S+S Regeltechnik AERASGARD ACO2-Modbus Manual Download Page 6

19

HYGRASGARD

®

    AFTM-  ⁄  KFTM - LQ - CO

2

 - Modbus

  |  

 

Configuration

 

Rev. 2017 - V14 GB intro

READOUT IN THE DISPLAY

By default, the display indicates the following measurements with the corresponding units 

cyclically

 and consecutively:  

CO

2

 content in ppm, 

air quality

 (VOC) in %, 

temperature

 in °C, 

relative humidity

 in % r.H.

   

   

   

The Modbus interface can be used to program an 

alternative output variable

 instead of the standard display: 

CO

2

 content in ppm, 

air quality

 (VOC) in %, 

temperature

 in °C, 

relative humidity

 in % r.H., 

atmospheric pressure

 in hPa 

In this case, the first line indicates the value while the second line indicates the corresponding unit

 statically

.  

The index in the third line indicates the display type, e.g. atmospheric pressure (see the table "Function 06 Write Single 
Register"). 

Reading: 

1013

 

Unit: 

hPa 

Index: 

The Modbus interface allows the display screen to be individually configured, both in the 7 segment range and in  
the dot-matrix range. This means that messages such as those from the PLC can be displayed. 
For the 

individual display

, the register 4x0001 (physical value displayed) must contain the value 10.  

The registers 4x0002 to 4x0019 contain information about the characters and segments to be displayed. 
The dot-matrix area is also programmable in the default setting (register 4x0001 contains the value 0).  
In this case, the current measured value is automatically displayed in the 7-segment area.
The two left-aligned positions are represented by the register 4x0003 (range -9...99). The value 0 switches  
off the display of both positions. The display is only active if the register 4x0002 has positive values.

Composition of Segment Pattern   (Register 4x0005)

Bit  0 ......

Dot  A

Bit  1 ......

Dot  B

Bit  2 ......

Dot  C

Bit  3 ......  

Dot  D

Bit  4 ......

Dot  DP1

Bit  5 ......

- -

Bit  6 ......

Dot  E

Bit  7 ......

Dot  DP2

Bit  8 ......

- -

Bit  9 ......

- -

Bit  10 ....

- -

Bit  11 ....

- -

Bit  12 ....

- -

Bit  13 ....

- -

Bit  14 ....  

- -

Bit  15 ....  

- -

  Dot  Matrix 

A  H  B  I  C  J  D  K  E  L  F  M  G  N

Dot A

Dot B

Dot C

Dot D

Dot E

Dot DP1

Dot DP2

Summary of Contents for AERASGARD ACO2-Modbus

Page 1: ... temperature 0 2 K at 25 C AIR QUALITY VOC VOC sensor VOC sensor metal oxide with automatic calibration VOC volatile organic compounds VOC measuring range 0 100 air quality with reference to calibration gas multi range switching VOC sensitivity low medium high VOC measuring accuracy 20 final value with reference to the calibration gas Service life 60 months under normal load conditions CARBON DIOX...

Page 2: ...dicates the following measurements with the corresponding units cyclically and consecutively CO2 content in ppm air quality VOC in temperature in C relative humidity in r H Backlighting is provided for improved legibility The Modbus interface allows the display to be individually configured both in the 7 segment range and in the dot matrix range Display standard Display alternative output variable...

Page 3: ... WG02 Measuring Range Humidity Temperature CO2 Display VOC Item No ACO2 Modbus ACO2 MODBUS 5000 ppm 1501 7110 6001 200 ACO2 MODBUS DISPLAY 5000 ppm 1501 7110 6071 200 ALQ CO2 Modbus ALQ CO2 MODBUS 5000 ppm 0 100 1501 7111 6001 200 ALQ CO2 MODBUS DISPLAY 5000 ppm 0 100 1501 7111 6071 200 AFTM CO2 Modbus AFTM CO2 MODBUS 0 100 r H 35 80 C 5000 ppm 1501 7116 6001 200 AFTM CO2 MODBUS DISPLAY 0 100 r H ...

Page 4: ...uring Range Humidity Temperature CO2 Display VOC Item No KCO2 Modbus KCO2 MODBUS 5000 ppm 1501 8110 6001 200 KCO2 MODBUS DISPLAY 5000 ppm 1501 8110 6071 200 KLQ CO2 Modbus KLQ CO2 MODBUS 5000 ppm 0 100 1501 8111 6001 200 KLQ CO2 MODBUS DISPLAY 5000 ppm 0 100 1501 8111 6071 200 KFTM CO2 Modbus KFTM CO2 MODBUS 0 100 r H 35 80 C 5000 ppm 1501 8116 6001 200 KFTM CO2 MODBUS DISPLAY 0 100 r H 35 80 C 50...

Page 5: ...ve default OFF Inactive OFF The baud rate speed of transmission is set at DIP switches 1 and 2 of DIP switch block B Selectable are 9600 baud 19200 baud or 38400 baud see table Parity is set at DIP switch 3 of DIP switch block B Selectable are EVEN or ODD see table Parity check is activated via DIP switch 4 of DIP switch block B Selectable are active 1 stop bit or inactive 2 stop bits i e no parit...

Page 6: ...n to be individually configured both in the 7 segment range and in the dot matrix range This means that messages such as those from the PLC can be displayed For the individual display the register 4x0001 physical value displayed must contain the value 10 The registers 4x0002 to 4x0019 contain information about the characters and segments to be displayed The dot matrix area is also programmable in ...

Page 7: ... K 76 L 77 M 78 N 79 O 80 P 81 Q 82 R 83 S 84 T 85 U 86 V 87 W 88 X 89 Y 90 Z 91 93 ASCII Sign 94 95 _ 96 97 a 98 b 99 c 100 d 101 e 102 f 103 g 104 h 105 i 106 j 107 k 108 l 109 m 110 n 111 o 112 p 113 q ASCII Sign 114 r 115 s 116 t 117 u 118 v 119 w 120 x 121 y 122 z 123 124 125 129 ü 132 ä 142 Ä 148 ö 153 Ö 154 Ü 223 ASCII characters or control characters are displayed as spaces G HYGRASGARD AF...

Page 8: ...r H 0 Default setting alternative display static CO2 in ppm 1 1 VOC in 2 2 Temperature in C 3 3 Relative humidity in r H 4 4 Atmospheric pressure in hPa 5 5 Freely configurable display 10 4x0002 7 Segment Value Signed 16 bit 999 9999 999 9999 4x0003 7 Segment Value Signed 8 bit 9 99 9 99 4x0004 4x0005 Segment Pattern Unsigned 16 bit See Binary Pattern 4x0006 Dot Matrix Character A Unsigned 8 bit 0...

Page 9: ...Echo telegram 04 Activation listen only mode No answer 10 Delete counter Echo telegram 11 Counter bus telegrams Unsigned 16 bit All valid bus telegrams 12 Counter communication errors Parity CRC frame errors etc Unsigned 16 bit Faulty bus telegrams 13 Counter exception telegrams Unsigned 16 bit Error counter 14 Counter slave telegrams Unsigned 16 bit Slave telegrams 15 Counter telegrams without an...

Page 10: ...he number of subscribers is greater the bus must be subdivided into several segments separated by repeaters The subscriber address can be set from 1 to 247 For the bus line a twisted pair cable data line power supply line and copper mesh wire shield must be used Therefore the line capacitance should be less than 100 pF m e g Profibus cable Slave n MODBUS RTU Master RS 485 Line termination Line ter...

Page 11: ...e devices returned in original packing will be accepted These instructions must be read before installation and putting in operation and all notes provided therein are to be regarded Devices are to be connected under dead voltage condition Devices must only be connected to safety extra low voltage Consequential damages caused by a fault in this device are excluded from war ranty or liability Insta...