10
4. Attach an approved ‘rain-tight’ or ‘wet location’ hub to the conduit. After the hub is attached
to the conduit, attach the hub to the enclosure.
5. Connect the GFCI protected, 15A max, supply voltage line to the right side of the terminal
block. Strip ¼” of insulation and then connect the wires to the marked terminals and tighten
securely.
120V Hot GFCI Load to terminal marked:
H
120V Neutral GFCI Load to terminal marked:
N
Electrical System Ground to terminal marked:
GND
6. Replace and secure the metal input voltage isolation barrier and verify that the input wiring
screw terminals are secure.
12VAC
13VAC
POWER INPUT
NEUTRAL
POWER INPUT
POWER INPUT
GROUN
D
COM
GROUN
D
GND
N
H
Input Wiring Locations
O u t p u t W i r i n g f o r L i g h t s a n d L i g h t S o u r c e s
1. The combined load of all lights connected to the poolLUX
®
Plus must not exceed the following:
• pLX-PL60 = 60 watts max
• pLX-PL100 = 100 watts max
2. The enclosure provides four (4) output conduit locations. If additional conduit terminations
are required, an approved junction box may be used as a termination point and multiple output
cables may be run through a single feeder conduit to the poolLUX
®
Plus.
3a
3b
1a
2a
1b
2b
Locations of Input
Power Knockouts
Locations of Output
Power Knockouts
GND
12V
L/V
13V
Fuse Holder