background image

Connecting scheme 

Parallel operation

Connecting scheme 

Individual operation

SUPPLY VOLTAGE:

For operating voltage reverse polarity protection, a one-way rectifier or 
reverse  polarity  protection  diode  is  integrated  in  this  device  variant. 
This internal one-way rectifier also allows operating 0 – 10 V devices on 
AC supply voltage.

The  output  signal  is  to  be  tapped  by  a  measuring  instrument.  Output 
voltage is measured her against zero potential (O V) of the input voltage!

When this device is operated on DC supply voltage, the operating volt-
age input UB+ is to be used for 15...36 V DC supply and UB – or GND for 
ground wire!

When several devices are supplied by one 24 V AC voltage supply, it is 
to be ensured that all ”positive“ operating voltage input terminals (+) of 
the field devices are connected with each other and all ”negative“ opera-
ting  voltage  input  terminals  (–)  (=  reference   potential)  are  connected 
together  (in-phase  connection  of  field  devices).  All  outputs  of  field  de-
vices must be referenced to the same potential!

In  case  of  reversed  polarity  at  one  field  device,  a  supply  voltage  short-
circuit  would  be  caused  by  that  device.  The  consequential  short-circuit 
current flowing through this field device may cause damage to it.

Therefore, pay attention to correct wiring!

Circuitry

Circuitry

0...10V

0V/GND

0...10V

0V/GND

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

Circuitry

0...10V

0V/GND

V

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

 Load resistance diagram

4 …  20 mA

800

700

600

500

400

300
250

50

200

10

15

20

25

30 35 36 40

Load resistance diagram

W

orking r

esis

tanc

e  (Ohm)

Operating voltage  (V DC)

Admissible

  range

NOTE

For 4 ... 20 mA devices, DC voltage must be used (without residual  ripple, 
see permissible range of load resistance diagram). Do not use pulsating 
DC voltage.

Summary of Contents for HYGRASGARD RPFF

Page 1: ...kalibrierfähig mit Mehrbereichsumschaltung und aktivem Ausgang G Operating Instructions Mounting Installation Pendulum room humidity and temperature sensors calibrateable with multi range switching and active output F Notice d instruction Sonde d ambiance pendulaire combinée humidité et température étalonnable avec commutation multi gamme et sortie active r Руководство по монтажу и обслуживанию Да...

Page 2: ...D G F r HYGRASGARD RPFF HYGRASGARD RPFTF Maßzeichnung RPFF Dimensional drawing RPFTF Plan coté Габаритный чертеж MF 16 K ...

Page 3: ...t kleine Hysterese hohe Langzeitstabilität Sensorschutz Membranfilter austauschbar RPFF RPFTF Metallsinterfilter RPFF 25 RPFTF 25 Kunststoffsinterfilter FEUCHTE Messbereich Feuchte 0 100 r H Ausgang entspricht 0 10 V oder 4 20 mA Arbeitsbereich Feuchte 0 95 r H ohne Betauung Abweichung Feuchte 3 r H 20 80 bei 20 C sonst 5 r H Ausgang Feuchte 0 10 V bei U Variante 4 20 mA bei I Variante Bürde 800 Ω...

Page 4: ...euchtung zweizeilig Zubehör MF 16 K Montageflansch aus Kunststoff HYGRASGARD RPFF und RPFTF Typ WG1 Messbereich Ausgang Feuchte relativ Temperatur umschaltbar Feuchte relativ Temperatur RPFF 25 I 0 100 r H 4 20mA RPFF 25 U 0 100 r H 0 10V RPFTF 25 I 0 100 r H 35 75 C 4 20mA 4 20mA 35 35 C 0 50 C 0 80 C RPFTF 25 U 0 100 r H 35 75 C 0 10V 0 10V 35 35 C 0 50 C 0 80 C RPFF 25 RPFTF 25 xx Display Displ...

Page 5: ...usgang Temperatur 4 20mA in C UB GND optional für LCD Hintergrundbeleuchtung Stecker Display passiver Sensor DIP Schalter Mehrbereichs umschaltung Offset Temperatur 5 K Feuchte 10 r H 4 3 2 1 5 6 Offset C r H 1 2 0N UB 24V AC DC UB GND Ausgang Feuchte 0 10V in r H Ausgang Temperatur 0 10V in C Stecker Display Mehrbereichs umschaltung DIP Schalter passiver Sensor Offset Temperatur 5 K Offset Feucht...

Page 6: ...20 7 9 16 6 25 8 6 17 7 30 9 3 18 9 35 10 0 20 0 C UA in V IA in mA 0 0 0 4 0 5 0 6 5 0 10 1 3 6 0 15 1 9 7 0 20 2 5 8 0 25 3 1 9 0 30 3 8 10 0 35 4 4 11 0 40 5 0 12 0 45 5 6 13 0 50 6 3 14 0 55 6 9 15 0 60 7 5 16 0 65 8 1 17 0 70 8 8 18 0 75 9 4 19 0 80 10 0 20 0 C UA in V IA in mA 0 0 4 0 5 1 5 6 10 2 7 2 15 3 8 8 20 4 10 4 25 5 12 0 30 6 13 6 35 7 15 2 40 8 16 8 45 9 18 4 50 10 20 0 r H UA in V...

Page 7: ...erden mehrere Geräte von einer 24 V AC Spannung versorgt ist darauf zu achten dass alle positiven Betriebsspannungseingänge der Feldgeräte miteinander verbunden sind sowie alle negativen Be triebsspannungseingänge Bezugspotential miteinander ver bunden sind phasengleicher Anschluss der Feldgeräte Alle Feld ge räte aus gänge müssen auf das gleiche Potential bezogen werden Bei Verpolung der Versorgu...

Page 8: ... durch Spannungsinduktion zu verhindern sind abgeschirmte Leitungen zu verwenden eine Parallelverlegung zu stromführenden Leitungen zu vermeiden und die EMV Richtlinien zu beachten Dieses Gerät ist nur für den angegebenen Verwendungszweck zu nutzen dabei sind die entsprechenden Sicherheitsvorschriften des VDE der Länder ihrer Überwachungsorgane des TÜV und der örtlichen EVU zu beachten Der Käufer ...

Page 9: ......

Page 10: ...nsor protection membrane filter exchangeable RPFF RPFTF metal sinter filter RPFF 25 RPFTF 25 plastic sinter filter HUMIDITY Measuring range humidity 0 100 r H output corresponding to 0 10V or 4 20mA Operating range humidity 0 95 r H without formation of dew Deviation humidity 3 r H 20 80 at 20 C otherwise 5 r H Output humidity 0 10V at U variant 4 20mA at I variant working resistance 800 Ω see loa...

Page 11: ...lay with illumination Accessories MF 16 K Mounting flange plastic HYGRASGARD RPFF and RPFTF Type WG1 Measuring Range Output Humidity relative Temperature switchable Humidity relative Temperature RPFF 25 I 0 100 r H 4 20mA RPFF 25 U 0 100 r H 0 10V RPFTF 25 I 0 100 r H 35 75 C 4 20mA 4 20mA 35 35 C 0 50 C 0 80 C RPFTF 25 U 0 100 r H 35 75 C 0 10V 0 10V 35 35 C 0 50 C 0 80 C RPFF 25 RPFTF 25 xx Disp...

Page 12: ...V DC Output humidity 4 20mA in r H Output temperature 4 20mA in C UB GND optional for LCD background lighting Plug display Passive sensor DIP switches multi range switching Offset Temperature 5 K Humidity 10 r H 4 3 2 1 5 6 Offset C r H 1 2 0N UB 24V AC DC UB GND Output humidity 0 10 V in r H Output temperature 0 10 V in C Plug display DIP switches multi range switching Passive sensor Offset tempe...

Page 13: ... 15 4 20 7 9 16 6 25 8 6 17 7 30 9 3 18 9 35 10 0 20 0 C UA in V IA in mA 0 0 0 4 0 5 0 6 5 0 10 1 3 6 0 15 1 9 7 0 20 2 5 8 0 25 3 1 9 0 30 3 8 10 0 35 4 4 11 0 40 5 0 12 0 45 5 6 13 0 50 6 3 14 0 55 6 9 15 0 60 7 5 16 0 65 8 1 17 0 70 8 8 18 0 75 9 4 19 0 80 10 0 20 0 C UA in V IA in mA 0 0 4 0 5 1 5 6 10 2 7 2 15 3 8 8 20 4 10 4 25 5 12 0 30 6 13 6 35 7 15 2 40 8 16 8 45 9 18 4 50 10 20 0 r H U...

Page 14: ...ices are connected with each other and all negative opera ting voltage input terminals reference potential are connected together in phase connection of field devices All outputs of field de vices must be referenced to the same potential In case of reversed polarity at one field device a supply voltage short circuit would be caused by that device The consequential short circuit current flowing thr...

Page 15: ...ltage condition To avoid damages and errors the device e g by voltage induction shielded cables are to be used laying parallel with current carrying lines is to be avoided and EMC directives are to be observed This device shall only be used for its intended purpose Respective safety regulations issued by the VDE the states their control authorities the TÜV and the local energy supply company must ...

Page 16: ......

Page 17: ...ntégré résistant à la condensation petit hystérésis haute stabilité long terme Protection de capteur Filtre à membrane remplaçable RPFF RPFTF filtre en métal fritté RPFF 25 RPFTF 25 filtre en matière synthétique frittée HUMIDITÉ Plage de mesure humidité 0 100 h r sortie correspond à 0 10 V ou 4 20 mA Plage de service humidité 0 95 h r sans condensation Incertitude de mesure humidité 3 h r 20 80 à ...

Page 18: ...x lignes Accessoires MF 16 K bride de montage en matière plastique HYGRASGARD RPFF et RPFTF Désignation WG1 plage de mesure sortie humidité relative température commutable humidité relative température RPFF 25 I 0 100 h r 4 20mA RPFF 25 U 0 100 h r 0 10V RPFTF 25 I 0 100 h r 35 75 C 4 20mA 4 20mA 35 35 C 0 50 C 0 80 C RPFTF 25 U 0 100 h r 35 75 C 0 10V 0 10V 35 35 C 0 50 C 0 80 C RPFF 25 RPFTF 25 ...

Page 19: ... C r H UB 24V DC Output humidity 4 20mA in r H Output temperature 4 20mA in C UB GND optional for LCD background lighting Plug display Passive sensor DIP switches multi range switching Offset Temperature 5 K Humidity 10 r H 4 3 2 1 5 6 Offset C r H 1 2 0N UB 24V AC DC UB GND Output humidity 0 10 V in r H Output temperature 0 10 V in C Plug display DIP switches multi range switching Passive sensor ...

Page 20: ...0 12 0 5 5 7 13 1 10 6 4 14 3 15 7 1 15 4 20 7 9 16 6 25 8 6 17 7 30 9 3 18 9 35 10 0 20 0 C UA en V IA en mA 0 0 0 4 0 5 0 6 5 0 10 1 3 6 0 15 1 9 7 0 20 2 5 8 0 25 3 1 9 0 30 3 8 10 0 35 4 4 11 0 40 5 0 12 0 45 5 6 13 0 50 6 3 14 0 55 6 9 15 0 60 7 5 16 0 65 8 1 17 0 70 8 8 18 0 75 9 4 19 0 80 10 0 20 0 C UA en V IA en mA 0 0 4 0 5 1 5 6 10 2 7 2 15 3 8 8 20 4 10 4 25 5 12 0 30 6 13 6 35 7 15 2 ...

Page 21: ...terrain soient reliées entre elles de même que toutes les entrées de tension négatives potentiel de référence soient reliées entre elles les appareils de terrain doivent être branchés en phase Toutes les sorties d appareil de terrain doivent se référer au même potentiel Une inversion de la polarisation de la tension d alimentation sur un des appareils de terrain provoquerait un court circuit Le co...

Page 22: ... endommagements erreurs sur l appareil par ex dus à une induction de tension parasite il est conseillé d utiliser des câbles blindés ne pas poser les câbles de sondes en parallèle avec des câbles de puissance les directives CEM sont à respecter Cet appareil ne doit être utilisé que pour l usage qui est indiqué en respectant les règles de sécurité correspondantes de la VDE des Länders de leurs orga...

Page 23: ......

Page 24: ... долговременной стабильностью Защита чувствительного элемента сменный металлический спеченный фильтр RPFF RPFTF металлический спеченный фильтр RPFF 25 RPFTF 25 пластиковый спеченный фильтр ВЛАЖНОСТЬ Диапазон измерения влажности 0 100 относительной влажности на выходе соответствует 0 10B или 4 20мА Рабочий диапазон влажности 0 95 относительной влажности Погрешность измерения влажности 3 относительн...

Page 25: ...трочный Принадлежности MF 16 K Присоединительный фланец из пластика HYGRASGARD RPFF и RPFTF Тип группа товаров1 Диапазон измерения Выход отн влажности температуры переключаемый отн влажности температуры RPFF 25 I 0 100 отн вл 4 20мA RPFF 25 U 0 100 отн вл 0 10В RPFTF 25 I 0 100 отн вл 35 75 C 4 20мA 4 20мA 35 35 C 0 50 C 0 80 C RPFTF 25 U 0 100 отн вл 35 75 C 0 10В 0 10В 35 35 C 0 50 C 0 80 C RPFF...

Page 26: ...erature 5 K Humidity 10 r H 1 2 3 4 5 6 1 2 0N Offset C r H UB 24V DC Output humidity 4 20mA in r H Output temperature 4 20mA in C UB GND optional for LCD background lighting Plug display Passive sensor DIP switches multi range switching Offset Temperature 5 K Humidity 10 r H 4 3 2 1 5 6 Offset C r H 1 2 0N UB 24V AC DC UB GND Output humidity 0 10 V in r H Output temperature 0 10 V in C Plug displ...

Page 27: ... 5 5 7 13 1 10 6 4 14 3 15 7 1 15 4 20 7 9 16 6 25 8 6 17 7 30 9 3 18 9 35 10 0 20 0 C UA В IA in мA 0 0 0 4 0 5 0 6 5 0 10 1 3 6 0 15 1 9 7 0 20 2 5 8 0 25 3 1 9 0 30 3 8 10 0 35 4 4 11 0 40 5 0 12 0 45 5 6 13 0 50 6 3 14 0 55 6 9 15 0 60 7 5 16 0 65 8 1 17 0 70 8 8 18 0 75 9 4 19 0 80 10 0 20 0 C UA В IA in мA 0 0 4 0 5 1 5 6 10 2 7 2 15 3 8 8 20 4 10 4 25 5 12 0 30 6 13 6 35 7 15 2 40 8 16 8 45...

Page 28: ...жительные входы рабочего напряжения полевых устройств были соединены друг с другом Это относится также ко всем отрицательным входам рабочего напряжения опорного потенциала синфазное подключение полевых устройств Все выходы полевых устройств должны относиться к одному потенциалу Подключение питающего напряжения одного из полевых устройств с неверной полярностью ведёт к короткому замыканию напряжени...

Page 29: ...избежание повреждений и отказов например вследствие наводок следует использовать экранированную проводку избегать параллельной прокладки токоведущих линий и учитывать предписания по электромагнитной совместимости Данный прибор следует применять только по прямому назначению учитывая при этом соответствующие предписания VDE союза немецких электротехников требования действующие в Вашей стране инструк...

Page 30: ......

Page 31: ...ümer und technische Änderungen vorbehalten Errors and technical changes excepted Sous réserve d erreurs et de modifications techniques Возможны ошибки и технические изменения Maßzeichnung RPFF 25 Dimensional drawing RPFTF 25 Plan coté Габаритный чертеж ...

Page 32: ...D RPFTF 25 RPFF 25 RPFTF 25 mit Display with display avec écran с дисплеем RPFF 25 RPFTF 25 Messkopf steckbar und verschraubt Measuring head pluggable and screwed in place tête de mesure enfichable et vissée вставная измерительная головка ...

Reviews: