FUNCTIONS

Holding down the C button

By keeping pressed the

C

pushbutton for 5 seconds, the measured weight is zeroed. If this

button is pressed for 5 seconds with load inside the car, once the load is removed the
699Plus will show a negative measure. Pressing and holding down the button again, new
zero is stored and the display will show positive load once weight is placed inside the cabin.
Zero is stored into EEprom memory.

Compensation Chain and Relays block function

When doors are closed, feed between

INPUT1

(terminal 5) and

EXGND

(terminal 6 =

GND/common reference) a voltage coming from door relay where:

0 Vac/dc = lift DOOR OPEN

.

+12/24Vdc (9/18 Vac) = lift DOOR CLOSED.

In case of black out, send cabin to lowest floor and reconnect the 699Plus control unit again
to the power supply. 699Plus will automatically re-check and activate the compensation
function.

699 Relay test procedure

Press

+

C

buttons and press RESET until display shows TREL.

Press

to test Relay 1,

to test Relay 2 or

E

to test Relay 3.

Press

Reset

button to return to normal measurement operation.

Er.24 Reset

1.

Reset the unit

(right side push-button) keeping pressed the

+

+

C

buttons, until

display shows

ECLR

2.

Releasing the three front buttons, display shows

CLRA

, to indicate You initiated the

procedure

3.

Press once

E

button to clear Er.24. Display shows

MEMO

to confirm.

4.

Press

C

button to end procedure.

5.

Display shows

SAVE

and then will reset of 699Plus.

6.

ECAL

is displayed to warn that controller is UNCALIBRATED and a NEW CALLIBRATION

MUST BE DONE.

At this moment, the 699 unit

IS UNCALIBRATED

and a NEW CALIBRATION has to be

performed, after having removed the condition that generated the wrong calibration.

Measurement is blinking

, as it is based on the

default calibration parameters (

for

troubleshooting purposes),

to indicate that a new calibration is needed

.

Electrical Connection limits
Power supply

(Terminal 1 and 2):

+ 24 Vdc (-20/+10%) Current 50 mA with inrush current of max 1 A
+ 12 Vdc (-20/+10%) Current 100 mA with inrush current of max 300 mA

Relay

- resistive loads (Terminals from 7 to 15): 1 A 24Vdc / 125 Vac

Digital I/O inputs

(Terminals from 4 to 6): opto-ins12/24 V ac/dc (-20/+10%)

Respect all the relevant safety and electrical regulations.

CE DECLARATION

699 digital conditioner complies with the requirements of the following norms:
EN 61326-1(1997) + A1(1998) + A2(2001) + A3(2003); EN 61000-6-2(2001); EN 61000-3-2(2000) + A2(2005);EN 61000-3-
3(1995) + A1(2001); EN 61000-4-2 (1995) + A1(1998) +A2(2001); EN 61000-4-3(2002) + A1(2002); EN 61000-4-4(1995) +
A1(2001) + A2(2001); EN 61000-4-5(1995) + A1(2001); EN61000-4-6(1996) + A1(2001); EN 61000-4-8(1993)+A1(2001); EN
61000-4-11(2004)

Notice:

The information in this manual is subject to change without notice.S2Tech shall not be liable for technical or editorial

errors or omissions contained herein, nor for incidental or consequential damages resulting from the furnishing, performance,

or use of this material. This manual contains information protected by copyright. No part of this manual may be photocopied,
or reproduced in any form, or translated without prior written consent from S2Tech.
Z:\Manuali\699 Plus Load Sentry MANU\699Plus LoadSentry MANU UK 050517.docx

Document history

3.3

050517

1.38

5.1

SP/CF

CF/CM

Rev

Date

Description

FW

HW

Writer

Check

Reviews: