MOUNTING OF FLUE THERMOSTAT
Ensure that the flue thermostat is firmly and securely inserted in or bonded to the flue pipe.
WATER CONNECTION
The water connections are at the bottom of the unit. Where pipe connections are rigid, flexible connections
may be used to compensate for mechanical and thermal stresses.
IMPORTANT
Isolation valves should be fitted to all connections to facilitate maintenance operations.
All water connections are female threaded with a union in accordance with ISO 228/1 G3 / 4 “F.
CAUTION
Take care when tightening the unit connections to avoid distortion of the copper tubes. Do not apply
excessive torque and support connections adequately.
CAUTION
All units are pressure tested with water. It is possible that seals have suffered a natural volume
reduction due to drying. The installer should check all connections and tighten them if necessary
to restore the compression of the gasket. The installer is responsible for ensuring that the entire
system is watertight.
NOTE
Ensure thorough flushing of the system, to eliminate dirt, before commissioning.
A
Flow to System
C
Return from System
D
Return to Stove
E
Flow from Stove