background image

G  

General notes

–  This device may only be used in non-precipitating air without above-atmospheric or below-atmospheric pressure at the sensor element. 
–  The voltage output is short-circuit proof. 
–  Applying overvoltage will destroy the device.
–  In case of pollution, we recommend cleaning and recalibration in the factory. 
–  The device operating range covers 10 ... 95  % relative humidity respectively 0 ... 50 °C.  

Outside of that range, mismeasurements or increased deviations will occur. 

–  The device calibrates itself at an interval of 7 days. To ensure this function, the device needs to be supplied with  

fresh air (CO

2

 content 300  ppm ... 400  ppm) at least for 10 minutes during each 7-day period. 

–  If this device is operated beyond the specified range, all warranty claims are forfeited.

Our “General Terms and Conditions for Business“ together with the “General Conditions for the Supply of Products and Services of the Electrical 

and Electronics Industry“ (ZVEI conditions) including supplementary clause “Extended Retention of Title“ apply as the exclusive terms and conditions.

In additionIn addition, the following points are to be observed:
–  These instructions must be read before installation and putting in operation and all notes provided therein are to be  regarded!
–  Devices must only be connected to safety extra-low voltage and under dead-voltage condition. To avoid damages and errors the device  

(e.g. by voltage induction) shielded cables are to be used, laying parallel with current-carrying lines is to be avoided, and EMC directives are to 

be observed.

–  This device shall only be used for its intended purpose. Respective safety regulations issued by the VDE, the states, their  control authorities, 

the TÜV and the local energy supply company must be observed. The purchaser has to adhere to the building and safety regulations and has to 

prevent perils of any kind.

–  No warranties or liabilities will be assumed for defects and damages arising from improper use of this device.
–  Consequential damages caused by a fault in this device are excluded from warranty or liability.
–  These devices must be installed by authorised specialists only.
–  The technical data and connecting conditions of the mounting and operating instructions delivered together with the device are exclusively 

valid. Deviations from the catalogue representation are not explicitly mentioned and are possible in terms of technical progress and continuous 

improvement of our products.

–  In case of any modifications made by the user, all warranty claims are forfeited.
–  This device must not be installed close to heat sources (e.g. radiators) or be exposed to their heat flow. Direct sun irradiation or heat 

 irradiation by similar sources (powerful lamps, halogen spotlights) must absolutely be avoided.

–  Operating this device close to other devices that do not comply with EMC directives may influence functionality.
–  This device must not be used for monitoring applications, which solely serve the purpose of protecting persons against hazards or injury,  

or as an EMERGENCY STOP switch for systems or machinery, or for any other similar safety-relevant purposes.

–  Dimensions of enclosures or enclosure accessories may show slight tolerances on the specifications provided in these instructions.
–  Modifications of these records are not permitted.
–  In case of a complaint, only complete devices returned in original packing will be accepted.

These instructions must be read before installation and putting in operation and all notes provided therein are to be regarded!

Connecting scheme 

Parallel operation

Connecting scheme 

Individual operation

SUPPLY  VOLTAGE :

For operating voltage reverse polarity protection, a one-way rectifier or 
reverse polarity protection diode is integrated in this device variant. 

 

This internal one-way rectifier also allows operating 0 - 10 V devices on AC 
supply voltage.

The output signal is to be tapped by a measuring instrument. Output 
 voltage is measured her against zero potential (O V) of the input voltage!

When this device is operated on 

DC supply voltage

,  the operating voltage 

input UB+ is to be used for 15...36 V DC supply and UB – or GND for ground 
wire!

When several devices are supplied by one 24 V

 AC voltage supply

, it is to 

be ensured that all ”positive“ operating voltage input terminals (+) of the 
field devices are connected with each other and all ”negative“ operating 
voltage input terminals (–) (= reference  potential) are connected together 
(in-phase connection of field devices). All outputs of field devices must be 
referenced to the same potential!

In case of reversed polarity at one field device, a supply voltage short- 
circuit would be caused by that device. The consequential short-circuit 
current flowing through this field device may cause damage to it.

Therefore, pay attention to correct wiring!

Circuitry

Circuitry

0...10V

0V/GND

0...10V

0V/GND

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

Circuitry

0...10V

0V/GND

V

Power supply

AC 24V~ 

0V

DC 15-36V =  GND

Summary of Contents for 1501-1110-1001-022

Page 1: ...usgang G Operating Instructions Mounting Installation On wall CO2 sensors respectively measuring transducers self calibrating with multi range switching and active output or active switching output F...

Page 2: ...AERASGARD ACO2 D G F r Ma zeichnung Dimensional drawing Plan cot ACO2 73 40 73 5 17 108 40 20 M16x1 5...

Page 3: ...her Luftdruckkompensation Messbereich Mehrbereichsumschaltung ber DIP Schalter w hlbar 0 2000 ppm 0 5000 ppm 0 10000 ppm Ausgang 0 10 V oder mit potentialfreiem Wechsler 24 V Messgenauigkeit CO2 70 pp...

Page 4: ...t werden Sonde 2 Nach dem Anschlie en des Ger tes ist ein Dauerbetrieb von mindestens 10 Minuten bei Frischluft CO2 Gehalt 300 400 ppm sicherzustellen Die manuelle Kalibrierung des Ausgangssignals auf...

Page 5: ...stetigen Verbesserung unserer Produkte m glich Bei Ver nderungen der Ger te durch den Anwender entfallen alle Gew hrleistungsanspr che Dieses Ger t darf nicht in der N he von W rmequellen z B Heizk r...

Page 6: ...pm 0 10000ppm Output 0 10 V or with potential free changeover contact 24 V Measuring accuracy CO2 70 ppm plus 5 of measured value Pressure dependence 0 5 of measured value kPa at compensated versions...

Page 7: ...bration of carbon dioxide measurement Manual calibration can be started independently from the position of the DIP4 switch by pushing the button probe 2 After connecting the device a period of at leas...

Page 8: ...in terms of technical progress and continuous improvement of our products In case of any modifications made by the user all warranty claims are forfeited This device must not be installed close to hea...

Page 9: ...e commutation multi gamme interrupteur DIP 0 2000 ppm 0 5000 ppm 0 10000 ppm Sortie 0 10 V ou avec inverseur libre de potentiel 24 V Incertitude de mesure 70 ppm 5 de la Vf D pendance de la pression 0...

Page 10: ...nage manuel de la mesure du dioxyde de carbone L talonnage manuel peut tre lanc ind pendamment de la position de l interrupteur DIP4 en actionnant le bouton poussoir capteur 2 Apr s le branchement de...

Page 11: ...nt pas mentionn es explicitement et sont possibles suite au progr s technique et l am lioration continue de nos produits En cas de modifications des appareils par l utilisateur tous droits de garantie...

Page 12: ...14 x ACO2 ACO2 W ACO2 ACO2 W 1 2 3 5 6 7 ACO2 W min max 2000 5000 10000 auto 1 2 34 ON ATM Sensor plug Set CO 2 Output CO 2 content 0 10V UB 24V AC DC UB GND Breaker Normally open CO2 range Switching...

Page 13: ...2 DIP 3 0 2000 pp ON OFF OFF 0 5000 pp OFF ON OFF 0 10000 pp OFF OFF ON CO2 DIP 4 ON OFF 1 CO2 CO2 ACO2 ACO2 0 2000 5000 10000 pp 0 10 ATM 1501 1110 1001 022 ACO2_DISPLAY 0 2000 5000 10000 pp 0 10 AT...

Page 14: ...50 C 7 300 400 ppm 10 7 ZVEI VDE EMV 0 10 0 UB 15 36 UB GND 24 Circuitry Circuitry 0 10V 0V GND 0 10V 0V GND Power supply AC 24V 0V DC 15 36V GND Circuitry 0 10V 0V GND V Power supply AC 24V 0V DC 15...

Page 15: ...niques Copyright by S S Regeltechnik GmbH Nachdruck auch auszugsweise nur mit Genehmigung von S S Regeltechnik GmbH gestattet Reprints in part or in total are only permitted with the approval of S S R...

Page 16: ...AERASGARD ACO2 D G F r...

Reviews: