![S+S Regeltechnik AERASGARD RLQ-CO2-W Operating Instructions, Mounting & Installation Download Page 11](http://html1.mh-extra.com/html/s-s-regeltechnik/aerasgard-rlq-co2-w/aerasgard-rlq-co2-w_operating-instructions-mounting-and-installation_3093598011.webp)
11
G
AERASGARD
®
RCO
2
- W ⁄ RLQ - CO
2
- W ⁄ RFTM - LQ - CO
2
- W ⁄ RTM - CO
2
- SD
Rev. 2019 - V29
TECHNICAL DATA
(continued)
Pressure dependence:
± 0.13 % ⁄ mm Hg
Long-term stability:
< 2 % in 15 years
Gas exchange:
by diffusion
Ambient temperature:
0...+ 50 °C
Warm up time:
approx. 1 hour
Response time:
< 2 minutes
Electrical connection:
0.14 - 1.5 mm
2
, via screw terminals
Housing:
plastic, material ABS, colour pure white (similar to RAL 9010), stainless steel
V2A
(1.4301) housing optional
Dimensions:
98 x 98 x 33 mm (Baldur 2)
Installation:
wall mounting or on in-wall flush box, Ø 55 mm, base with 4 holes,
for attachment to vertically or horizontally installed in-wall flush boxes for rear cable entry,
with predetermined breaking point for cable entry from top ⁄ bottom in case of plain on-wall installation
Protection class:
III (according to EN 60 730)
Protection type:
IP 30 (according to EN 60 529)
Standards:
CE conformity, electromagnetic compatibility according to EN 61 326,
EMC Directive 2014 ⁄ 30 ⁄ EU, Low Voltage Directive 2014 ⁄ 35 ⁄ EU
Optional:
display with illumination,
two line, cutout approx. 36 x 15 mm (W x H),
for displaying actual humidity, actual temperature, air quality and / or the actual CO
2
content
AERASGARD
®
RTM - CO
2
- SD
Room temperature and CO
2
sensor, Standard
AERASGARD
®
RCO
2
- W
Room CO
2
sensor, Premium
AERASGARD
®
RLQ - CO
2
- W
Room air quality (VOC) and CO
2
sensor, Premium
AERASGARD
®
RFTM - CO
2
- W
Multifunctional room sensor
for humidity, temperature and CO
2
content, Deluxe
AERASGARD
®
RFTM - LQ - CO
2
- W
Multifunctional room sensor
for humidity, temperature, CO
2
content and air quality (VOC), Deluxe
Type ⁄ WG02
Measuring Range
Humidity
Temperature
CO
2
Equipment
VOC
Display
Item No.
(Baldur 2)
RTM - CO
2
- SD
(fixed)
R T M - C O2- SD -U
–
0...+50 °C
0...2000 ppm
–
– 1501-61B2-1001-200
RCO
2
- W
(switchable)
RC O2-W
–
–
0...2000 ⁄ 5000 ppm
–
W
1501-61A0-7301-200
RC O2-W-DISP L AY
–
–
0...2000 ⁄ 5000 ppm
–
W
■
1501-61B0-7321-200
RLQ - CO
2
- W
(switchable)
RL Q - C O2-W
–
–
0...2000 ⁄ 5000 ppm
0...100 %
W
1501-61B1-7301-200
RL Q - C O2-W DISP L AY
–
–
0...2000 ⁄ 5000 ppm
0...100 %
W
■
1501-61B1-7321-200
RFTM - CO
2
- W
(switchable)
RF T M - C O2-W
0...100 % r.H.
0...+50 °C
0...2000 ⁄ 5000 ppm
–
W
1501-61B6-7301-200
RF T M - C O2-W DISP L AY
0...100 % r.H.
0...+50 °C
0...2000 ⁄ 5000 ppm
–
W
■
1501-61B6-7321-200
RFTM - LQ - CO
2
- W
(switchable)
RF T M -L Q - C O2-W
0...100 % r.H.
0...+50 °C
0...2000 ⁄ 5000 ppm
0...100 %
W
1501-61B8-7301-200
RF T M -L Q - C O2-W DISPL AY 0...100 % r.H.
0...+50 °C
0...2000 ⁄ 5000 ppm
0...100 %
W
■
1501-61B8-7321-200
Outputs:
0 -10 V or 4...20 mA
(selectable via DIP switches, selected variant applies for all outputs) –
Standard room sensor
RTM - CO
2
- SD
with fixed output 0 -10 V!
Equipment:
W = changeover contact
– Standard room sensor
RTM - CO
2
- SD
without changeover contact !
Note:
This unit
must not
be used as safety-relevant device!