PREMASREG

®

 716x - VA  ID

   

Rev.  ID20 - V11

The electronic 

PREMASREG

® 

716x - VA

 pressure sensor and switch is equipped with measuring functions for volume flow, differential pressure, 

filter monitoring and liquid level detection based on pressure measurement in clean air. The devices with  a housing made from impact-resistant  
plastic, with cable gland or M12 connector according to DIN EN 61076-2-101 and pressure port by stainless steel quick connect (pipe fitting  
optional) are fitted with one switching output, one continuous output and one backlit display for setting the switching point and displaying the  
ACTUAL values. The piezoresistive measuring element guarantees a high degree of reliability and accuracy. 

This pressure sensor is used in clean room, medical and filter technology, in ventilation and air conditioning ducts, in spray booths, in large-scale 
catering facilities, for filter monitoring and level measurement or for triggering frequency converters. The medium measured is air (non-precipitating), 
or other gaseous, non-aggressive, non-combustible media. It has a manual zero point pushbutton and an offset potentiometer for final value correction. 
Parameter entry is menu-based and is easy to perform using three buttons with the help of the display.

TECHNICAL DATA

Power supply:  

24 V AC ⁄ DC (± 10 %)  and  15...36 V DC 

Load resistance: 

R

L

 > 5 kOhm

Power consumption:  

< 1.5 VA  ⁄  24 V DC,  < 2.8 VA  ⁄  24 V AC

Output:  

0  -10 V 
1 changeover contact (24 V), 1 A ohmic load

Connection type:  

3-wire  connection

Measuring  function:  

Volume flow, differential pressure, filter monitoring, fill level 

 (adjustable)

Measuring ranges:  

10...100% 

 (adjustable)

Type of pressure:  

differential pressure

Pressure  connection:  

equipped as standard with 

quick

 connect made from stainless steel  

for PVC-fabric pressure hose Ø 6 mm ( 4 ⁄ 8  mm optional) 
optionally with 

pipe fitting

, stainless steel V2A (1.4305)    

for pressure lines Ø 6 mm

Medium:  

clean air and non-aggressive, non-combustible gases

Media  temperature:  

–20...+50 °C

Accuracy:   

Type 7161

 (1000 Pa):  typically   ± 5 Pa 

Type 7165

 (5000 Pa):  typically ± 25 Pa 

compared to the calibrated reference device

Sum of Lihysteresis:  

<  ± 1 % of final value (pressure)

Temp. drift values:  

± 0.1 %  ⁄ °C

Above-⁄ below-atmospheric pressure:  max.   ± 10000  Pa

Signal  filtering:  

switchable  1 s  ⁄  10 s  

(via DIP switches) 

and small value suppression < 1 %

Signal hysteresis:  

± 1 % or final value (pressure)  10 Pa ⁄ 50 Pa

Electrical connection:  

0.14 - 1.5 mm²,  via plug-in screw terminal

Cable connection: 

cable gland, stainless steel V2A

 (1.4305)   

(M 20 x 1.5; with strain relief, exchangeable, inner diameter 6 - 12 mm) 

or  

M12 connector

 (male, 12-pin, A-code) according to DIN EN 61076-2-101

Housing:  

stainless steel V4A

 (1.4571), with non-distortion cover bolting, impact-resistant,   

high EMI shielding, corrosion, temperature, UV and weathering resistant

Dimensions:  

143  x  97  x  61 mm    (Tyr 2E)

Air  humidity:  

< 95 %  r. H.,  non-precipitating  air

Protection  type:  

IP 65

   (according to EN 60 529)  in the built-in state 

Housing tested, TÜV SÜD, Report No. 713160960B (Skadi2)  

Standards:  

CE conformity according to EMC Directive 2014 ⁄ 30 ⁄ EU, 
according to EN 61326-1, according to EN 61326-2-3

Equipment:  

Display with illumination, 

three-line,  cutout  approx. 70 x 40 mm  (W x H),       

for displaying the 

volume flow, differential pressure, contamination degree 

or

 level

 and  

for setting the 

switchpoint, K factor, measuring range limits 

and other settings

K factor:  

1 to 3000 

 (adjustable) 

Units:  

m³ ⁄ s,    m³ ⁄ min,    m³ ⁄ h,    l  ⁄ s,    l  ⁄ min,    l  ⁄  h,    %,    cm 

 (adjustable) 

Max. value displayed:  

999999

ACCESSORIES

 

see table

Summary of Contents for PREMASREG 716x-VA ID Series

Page 1: ...ung G Operating Instructions Mounting Installation Pressure measuring transducer swtich control switch for volume flow differential pressure filter monitoring and liquid level detection F Notice d ins...

