The maintenance-free, microprocessor-controlled 

AERASGARD

®

 

ACO

2

 - SD - TYR2

 or 

ATM - CO

- SD - TYR2

 is designed  for on-wall installation and 

is used to detect CO

2

 content as well as gas  temperature. The measurement signals are converted to standard signals of 0 -10 V.  

The CO

2

 content of the air is measured using an optical NDIR sensor (non-dispersive infra-red technology). The detection range of the CO

2

 sensor is 

calibrated for standard applications such as monitoring residential rooms and conference rooms. Room ventilation on an as-needed basis, improved 
well-being and customer benefit, increased comfort as well as reduced operating costs through energy conservation are just some of the benefits of 
employing AERASGARD

® 

CO

2

 sensors.  

A measuring system based on NDIR (non-dispersive infra-red technology) for CO

2

 measurement consists of a light source and a receptor. A certain 

range of wavelengths of light radiated by the source is damped and absorbed by CO

2

 molecules in the measured section. This damping is detected by 

the receptor. 

TECHNICAL DATA

Voltage supply:  

24 V AC ⁄ DC

Average power consumption:  

< 3 VA  at 24 V DC

CARBON DIOXIDE (CO

2

)

Sensor, CO

2

:  

optical NDIR sensor  
(non-dispersive infra-red technology) 

dual-beam measuring system 
with automatic calibration

Measuring range, CO

2

:  

multi-range switching  

(selectable via DIP switches)

 

0...2000  ppm   ⁄  0...5000  ppm

Output, CO

2

:   

0 -10 V 

Measuring accuracy, CO

2

:   

up to 2000  ppm:  ± 70 ppm plus 5 % of measured value 
up to 5000  ppm:  ± 70 ppm plus 10 % of measured value

Temperature  dependence:  

approx.  10  ppm  ⁄  K    at  +25 °C

Pressure dependence:  

± 1.5 % of measured value  ⁄ kPa   
(referred to standard pressure)

Long-term stability:  

± 2 % of final value ⁄ year

Gas exchange:  

by diffusion

TEMPERATURE 

Measuring range, temperature:  

0...+50 °C

Output,  temperature:  

0 -10 V

Warm up time:  

approx. 1 hour 

Ambient  temperature:  

+10...+50 °C   

Humidity: 

< 95 %  r. H.,  non-precipitating  air

Response  time:  

approx. 2 minutes

Electrical connection:  

0.14 - 1.5 mm

2

, via screw terminals

Enclosure:  

plastic, material polyamide,  
30 % glass-globe reinforced,  
with quick-locking screws  
(slotted ⁄ Phillips head combination), 
colour traffic white (similar to RAL 9016)

Dimensions: 

126  x  90  x  50 mm    (Tyr 2)

Cable gland:  

M 16 x 1.5; including strain relief,  
exchangeable

Process connection: 

via screws 

Protection class: 

III  (according to EN 60 730)

Protection type: 

IP 65  (according to EN 60 529) 

Standards: 

CE conformity,  
electromagnetic compatibility according to EN 61 326,  
EMC Directive 2014 ⁄ 30 ⁄ EU 

ACCESSORIES

 

WS-03

 

Weather and sun protection,  
200 x 180 x 150 mm, stainless steel

Summary of Contents for 1501-7110-1000-300

Page 1: ... Operating Instructions Mounting Installation On wall CO2 sensors and measuring transducers with multi range switching and active switching output F Notice d instruction Sonde transmetteur de CO2 pour montage en saillie avec commutation multi gamme et sortie active tout ou rien r Руководство по монтажу и обслуживанию Датчик измерительный преобразователь содержания углекислого газа для открытой уст...

Page 2: ...AERASGARD ACO2 SD TYR2 AERASGARD ATM CO2 SD TYR2 D G F r Maßzeichnung Dimensional drawing Plan coté Габаритный чертеж ACO2 SD TYR2 ATM CO2 SD TYR2 126 112 90 50 4 20 112 M16x1 5 ...

Page 3: ...hme 3 VA bei 24 V DC KOHLENDIOXID CO2 Sensor CO2 optischer NDIR Sensor nicht dispersive Infrarot Technologie Zweistrahl Messverfahren mit automatischer Kalibrierung Messbereich CO2 Mehrbereichsumschaltung über DIP Schalter wählbar 0 2000 ppm 0 5000 ppm Ausgang CO2 0 10 V Messgenauigkeit CO2 bis 2000 ppm 70 ppm zzgl 5 des Messwerts bis 5000 ppm 70 ppm zzgl 10 des Messwerts Temperaturabhängigkeit ca...

Page 4: ...librierung verwendet Stattdessen kann mittels des ent sprechenden Abgleich Potentiometers bei Bedarf der Ausgabewert um bis zu 500 ppm korrigiert werden Inbetriebnahme Nach dem Einschalten des Gerätes erfolgen ein Selbsttest und die Temperierung Dieser Vorgang dauert je nach Umgebungsbedingungen 3 bis 5 Minuten in dieser Zeit weicht die ausgegebene Analogspannung vom tatsächlichen Messwert ab AERA...

Page 5: ...der entfallen alle Gewährleistungsansprüche Dieses Gerät darf nicht in der Nähe von Wärmequellen z B Heizkörpern oder deren Wärmestrom eingesetzt werden eine direkte Sonnen einstrahlung oder Wärmeeinstrahlung durch ähnliche Quellen starke Leuchte Halogenstrahler ist unbedingt zu vermeiden Der Betrieb in der Nähe von Geräten welche nicht den EMV Richtlinien entsprechen kann zur Beeinflussung der Fu...

Page 6: ...DE CO2 Sensor CO2 optical NDIR sensor non dispersive infra red technology dual beam measuring system with automatic calibration Measuring range CO2 multi range switching selectable via DIP switches 0 2000 ppm 0 5000 ppm Output CO2 0 10 V Measuring accuracy CO2 up to 2000 ppm 70 ppm plus 5 of measured value up to 5000 ppm 70 ppm plus 10 of measured value Temperature dependence approx 10 ppm K at 25...

Page 7: ...tomatic calibration is not used Instead the output value can be corrected by up to 500 ppm by means of the corresponding calibration potentiometer if required Putting in operation After switching on the device a self test and tempering period follows This procedure takes 3 to 5 minutes depending on ambient conditions During this time the output analog voltage differs from the actual measured value...

Page 8: ...ifications made by the user all warranty claims are forfeited This device must not be installed close to heat sources e g radiators or be exposed to their heat flow Direct sun irradiation or heat irradiation by similar sources powerful lamps halogen spotlights must absolutely be avoided Operating this device close to other devices that do not comply with EMC directives may influence functionality ...

Page 9: ...ES TECHNIQUES Alimentation en tension 24 V ca cc Consommation électrique moyenne 3 VA à 24 V cc DIOXYDE DE CARBONE CO2 Capteur CO2 capteur optique NDIR technologie infrarouge non dispersive procédé de mesure à double faisceaux avec étalonnage automatique Plage de mesure CO2 commutation multi gamme sélectionnable via interrupteur DIP 0 2000 ppm 0 5000 ppm Sortie CO2 0 10 V Précision de mesure CO2 j...

Page 10: ...pas utilisé En cas de besoin il est cependant possible de corriger la valeur de sortie jusqu à 500 ppm au moyen du potentiomètre de réglage correspondant Mise en service Après la mise en marche de l appareil celui ci effectue un autocontrôle et l équilibrage de température En fonction des conditions d environnement cette opération dure entre 3 et 5 minutes pendant ce temps la tension analogique ém...

Page 11: ...tion continue de nos produits En cas de modifications des appareils par l utilisateur tous droits de garantie ne seront pas reconnus Cet appareil ne doit pas être utilisé à proximité des sources de chaleur par ex radiateurs ou de leurs flux de chaleur il faut impérativement éviter un ensoleillement direct ou un rayonnement thermique provenant de sources similaires lampes très puissantes projecteur...

Page 12: ...АЗ CO2 Анализатор CO2 оптический NDIR недисперсионная инфракрасная технология двухлучевым методом измерения с автоматической калибровкой Диапазон измерения CO2 переключение диапазонов измерения можно выбрать при помощи DIP переключателя 0 2000 млн 1 0 5000 млн 1 Выход CO2 0 10 B Погрешность измерения CO2 до 2000 млн 1 70 млн 1 плюс 5 от измеренного значения до 5000 млн 1 70 млн 1 плюс 10 от измере...

Page 13: ...бровка не применяется Вместо этого с помощью соответствующего уравнивающего потенциометра при необходимости можно откорректировать выводимую величину на макс 500 млн 1 Запуск в эксплуатацию После включения прибора начинается самотестирование и терморегулирование Этот процесс длится от 3 до 5 минут в зависимости от окружающих условий в это время выходное аналоговое напряжение отличается от измеренн...

Page 14: ...ебителем гарантийные обязательства теряют силу Не разрешается использование прибора в непосредственной близости от источников тепла например радиаторов отопления или создаваемых ими тепловых потоков следует в обязательном порядке избегать попадания прямых солнечных лучей или теплового излучения от аналогичных источников мощные осветительные приборы галогенные излучатели Эксплуатация вблизи оборудо...

Page 15: ...ontre les intempéries et le soleil en option Приспособление для защиты от непогоды и солнечных лучей опция Copyright by S S Regeltechnik GmbH Nachdruck auch auszugsweise nur mit Genehmigung von S S Regeltechnik GmbH gestattet Reprints in part or in total are only permitted with the approval of S S Regeltechnik GmbH La reproduction des textes même partielle est uniquement autorisée après accord de ...

Page 16: ...лючения 1 2 3 UB 24V AC DC Ausgang CO2 0 10V in ppm UB GND 1 2 3 4 5 6 UB 24V AC DC Ausgang CO2 0 10V in ppm UB GND GND n c in C Ausgang Temperatur 0 10V OFFSET C CO 1 ON DIP 1 2 3 4 5 6 Ausgang Temperatur in C n c GND CO Sensor UB GND Ausgang CO in ppm UB 24V AC DC DIP 1 ON 5000 ppm OFF 2000 ppm 1 2 3 4 5 6 UB 24V AC DC Output CO2 0 10V in ppm UB GND GND n c in C Output temperature 0 10V 1 2 3 UB...

Reviews: