14
G
PREMASGARD
®
711x
1. For zero point setting, the device must be in operation for
at least 60 minutes.
2. Connect pressure inputs P (+) and P (–) with a hose.
(Pressure difference between the inputs = 0 Pa).
3. For zero point setting, press pushbutton uninterrupted for 10 seconds.
By pressing the pushbutton, a countdown of ca. 10 seconds is started.
The yellow LED is blinking and the countdown is shown on the display
(optional).
Zero point calibration takes place after the countdown period.
This is indicated by continuous LED light and at the display (optional) by
switching from "AUTO 0" to "PROG 0".
Note: By releasing the pushbutton during the countdown
(counter > 0), zero point setting is immediately cancelled!
Automatic offset setting:
Display readout:
Manual offset adjustment:
Automatic zero point calibration (optional):
The offset potentiometer functions additionally and
independently for automatically setting the zero point.
With the OFFSET potentiometer, a deviation outside of the zero
point can be aligned.
The range for adjustment is ca. ± 10 % of the pressure range.
A
zero point calibration
is carried out cyclically via an internal
valve.
The cycle time can be set between 15 minutes and 24 hours
using the „SET“ potentiometer.
During the automatic calibration, the output value remains at
its last pressure value.
DIP switches for
pressure range setting, output attenuation and zero compensation:
1
2
3
AUTO
ZERO
SET
min. max.
OFFSET
1 2 3 4 5 6
ON DIP
Plug for
display
Offset correction
ca. ±10 % of final value
Pushbutton
Zero point setting
Cont
act
pin side
SET-Setting Cycle time
(autom. zero point calibration)
The 1st line in the display shows the
actual pressure
.
In the 2nd line, the
unit
pascal (Pa) is shown.
Standard
Actual pressure (in Pa)
Calibration interval (arrows)
Zero point calibration active
remaining calibration time
(in seconds)
Adjustment of
zero point calibration
Cycle time (15 min to 24 hours)
adjustable by potentiometer
Pressure range
(selectable) – max. measuring range (default) is depending to the type of device
DIP
1
DIP
2
0...25 Pa
0...50 Pa
0...100 Pa 0...1000 Pa –25...+25 Pa
–50...+50 Pa
–100...+100 Pa
–1000...+1000 Pa
OFF
OFF
–
–
0...300 Pa 0...2000 Pa
–
–
–300...+300 Pa
–2000...+2000 Pa
O N
OFF
–
–
0...500 Pa 0...3000 Pa
–
–
–500...+500 Pa
–3000...+3000 Pa
OFF
O N
0
...
25 Pa 0
...
100 Pa 0
...
1000 Pa 0
...
5000 Pa –25
...
+25 Pa –100
...
+100 Pa
–1000
...
+1000 Pa
–5000
...
+5000 Pa
O N
O N
Measuring range mode
(Mode selectable)
DIP
3
Measurement signal filtering
(Time interval selectable)
DIP
5
Unidirectional ( 0 ...+MR ) (default)
OFF
10 s (default)
OFF
Bidirectional (–MR ...+MR )
O N
1 s
O N
# 502