Page 2: ...8 8 17 126 8 8 17 126 8 8 17 126 8 8 17 126 113 M20x1 5 M20x1 5 143 61 126 8 8 17 126 8 8 17 Schnell Steckanschluss standardm ig Quick connect standard Raccord rapide de s rie 126 M12 M12 113 M20x1 5...

Page 3: ...art Differenzdruck Druckanschluss standardm ig mittels Schnell Steckanschluss aus rostfreiem Stahl f r PVC Gewebe Druckschlauch 6 mm 4 8 mm optional optional mittels Rohrverschraubung aus Edelstahl V2...

Page 4: ...halter 4 ist nicht belegt PREMASREG 716x U W 3 Leiter Anschluss Schaltbild 1 2 3 230V AC 24V AC DC SPS PC UB 24V AC DC Ausgang Druck 0 10V in Pa UB GND PREMASREG 716x U W 1 2 3 UP DOWN SELECT AUTO ZER...

Page 5: ...Volumenstrom V k p V Volumenstrom in m3 h k k Faktor 1 3000 p Differenzdruck in Pa Differenzdruck p p p p Differenzdruck in Pa p h herer Druck p niedriger Druck Filterverschmutzung S 100 p pFilter S...

Page 6: ...Nullpunktes Dies wird durch ein Dauerlicht der LED und im Display durch das Umschalten von AUTO 0 nach PROG 0 angezeigt Hinweis Durch Loslassen des Tasters w hrend des Countdowns Z hler 0 wird das Se...

Page 7: ...er zweiten Zeile wird die entsprechende Einheit z B Pa m3 h cm dargestellt In der dritten Zeile kann der Schaltzustand des Relais Kreis ausgef llt leer mit dem entsprechenden Set Wert abgelesen werden...

Page 8: ...lle Relais Volumenstrom Einstellung Schaltpunkt Relais 10 bis Messbereichsendwert in der eingestellten Einheit Typ 1 Differenzdruck Differenzdruck f r max Ausgangsignal 10V Einstellung Messbereichsend...

Page 9: ...e m glich Bei Ver nderungen der Ger te durch den Anwender entfallen alle Gew hrleistungsanspr che Dieses Ger t darf nicht in der N he von W rmequellen z B Heizk rpern oder deren W rmestrom eingesetzt...

Page 10: ...f pressure differential pressure Pressure connection equipped as standard with quick connect made from stainless steel for PVC fabric pressure hose 6 mm 4 8 mm optional optionally with pipe fitting st...

Page 11: ...1 2 3 230V AC 24V AC DC PLC PC UB 24V AC DC Output pressure Pa 0 10V UB GND Pin assignment M12 PREMASREG 716x U W 45 1 2 3 7 6 5 4 9 8 11 10 12 1 2 3 4 5 6 7 8 9 10 11 12 UB 24V AC 15 36V DC Output p...

Page 12: ...K factor 1 3000 p Differential pressure in Pa Differential pressure p p p p Differential pressure in Pa p higher pressure p lower pressure Filter contamination S 100 p pFilter S Contamination degree...

Page 13: ...oint calibration takes place This is indicated by continuous light of the LED and on the display by switching from AUTO 0 to PROG 0 Note When releasing the pushbutton during countdown counter 0 zero p...

Page 14: ...degree or level The second line shows the corresponding unit e g Pa m3 h cm In the third line the switching status of the relay circuit completed empty with the corresponding set value can be read If...

Page 15: ...tching threshold at volume flow rate Setting relay switchpoint 10 to measuring range end value in the selected measurement unit Type 1 Differential pressure Differential pressure for max output signal...

Page 16: ...ur products In case of any modifications made by the user all warranty claims are forfeited This device must not be installed close to heat sources e g radiators or be exposed to their heat flow Direc...

Page 17: ...mesure 10 100 r glable Type de pression Pression diff rentielle Prise de pression de s rievia un raccord rapide enficher en acier inox pour tuyau de refoulement en PVC 6 mm 4 8 mm en option en option...

Page 18: ...t 1 2 3 230V AC 24V AC DC PLC PC UB 24V AC DC Output pressure Pa 0 10V UB GND Affectation des plots de connexion M12 PREMASREG 716x U W 45 1 2 3 7 6 5 4 9 8 11 10 12 1 2 3 4 5 6 7 8 9 10 11 12 UB 24V...

Page 19: ...ression diff rentielle en Pa Pression diff rentielle p p p p pression diff rentielle en Pa p pression plus lev e p pression moins lev e Encrassement du filtre S 100 p pFiltre S degr d encrassement en...

Page 20: ...l cran Une fois le compte rebours termin l appareil effectue le calibrage du point z ro Ceci est indiqu par la DEL allum e en continu ainsi que par l cran qui passe du mode AUTO 0 en mode PROG 0 Atte...

Page 21: ...pression le degr d encrassement ou le niveau L unit correspondante est repr sent e dans la deuxi me ligne par ex Pa m3 h cm L tat de commutation du relais cercle plein vide peut tre lu dans la troisi...

Page 22: ...age relais point de commutation 10 jusqu la valeur de fin de plage de mesure dans l unit param tr e Type 1 pression diff rentielle Pression diff rentielle pour signal de sortie max 10 V R glage valeur...

Page 23: ...itement et sont possibles suite au progr s technique et l am lioration continue de nos produits En cas de modifications des appareils par l utilisateur tous droits de garantie ne seront pas reconnus C...

Page 24: ...1 3 10 100 6 4 8 V2A 1 4305 6 20 50 C 7161 1000 5 7165 5000 25 1 0 1 C 10 000 1 c 10 c DIP 1 1 10 50 0 14 1 5 V2A 1 4305 M 20 x 1 5 6 12 M12 12 A DIN EN 61076 2 101 V4A 1 4571 143 x 97 x 61 Tyr 2E 95...

Page 25: ...free free free 45 1 2 3 7 6 5 4 9 8 11 10 12 1 2 3 4 5 6 7 8 9 10 11 12 UB 24V AC 15 36V DC Output pressure 0 10V Pa free UB GND free free COM Common NC Normally Closed NO Normally Open free free free...

Page 26: ...P1 P2 E P1 P2 P1 P2 A B C D E Types de V k p V 3 k 1 3000 p p p p p p p S 100 p p S p p h p g h p 700 1300 3 g 9 81 2 DIP 1 1 0 DIP 2 DIP 3 0 MR default OFF default OFF default OFF MR MR ON ON ON DIP...

Page 27: ...SET 1 2 3 UP DOWN SELECT AUTO ZERO SET min max min max OFFSET 1 2 3 4 5 6 ON DIP 12 11 13 1 2 3 UP DOWN SELECT AUTO ZERO SET min max min max OFFSET 1 2 3 4 5 6 ON DIP 12 11 13 1 2 3 UP DOWN SELECT AUT...

Page 28: ...P DOWN 1 2 3 UP DOWN SELECT AUTO ZERO SET min max min max OFFSET 1 2 3 4 5 6 ON DIP 12 11 13 1 2 3 UP DOWN SELECT AUTO ZERO SET min max min max OFFSET 1 2 3 4 5 6 ON DIP 12 11 13 3 limit DIP 3 OFF SEL...

Page 29: ...PREMASREG 716x 0 k 1 3000 k kS S kEBM PAPST kS S kZIEHL ABBEG kS S kGEBHARDT 0 7746 kS S kROSENBERG 0 7746 kS S 3600 kFL KT 0 3 3 1 3 4 2 3 5 10 10 10 100 10 1 10 10 10 100 10 2 10 0 100 3 700 1300 3...

Page 30: ...30 P P 10 ZVEI VDE EMV r 0 10 0 UB 15 36 UB GND 24 Circuitry Circuitry 0 10V 0V GND 0 10V 0V GND Power supply AC 24V 0V DC 15 36V GND Circuitry 0 10V 0V GND V Power supply AC 24V 0V DC 15 36V GND...

Page 31: ...ol their particular suitability must be verified by each customer and or end user themselves Existing property rights must be observed We warrant the faultless quality of our products as stated in our...

Page 32: ...REMASREG 716x VA ID D G F r WS 03 Wetter und Sonnenschutz optional Weather and sun protection optional Protection contre les intemp ries et le soleil en option PREMASREG 716x VA LCD PREMASREG 716x VAQ...

Reviews: