background image

AERASGARD

® 

RFTM - LQ - CO

2

 - Modbus

D G F r

Herzlichen Glückwunsch!  
Sie haben ein deutsches Qualitätsprodukt erworben.
Congratulations!  
You have bought a German quality product.
Félicitations !    
Vous avez fait l’acquisition d’un produit allemand de qualité.
Примите наши поздравления !   
Вы приобрели качественный продукт, изготовленный в Германии.

D

  

Bedienungs- und Montageanleitung

Multifunktionaler Raumfühler bzw. Messumformer, 
für Feuchte, Temperatur, Luftgüte (VOC) und CO

2

 - Gehalt,   

kalibrierfähig, mit 

Modbus

-Anschluss

G

  

Operating Instructions, Mounting & Installation

Multifunctional room sensors and measuring transducers, 
for humidity, temperature, air quality (VOC) and CO

2

 content,  

calibratable, with 

Modbus 

connection

F

  

Notice d’instruction

Sonde d'ambiance (transmetteur) multifonctionnelle, 
pour l'humidité, la température,  
la qualité d'air (COV) et de teneur en CO

2

,  

étalonnable, avec raccordement

 Modbus  

r

  

Руководство по монтажу и обслуживанию

Мультифункциональный датчик для помещений ⁄ измерительный  
преобразователь, для измерения влажности, температуры, 
качества воздуха (VOC) и содержания CO

2

,  

калибруемый, с подключением к шине 

Modbus

S+S REGELTECHNIK GMBH 
PIRNAER STRASSE 20 
90411 NÜRNBERG ⁄ GERMANY

FON  +49 (0) 911 ⁄ 5 19  47- 0 
FAX  +49 (0) 911 ⁄ 5 19  47- 70

[email protected] 
www.SplusS.de

6003-4700-2017-000

  34700-2017  V101

  03/2017

Summary of Contents for 1501-61B0-6001-200

Page 1: ...t Modbus Anschluss G Operating Instructions Mounting Installation Multifunctional room sensors and measuring transducers for humidity temperature air quality VOC and CO2 content calibratable with Modb...

Page 2: ...2 AERASGARD RFTM LQ CO2 Modbus D G F r T K 6 0 98 98 32 6 RCO2 Modbus RLQ CO2 Modbus RFTM CO2 Modbus RFTM LQ CO2 Modbus Ma zeichnung Dimensional drawing Plan cot Baldur 2...

Page 3: ...usschnittstelle RS 485 galvanisch getrennt Busabschluss ber DIP Schalter aktivierbar Bis zu 32 Ger te auf einem Segment m glich Bei gr erer Anzahl von Ger ten m ssen RS 485 Transceiver eingesetzt werd...

Page 4: ...tive Ausgangsgr en Anzeige individuell programmierbar AERASGARD RCO2 Modbus Raum CO2 F hler Deluxe AERASGARD RLQ CO2 Modbus Raum Luftqualit ts VOC und CO2 F hler Deluxe AERASGARD RFTM CO2 Modbus Multi...

Page 5: ...t 2 Stoppbits OFF inaktiv default OFF inaktiv OFF Die Baudrate bertragungsgeschwindigkeit wird ber Pos 1 und 2 des DIP Schalters B eingestellt Einstellbar sind 9600 Baud 19200 Baud oder 38400 Baud sie...

Page 6: ...miert werden Somit k nnen auch beispielsweise Meldungen von der SPS angezeigt werden F r die individuelle Anzeige muss das Register 4x0001 physikalischer Anzeigewert den Wert 10 enthalten Die Register...

Page 7: ...D 69 E 70 F 71 G 72 H ASCII Sign 73 I 74 J 75 K 76 L 77 M 78 N 79 O 80 P 81 Q 82 R 83 S 84 T 85 U 86 V 87 W 88 X 89 Y 90 Z 91 93 ASCII Sign 94 95 _ 96 97 a 98 b 99 c 100 d 101 e 102 f 103 g 104 h 105...

Page 8: ...ed 8 Bit 0 10 0 10 Standardanzeige zyklisch VOC in CO2 in ppm Temperatur in C relative Feuchte in r H 0 Default einstellung alternative Anzeige statisch CO2 in ppm 1 1 VOC in 2 2 Temperatur in C 3 3 r...

Page 9: ...Listen Only Mode Echo Telegramm 04 Aktivierung Listen Only Mode Keine Antwort 10 L sche Z hler Echo Telegramm 11 Z hler Bustelegramme Unsigned 16 Bit alle g ltigen Bustelegramme 12 Z hler Kommunikati...

Page 10: ...er Repeater getrennte Segmente aufzuteilen Die Teilnehmeradresse kann von 1 bis 247 eingestellt werden F r die Busleitung ist ein Kabel mit paarverseilter Datenleitung Spannungsversorgung und Kupferab...

Page 11: ...e sicherheitsrelevante Aufgaben verwendet werden Die Geh use und Geh usezubeh rma e k nnen geringe Toleranzen zu den Angaben dieser Anleitung aufweisen Ver nderungen dieser Unterlagen sind nicht gesta...

Page 12: ...der Ger te darf nur durch Fachpersonal erfolgen Es gelten ausschlie lich die technischen Daten und Anschlussbedingungen der zum Ger t gelieferten Montage und Bedienungs anleitung Abweichungen zur Kata...

Page 13: ...13...

Page 14: ...DIP switch Bus interface RS 485 galvanically isolated bus termination can be activated via DIP switch Up to 32 devices possible in one segment In case of a greater number of devices RS 485 transceiver...

Page 15: ...output variables Display individually programmable AERASGARD RCO2 Modbus Room CO2 sensor Deluxe AERASGARD RLQ CO2 Modbus Room air quality VOC and CO2 sensor Deluxe AERASGARD RFTM CO2 Modbus Multifunct...

Page 16: ...Aktive ON ODD numbered OFF Inactive no parity 2 stop bits OFF Inactive default OFF Inaktive OFF The baud rate speed of transmission is set at DIP switches 1 and 2 of DIP switch block B Selectable are...

Page 17: ...This means that messages such as those from the PLC can be displayed For the individual display the register 4x0001 physical value displayed must contain the value 10 The registers 4x0002 to 4x0012 co...

Page 18: ...65 A 66 B 67 C 68 D 69 E 70 F 71 G 72 H ASCII Sign 73 I 74 J 75 K 76 L 77 M 78 N 79 O 80 P 81 Q 82 R 83 S 84 T 85 U 86 V 87 W 88 X 89 Y 90 Z 91 93 ASCII Sign 94 95 _ 96 97 a 98 b 99 c 100 d 101 e 102...

Page 19: ...0 0 10 Standard display cyclic VOC in CO2 in ppm temperature in C relative humidity in r H 0 Default setting alternative display static CO2 in ppm 1 1 VOC in 2 2 Temperature in C 3 3 Relative humidity...

Page 20: ...ten only mode Echo telegram 04 Activation listen only mode No answer 10 Delete counter Echo telegram 11 Counter bus telegrams Unsigned 16 bit All valid bus telegrams 12 Counter communication errors Pa...

Page 21: ...number of subscribers is greater the bus must be subdivided into several segments separated by repeaters The subscriber address can be set from 1 to 247 For the bus line a twisted pair cable data line...

Page 22: ...ure accessories may show slight tolerances on the specifications provided in these instructions Modifications of these records are not permitted In case of a complaint only complete devices returned i...

Page 23: ...ialists only The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively valid Deviations from the catalogue representati...

Page 24: ...24...

Page 25: ...ivable via interrupteur DIP Jusqu 32 appareils possibles sur un segment Pour un nombre sup rieur d appareils utiliser des metteurs r cepteurs RS 485 Protocole de bus Modbus mode RTU plage d adresses r...

Page 26: ...5000 ppm 0 100 1501 61B8 6001 200 RFTM LQ CO2 MODBUS DISPLAY 0 100 h r 0 50 C 5000 ppm 0 100 1501 61B8 6021 200 Attention Cet appareil ne doit pas tre utilis comme un dispositif de s curit Via l inter...

Page 27: ...de Baud vitesse de transfert est r gl via les pos 1 et 2 de l interrupteur DIP B On peut r gler 9600 Baud 19200 Baud ou 38400 Baud voir tableau La parit est r gl e via la pos 3 de l interrupteur DIP...

Page 28: ...rice de point Il est ainsi possible par exemple d afficher les messages de l API Pour l affichage librement programmable le registre 4x0001 valeur d affichage physique doit contenir la valeur 10 Les r...

Page 29: ...66 B 67 C 68 D 69 E 70 F 71 G 72 H ASCII Sign 73 I 74 J 75 K 76 L 77 M 78 N 79 O 80 P 81 Q 82 R 83 S 84 T 85 U 86 V 87 W 88 X 89 Y 90 Z 91 93 ASCII Sign 94 95 _ 96 97 a 98 b 99 c 100 d 101 e 102 f 10...

Page 30: ...Temp rature en C Humidit relative en h r 0 R glage par d faut Affichage alternatif statique CO2 en ppm 1 1 COV en 2 2 Temp rature en C 3 3 Humidit relative en r H 4 4 Affichage librement configurable...

Page 31: ...T l gramme d cho 04 Activation Listen Only Mode mode coute seule Pas de r ponse 10 Efface compteur T l gramme d cho 11 Compteur T l grammes de bus Unsigned 16 Bit Tous les t l grammes de bus valides...

Page 32: ...dants le bus doit tre r parti en plusieurs segments par l interm diaire de repeaters L adresse des correspondants peut tre fix e de 1 247 Pour la ligne de bus on peut utiliser un c ble avec ligne de d...

Page 33: ...es Il est possible que les dimensions du bo tier et des accessoires du bo tier divergent l g rement des indications donn es dans cette notice Il est interdit de modifier la pr sente documentation En c...

Page 34: ...ialiste qualifi Seules les donn es techniques et les conditions de raccordement indiqu es sur la notice d instruction accompagnant l appareil sont applicables des diff rences par rapport la pr sentati...

Page 35: ...35...

Page 36: ...15 x Modbus CO2 VOC CO2 0 5000 1 VOC LOW MEDIUM HIGH 0 50 C 0 100 VOC NDIR 10 1 2 3 4 1 2 3 4 shield shield U GND A B U GND A B mode address zero offset CO CO VOC VOC r H C 1 2 3 4 5 6 7 8 ON DIPA 1...

Page 37: ...ODBUS DISPLAY 5000 1 1501 61B0 6021 200 RLQ CO2 Modbus RLQ CO2 MODBUS 5000 1 0 100 1501 61B1 6001 200 RLQ CO2 MODBUS DISPLAY 5000 1 0 100 1501 61B1 6021 200 RFTM CO2 Modbus RFTM CO2 MODBUS 0 100 0 50...

Page 38: ...IP DIP 1 128 DIP 1 ON DIP 2 64 DIP 2 ON DIP 3 32 DIP 3 OFF DIP 4 16 DIP 4 OFF DIP 5 8 DIP 5 OFF DIP 6 4 DIP 6 OFF DIP 7 2 DIP 7 OFF DIP 8 1 DIP 8 ON 128 64 1 193 Modbus DIP 1 DIP 2 MODBUS DIP B 9600 O...

Page 39: ...8 3 C 7 14 4x0001 10 4 0002 4 0012 4x0001 0 7 4x0005 0 A 1 B 2 C 3 D 4 DP 5 6 7 8 9 10 11 12 13 14 15 A A B C D E F G B C D DP 14 1 14 2 14 4x0003 4x0004 0 A 1 B 2 C 3 D 4 E 5 F 6 G 7 G 8 H 9 I 10 J 1...

Page 40: ...64 65 A 66 B 67 C 68 D 69 E 70 F 71 G 72 H ASCII 73 I 74 J 75 K 76 L 77 M 78 N 79 O 80 P 81 Q 82 R 83 S 84 T 85 U 86 V 87 W 88 X 89 Y 90 Z 91 93 ASCII 94 95 _ 96 97 a 98 b 99 c 100 d 101 e 102 f 103 g...

Page 41: ...32 16 0 500 0 0 50 0 C 3x0007 4 16 0 1000 0 0 100 0 3x0008 32 16 0 1000 0 0 100 0 06 Write Single Register 16 Write Multiple Register 4x0001 8 0 10 0 10 VOC 1 C 0 1 1 1 VOC 2 2 C 3 3 4 4 10 4x0002 7...

Page 42: ...ic VOC 3 0 1 OFF ON 0x0005 VOC low 4 0 1 OFF ON 0x0006 VOC medium 5 0 1 OFF ON 0x0007 VOC high 6 0 1 OFF ON 0x0008 7 0 1 OFF ON 08 Diagnostics 00 Loopback 01 Modbus Reset Listen Only Mode 04 Listen On...

Page 43: ...Modbus Modbus 32 1 247 100 Profibus Slave n MODBUS RTU Master RS 485 20 n 40 n Slave 1 Slave 2 LA LA A D1 D 5 B GND B D0 D MODBUS RTU Master Slave 1 Slave 2 r AERASGARD RFTM LQ CO2 Modbus Rev 2017 V14...

Page 44: ...44 EMV VDE VDI DDC PLC 0 5 g DIN 43763 S S r...

Page 45: ...45 ZVEI VDE r...

Page 46: ...46...

Page 47: ...ift up the bottom frame slightly Pull top cover forward and hold it Pour ouvrir le bo tier placer le tournevis 2 0 au centre de l encoche pousser vers le bas et soulever l g rement le cadre inf rieur...

Page 48: ...120 0 1 1 1 1 0 0 0 121 0 1 1 1 1 0 0 1 122 0 1 1 1 1 0 1 0 123 0 1 1 1 1 0 1 1 124 0 1 1 1 1 1 0 0 125 0 1 1 1 1 1 0 1 126 0 1 1 1 1 1 1 0 127 0 1 1 1 1 1 1 1 128 1 0 0 0 0 0 0 0 129 1 0 0 0 0 0 0 1...

Reviews: