PREMASGARD
®
1160 / PREMASREG
®
1160
1
st
line showing volume flow rate value
2
nd
line showing corresponding measurement unit
At the PREMASREG
®
1161 in addition, the switching
status of the relay is indicated in the second line :
○
Circle empty = relay in idle state
●
Circle solid = relay activated
At putting in operation, DIP switch 5 enables switching
over to displaying pressure values.
1. The device must be operative for at least 60 minutes before zero
point setting is started.
2. Connect pressure connections P (+) and P (–) with a hose
(differential pressure between the connections = 0 Pa).
3. Requirement: DIP-switch 6 is set to OFF.
4. To set the zero point, press pushbutton for 10 seconds without
interruption.
By pressing the button, a countdown of ca. 10 seconds is started.
The yellow LED is flashing and the countdown counter is shown on the
display (optional).
After the countdown period has elapsed, zero point calibration takes
place. This is indicated by continuous light of the LED, and on the
display (optional) by switching from "AUTO 0" to "PROG 0".
Note: When releasing the pushbutton during countdown (counter > 0),
zero point setting is immediately aborted !
Automatic offset correction:
1 2 3 4
LED
auto
zero
up down
select
1 2 3 4 5 6
ON
DIP
min. max.
Offset
Offset
auto
zero
GND
GND
P
a
V+
Pushbutton
Zero point settin
Plug for display
Offset correction
see graph
ca. ± 10%
DIP switches
Plug for
display
1
st
line showing actual pressure up to the measuring range limit.
Pa = Pascal
Precondition: DIP switch 5 is set to ON.
select
Pressing for more than 5 seconds =>
switches to setup mode
A short push following thereafter =>
switches to the next input value
respectively terminates setup mode
up
▲
(arrow pointing up) increases the input value. Keeping it
depressed increases the increment step by step by
which the parameter is increased.
down
▼
(arrow pointing down) decreases the input value.
Pressing for longer increases the increment step by
step by which the parameter is decreased.
Volume flow rate indication on the display:
Pressure reading at the display:
Setup button assignment:
Input k-value: 1…3000
1
st
line showing set value
2
nd
line showing type, flashing at a one-second cycle
Input measurement unit:
(Displayed unit of volume flow rate)
0 = m
3
⁄ s, 1 = m
3
⁄ min, 2 = m
3
⁄ h, 3 = liters ⁄ s, 4=liters ⁄ min, 5 = liters ⁄ h
Input volume flow rate at max. output signal 10 V:
Setting (measuring range end value ^= 10 V)
10% to 100% of max. possible volume flow rate
in the selected measurement unit.
Input relay switching threshold at volume flow rate:
Setting (relay switchpoint)
10% to 100% of max. possible volume flow rate
in the selected measurement unit.
Setup mode
Calculation formula – k-factor:
k = q ⁄
√(Pi)
q = volume flow rate in m
3
⁄ h
(Pi) = differential pressure in Pa
Adjustment range: 1…3000