S+S Regeltechnik AERASGARD RC02 Operating Instructions, Mounting & Installation Download Page 6

G  

AER

ASGARD

®

  RCO

2

Connecting diagram

 

RCO

2

 

Connecting diagram

 

RCO

2

 - Display

Schematic diagram

 

RCO

2

 - Display

1

2

3

4

CO

2

 Sensor

2000 5000 10000 aut

o

1 2 34

ON 

Set CO

2

CO

range 

2000 5000 10000 aut

o

1 2 34

ON 

Set CO

2

CO

range 

Fre

e

Output CO

2

 c

ont

ent  0-10V

UB+ 24V A

C/DC

 GND

Measuring 

range selection 

CO

2

Button and LED 

for manual 

CO

2

 setting 

1

2

3

4
5

6

7
8

UB+ 24V AC/DC

UB- 24V AC/DC

Free

Free

GND

Free

Free

Output CO

2

 content in ppm 0-10V

1

2

3

UB- GND

UB+ supply voltage 24V AC/DC

Output CO

2

 content in ppm 0-10V

The  maintenance-free microprocessor-controlled AERASGARD

®

 RCO

2

 is used to 

detect the CO

2

 content in air. This sensor is optionally available with or without 

 display. The measurement signals from the CO

2

 transmitter are converted into 

standard signals of 0 -10 V. Optionally, this CO

2

 measuring transducer can be 

 supplied with display or switching output. 
Elegant enclosure made of plastic, with snap-on lid, base with 4-hole attachment for 
installation on vertically or horizontally installed in-wall flush boxes, with predeter-
mined breaking point for on-wall cable entry. or in enclosures made of stainless steel 
(top and bottom part are of stainless steel, the lid is screwed on), van dalism-secure 
version e.g. for schools, military barracks, and public buildings. 
The CO

2

 content of air is determined by a dual beam NDIR sensor (non-dispersive 

infrared technology). The detection range of this CO

2

 sensor is calibrated for stand-

ard applications such as monitoring of residential rooms or con ference rooms. Room 
ventilation on an as-needed basis, improvement of well-being and customer benefit, 
increased comfort as well as a reduction of operating costs by energy conservation 
are only some of the beneficial results of employing AERASGARD

®

 RCO

2

 sensors. 

TECHNICAL DATA:

Power supply: ........................ 24 V AC ⁄ DC
Average power consumption: ....... < 3 VA  at 24 V DC

CARBON DIOXIDE  (CO

2

)

CO

2

 sensor: ........................... optical, dual beam sensor  (NDIR), 

with automatic self-calibration,

  

non-dispersive infrared technology, 
dual beam measuring method

Measuring range, CO

2

:.............

multi-range switching 

  

(selectable via DIP switches)  

0 … 2000  ppm;  0 … 5000  ppm;  0 … 10000  ppm

 

Output CO

2

: ........................... 0 -10 V

Measuring accuracy CO

2

: ......... ± 70 ppm plus 5 % of measured value

Pressure dependence: ............. ± 1.6 %  ⁄ kPa  (referred to standard pressure)
Long-term stability:................. ± 1 % of final value per year
Gas exchange: ........................ by diffusion
Warm-up time: ....................... ca. 1 hour
Ambient temperature: ............. 0 …+50 °C
Response time:  ....................... ca. 1 minute
Electrical connection: .............. 0.14 - 1.5 mm

2

, via screw terminals on circuit 

board

Enclosure: ............................. plastic, material ABS,  

colour pure white (similar RAL 9010),  
stainless steel enclosure optional

Dimensions: ........................... 98  x 106  x  32 mm    (Frija II) 

100  x 100 x  25 mm    (stainless  steel  enclosure)

Installation: ........................... wall mounting or on in-wall flush box, Ø 55 mm,  

base with 4-hole for mounting on vertically 
or horizontally installed in-wall flush boxes for  
cable entry from the back, with predetermined  
breaking point for on-wall cable entry from  
top  ⁄ bottom in case of plain on-wall installation

Protection class: .................... III  (according to EN 60 730)
Protection type: ..................... IP 30  (according to EN 60 529)
Standards: ............................ CE-conformity, electromagnetic compatibility  

according  to  EN  61 326 + A1 + A2,   
EMC directive 2004 ⁄ 108 ⁄ EC, 
low-voltage directive 73 ⁄ 23 ⁄ EEC

Optional: ............................... 8 - digit  display,   

cutout  36 x14  mm  (W x H), 
for displaying actual CO

2

 content  

6

7

# 14 -4018   (wie Katalog-

2014

, ab Seite 312)

ENDFASSUNG

  |  23. 01. 2014  ⁄ PR

  

 

# 281

00 - 2014

Summary of Contents for AERASGARD RC02

Page 1: ...Installation Room CO2 sensors respectively measuring transducers self calibrating with multi range switching and active output F Notice d instruction Sonde transmetteur de CO2 d ambiance auto calibra...

Page 2: ...Dimensional drawing Enclosure FrijaII Plan cot bo tier FrijaII FrijaII Ma zeichnung Geh use Edelstahl Dimensional drawing Enclosure stainless steel Plan cot bo tier acier inox 2 14 4018 wie Katalog 20...

Page 3: ...P Schalter w hlbar 0 2000 ppm 0 5000 ppm 0 10000 ppm Ausgang CO2 0 10 V Messgenauigkeit CO2 70 ppm zzgl 5 vom Messwert Druckabh ngigkeit 1 6 kPa bezogen auf Normaldruck Langzeitstabilit t 1 EW Jahr Ga...

Page 4: ...e en des Ger tes ist ein Dauerbetrieb von mindestens 10 Minuten bei Frischluft CO2 Gehalt 300 400 ppm sicherzustellen Die manuelle Kalibrierung des Ausgangssignals auf 1 75 V 350ppm Nullpunkt wird dur...

Page 5: ...ung unserer Produkte m glich Bei Ver nderungen der Ger te durch den Anwender entfallen alle Gew hrleistungsanspr che Dieses Ger t darf nicht in der N he von W rmequellen z B Heizk rpern oder deren W r...

Page 6: ...well being and customer benefit increased comfort as well as a reduction of operating costs by energy conservation are only some of the beneficial results of employing AERASGARD RCO2 sensors TECHNICAL...

Page 7: ...ion the device needs to be supplied with fresh air CO2 content 300 400 ppm at least for 10 minutes during each 7 day period For self calibration the devices memorises device internally the CO2 con ten...

Page 8: ...tinuous improvement of our products In case of any modifications made by the user all warranty claims are forfeited This device must not be installed close to heat sources e g radiators or be exposed...

Page 9: ...des r sultats que l on peut obtenir gr ce l utilisation des sondes AERASGARD RCO2 CARACT RISTIQUES TECHNIQUES Tension d alimentation 24 V ca cc Consommation lectrique moyenne 3 VA 24 V cc Capteur cap...

Page 10: ...de carbone L talonnage manuel peut tre lanc ind pendamment de la position de l interrupteur DIP4 en actionnant le bouton poussoir capteur 2 Apr s le branchement de l appareil il faut assurer un foncti...

Page 11: ...t possibles suite au progr s technique et l am lioration continue de nos produits En cas de modifications des appareils par l utilisateur tous droits de garantie ne seront pas reconnus Cet appareil ne...

Page 12: ...00 pp 0 10000 pp CO2 0 10 B CO2 70 pp 5 1 6 1 1 5 40 C 1 0 14 1 5 2 ABS RAL 9010 98 x 106 x 32 Frija II 100 x 100 x 25 55 III EN 60 730 IP 30 EN 60 529 CE EN 61 326 A1 A2 2004 108 EC 73 23 EEC 8 36 x...

Page 13: ...501 6110 1000 000 RCO2 VA 0 2000 pp 0 10 1501 4110 1000 005 RCO2 U umschaltbar RCO2 U 0 2000 5000 10000 pp 0 10 1501 6110 1001 000 RCO2 U VA 0 2000 5000 10000 pp 0 10 1501 6110 1002 005 8 CO2 DIP 1 DI...

Page 14: ...0 10 0 UB 15 36 UB GND 24 Circuitry Circuitry 0 10V 0V GND 0 10V 0V GND Power supply AC 24V 0V DC 15 36V GND Circuitry 0 10V 0V GND V Power supply AC 24V 0V DC 15 36V GND 14 14 4018 wie Katalog 2014 a...

Page 15: ...forward and hold it Pour ouvrir le bo tier placer le tournevis 2 0 au centre de l encoche pousser vers le bas et soulever l g rement le cadre inf rieur Tirer le couvercle vers l avant et le maintenir...

Page 16: ...AERASGARD RCO2 D G F r 16 14 4018 wie Katalog 2014 ab Seite 312 ENDFASSUNG 23 01 2014 PR 28100 2014...

Reviews: