13
G
PREMASREG
®
711x - VA
DIP switches for pressure range setting, output attenuation and zero compensation:
Pressure range
(selectable) – max. measuring range (default) is depending to the type of device
DIP
1
DIP
2
0...100 Pa
0...1000 Pa
–100...+100 Pa
–1000...+1000 Pa
OFF
OFF
0...300 Pa
0...2000 Pa
–300...+300 Pa
–2000...+2000 Pa
O N
OFF
0...500 Pa
0...3000 Pa
–500...+500 Pa
–3000...+3000 Pa
OFF
O N
0...1000 Pa
0...5000 Pa
–1000...+1000 Pa
–5000...+5000 Pa
O N
O N
Measuring range mode
(Mode selectable)
DIP
3
Measurement signal filtering
(Time interval selectable)
DIP
5
Unidirectional ( 0 ...+MR ) (default)
OFF
10 s (default)
OFF
Bidirectional (–MR ...+MR )
O N
1 s
O N
DIP-Schalter 4 und 6 sind nicht belegt!
PREMASREG
®
711x - U W
PREMASREG
®
711x - U W
Pin assignment
(M12)
3-wire
-
connection
Schematic diagram
-
+
+
-
1 2 3
230V AC
24V AC/DC
PLC
PC
+UB 24V A
C/DC
Output pr
es
sur
e P
a 0–10V
–UB-GND
1
2
3
12
11
13
AUTO
ZERO
SET
min. max.
OFFSET
1 2 3 4 5 6
ON DIP
+UB 24V AC / 15...36V DC
Output pressure 0-10V [Pa]
–UB GND
NC
Normally Closed
NO
Normally Open
COM Common
Pushbutton
Zero point setting
SET-Setting relay
switchpoint
Plug for
display
Offset correction
ca. ±10 % of final value
Cont
act
pin side
PREMASREG
®
711x - U W
45°
1
2
3
7
6
5
4
9
8
11 10
12
1
2
3
4
5
6
7
8
9
10
11
12
+UB 24V AC / 15...36V DC
Output pressure 0 -10V [Pa]
free
–UB GND
free
free
COM Common
NC Normally Closed
NO Normally Open
free
free
free
45°
1
2
3
7
6
5
4
9
8
11 10
12
1
2
3
4
5
6
7
8
9
10
11
12
+UB 24V AC / 15...36V DC
Output pressure 0 -10V [Pa]
free
–UB GND
free
free
COM Common
NC Normally Closed
NO Normally Open
free
free
free