Important notes

Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical and 
Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.

In addition, the following points are to be observed:

–  Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors at the device  

(e.g. by voltage induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to 
be observed.

–  This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their  control authorities, 

the TÜV and the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to 
prevent perils of any kind.

–  No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.

–  Consequential damages caused by a fault in this device are excluded from warranty or liability.

–  These devices must be installed by authorised specialists only.

–  The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid. 

Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous 
improvement of our products.

–  In case of any modifications made by the user, all warranty claims are forfeited.

–  This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow. Direct sun irradiation or heat 

 irradiation by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.

–  Operating this device close to other devices that do not comply with EMC directives may influence functionality.

–  This device must not be used for monitoring applications, which serve the purpose of protecting persons against hazards or injury,  

or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.

–  Dimensions of enclosures or enclosure accessories may show slight tolerances on the specifications provided in these instructions.

–  Modifications of these records are not permitted.

–  In case of a complaint, only complete devices returned in original packing will be accepted.

These instructions must be read before installation and putting in operation and all notes provided therein are to be regarded!

Devices are to be connected under dead-voltage condition. Devices 
must only be connected to safety extra-low voltage. Consequential 
damages caused by a fault in this device are excluded from war-
ranty or liability. Installation of these devices must only be realized 
by authorized qualified personnel. The technical data and connect-
ing conditions shown on the device labels and in the mounting 
and operating instructions delivered  together with the device are 
exclusively valid. Deviations from the catalogue representation are 
not explicitly mentioned and are possible in terms of technical pro-
gress and continuous improvement of our products. In case of any 
modifications made by the user, all warranty claims are  forfeited. 
Operating this device close to other devices that do not comply with 
EMC directives may influence functionality. This device must not be 
used for monitoring applications, which solely serve the purpose of 
protecting persons against hazards or injury, or as an EMERGENCY 
STOP switch for systems or machinery, or for any other similar 
safety-relevant purposes.
Dimensions of enclosures or enclosure accessories may show slight 
tolerances on the specifications provided in these instructions. 
Modifications of these records are not permitted. 
In case of a complaint, only complete devices returned in original 
packing will be accepted. 

Notes regarding mechanical mounting and attachment:
Mounting shall take place while observing all relevant regulations 
and standards applicable for the place of measurement  
(e.g. such as welding instructions, etc.). Particularly the following 
shall be regarded:
–  VDE  ⁄  VDI  directive  technical  temperature  measurements,   

measurement set - up for temperature measurements.

– The EMC directives must be adhered to. 
– It is imperative to avoid parallel laying of current-carrying lines.
– We recommend to use shielded cables with  

the shielding being attached at one side to the DDC  ⁄  PLC.

Before mounting, make sure that the existing thermometer‘s techni-

cal parameters comply with the actual conditions at the place of 
 utilization, in particular in respect of:

– Measuring range 
– Permissible maximum pressure, flow velocity 
– Installation length, tube dimensions
– Oscillations, vibrations, shocks are to be avoided (<  0.5  g)
Attention! In any case, please observe the mechanical and thermal 
load limits of protective tubes according to DIN 43763 respectively 
according to specific S+S standards!

G  

Mounting and Installation

Summary of Contents for AERASGARD ACO2-Modbus

Page 1: ... temperature 0 2 K at 25 C AIR QUALITY VOC VOC sensor VOC sensor metal oxide with automatic calibration VOC volatile organic compounds VOC measuring range 0 100 air quality with reference to calibration gas multi range switching VOC sensitivity low medium high VOC measuring accuracy 20 final value with reference to the calibration gas Service life 60 months under normal load conditions CARBON DIOX...

Page 2: ...dicates the following measurements with the corresponding units cyclically and consecutively CO2 content in ppm air quality VOC in temperature in C relative humidity in r H Backlighting is provided for improved legibility The Modbus interface allows the display to be individually configured both in the 7 segment range and in the dot matrix range Display standard Display alternative output variable...

Page 3: ... WG02 Measuring Range Humidity Temperature CO2 Display VOC Item No ACO2 Modbus ACO2 MODBUS 5000 ppm 1501 7110 6001 200 ACO2 MODBUS DISPLAY 5000 ppm 1501 7110 6071 200 ALQ CO2 Modbus ALQ CO2 MODBUS 5000 ppm 0 100 1501 7111 6001 200 ALQ CO2 MODBUS DISPLAY 5000 ppm 0 100 1501 7111 6071 200 AFTM CO2 Modbus AFTM CO2 MODBUS 0 100 r H 35 80 C 5000 ppm 1501 7116 6001 200 AFTM CO2 MODBUS DISPLAY 0 100 r H ...

Page 4: ...uring Range Humidity Temperature CO2 Display VOC Item No KCO2 Modbus KCO2 MODBUS 5000 ppm 1501 8110 6001 200 KCO2 MODBUS DISPLAY 5000 ppm 1501 8110 6071 200 KLQ CO2 Modbus KLQ CO2 MODBUS 5000 ppm 0 100 1501 8111 6001 200 KLQ CO2 MODBUS DISPLAY 5000 ppm 0 100 1501 8111 6071 200 KFTM CO2 Modbus KFTM CO2 MODBUS 0 100 r H 35 80 C 5000 ppm 1501 8116 6001 200 KFTM CO2 MODBUS DISPLAY 0 100 r H 35 80 C 50...

Page 5: ...ve default OFF Inactive OFF The baud rate speed of transmission is set at DIP switches 1 and 2 of DIP switch block B Selectable are 9600 baud 19200 baud or 38400 baud see table Parity is set at DIP switch 3 of DIP switch block B Selectable are EVEN or ODD see table Parity check is activated via DIP switch 4 of DIP switch block B Selectable are active 1 stop bit or inactive 2 stop bits i e no parit...

Page 6: ...n to be individually configured both in the 7 segment range and in the dot matrix range This means that messages such as those from the PLC can be displayed For the individual display the register 4x0001 physical value displayed must contain the value 10 The registers 4x0002 to 4x0019 contain information about the characters and segments to be displayed The dot matrix area is also programmable in ...

Page 7: ... K 76 L 77 M 78 N 79 O 80 P 81 Q 82 R 83 S 84 T 85 U 86 V 87 W 88 X 89 Y 90 Z 91 93 ASCII Sign 94 95 _ 96 97 a 98 b 99 c 100 d 101 e 102 f 103 g 104 h 105 i 106 j 107 k 108 l 109 m 110 n 111 o 112 p 113 q ASCII Sign 114 r 115 s 116 t 117 u 118 v 119 w 120 x 121 y 122 z 123 124 125 129 ü 132 ä 142 Ä 148 ö 153 Ö 154 Ü 223 ASCII characters or control characters are displayed as spaces G HYGRASGARD AF...

Page 8: ...r H 0 Default setting alternative display static CO2 in ppm 1 1 VOC in 2 2 Temperature in C 3 3 Relative humidity in r H 4 4 Atmospheric pressure in hPa 5 5 Freely configurable display 10 4x0002 7 Segment Value Signed 16 bit 999 9999 999 9999 4x0003 7 Segment Value Signed 8 bit 9 99 9 99 4x0004 4x0005 Segment Pattern Unsigned 16 bit See Binary Pattern 4x0006 Dot Matrix Character A Unsigned 8 bit 0...

Page 9: ...Echo telegram 04 Activation listen only mode No answer 10 Delete counter Echo telegram 11 Counter bus telegrams Unsigned 16 bit All valid bus telegrams 12 Counter communication errors Parity CRC frame errors etc Unsigned 16 bit Faulty bus telegrams 13 Counter exception telegrams Unsigned 16 bit Error counter 14 Counter slave telegrams Unsigned 16 bit Slave telegrams 15 Counter telegrams without an...

Page 10: ...he number of subscribers is greater the bus must be subdivided into several segments separated by repeaters The subscriber address can be set from 1 to 247 For the bus line a twisted pair cable data line power supply line and copper mesh wire shield must be used Therefore the line capacitance should be less than 100 pF m e g Profibus cable Slave n MODBUS RTU Master RS 485 Line termination Line ter...

Page 11: ...e devices returned in original packing will be accepted These instructions must be read before installation and putting in operation and all notes provided therein are to be regarded Devices are to be connected under dead voltage condition Devices must only be connected to safety extra low voltage Consequential damages caused by a fault in this device are excluded from war ranty or liability Insta...