U - variant 

(Range:     0...+ xx Pa)

After successful zero point calibration, the output voltage  
is 0 V at 0 Pa pressure difference (with the offset knob  
in central position)!

Output voltage 0...10 V  
for pressure difference from 0 Pa to final value

U - variant 

(Range:    – xx  ... + xx Pa)

After successful zero point calibration, the output voltage  
is 5 V at 0 Pa pressure difference (with the offset knob in  
central position)!

Output voltage 0...10 V  
for pressure difference – ΔP ... +ΔP

I  -  variant 

(Range:     0...+ xx Pa)

After successful zero point calibration, the output current  
is 4 mA at 0 Pa pressure difference (with the offset knob  
in central position)!

Output current 4...20 mA  
for pressure difference from 0 Pa to final value

I  -  variant 

(Range:   – xx  ... + xx Pa)

After successful zero point calibration, the output current  
is 12 mA at 0 Pa pressure difference (with the offset knob  
in central position)!

Output current 4... 20 mA  
for pressure difference  – ΔP ... +ΔP

G  

PREM

ASGARD

®

  211x 

 212x 

 212x - SD

  |  Configuration and zero point calibration

10 V

0 V

Displacement of characteristic line 
by control knob (right stop)
Offset =  +10%

Original characteristic line

Offset = 0 

Control knob in

central position = default

Displacement of characteristic line 
by control knob (left stop)
Offset =  –10%

(zero point offset)

100% of

measuring range

10 V

5 V

0 Pa

+ Pa

– Pa

Displacement of 
characteristic line(+) 
by control knob (right stop)
ca. +10%

Displacement of 
characteristic line(–) 
by control knob (left stop)
ca. –10%

Original characteristic line

Offset = 0 (potentiometer in

central position = factory setting)

Pressure difference in Pa

U output in V

Pressure at input
(P+)> pressure at 
input (P–)

Pressure at input
(P–)> Pressure at 
input (P+)

20 mA

4 mA

0 Pa

+ Pa

I output in mA

Displacement of characteristic line(+) 
by control knob (right stop)
ca. +10%

Original characteristic line

Offset = 0 (potentiometer in

central position = factory setting)

Pressure difference in Pa

Displacement of characteristic line(–) 
by control knob (left stop)
ca. –10%

20 mA

12 mA

0 Pa

+ Pa

– Pa

Displacement of 
characteristic line(+) 
by control knob (right stop)
ca. +10%

Displacement of 
characteristic line(–) 
by control knob (left stop)
ca. –10%

Original characteristic line

Offset = 0 (potentiometer in

central position = factory setting)

Pressure difference in Pa

Pressure at input
(P+)> pressure at 
input (P–)

Pressure at input
(P–)> Pressure at 
input (P+)

Summary of Contents for PREMASGARD 211 Series

Page 1: ...g connection set compact form adjustable calibratable with multi range switching and active output F Notice d instruction Convertisseur de pression et de pression diff rentielle y compris kit de racco...

Page 2: ...eichnung Dimensional drawing Plan cot ohne Display without display sin cran ohne Display without display sin cran mit Display with display avec cran mit Display with display avec cran 39 49 4 3 15 6 1...

Page 3: ...ture 20 50 C temperature compensated 0 50 C Pressure connection with connection nozzles for pressure hose 6 mm Type of pressure differential pressure Medium clean air and other non aggressive non comb...

Page 4: ...D 2125 LCD 0 10 V 4 20 mA 1301 11A7 2050 000 max 100 100 Pa PREMASGARD 2120 IP 67 0 50 Pa 50 50 Pa 0 100 Pa 100 100 Pa PREMASGARD 2120 0 10 V 4 20 mA 1301 11A7 0110 000 PREMASGARD 2120 LCD 0 10 V 4 20...

Page 5: ...a 110 Pa TYPES OF MONITORING Pressure connections at the pressure switch are marked with P1 for higher pressure and P2 for lower pressure A Below atmospheric pressure P1 is not connected but open to t...

Page 6: ...ecting diagram PREMASGARD 211x PREMASGARD 212x PREMASGARD 212x SD 1 2 3 230V AC 24V AC DC PLC PC UB 24 V AC DC UB AC DC GND Output pressure Pa DIP switches for pressure range setting output attenuatio...

Page 7: ...t in the display In the 1st line of the display the ACTUAL pressure up to the measuring range limit is displayed Switching between the units Pa and hPa 100 Pa 1 hP happens automatically Pa Pascal hP H...

Page 8: ...right stop Offset 10 Original characteristic line Offset 0 Control knob in central position default Displacement of characteristic line by control knob left stop Offset 10 zero point offset 100 of mea...

Page 9: ...ing instructions delivered together with the device are exclusively valid Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and...

Page 10: ...r control their particular suitability must be verified by each customer and or end user themselves Existing property rights must be observed We warrant the faultless quality of our products as stated...

Page 11: ...DAL 01 Dimensional drawing Plan cot ASD 06 Anschluss Set Connection set Kit de raccordement Ma zeichnung ASD 06 Dimensional drawing Plan cot ASD 07 Anschlussnippel Connection nipple Embouts de raccor...

Reviews: