4 MC500-1ERV

Figure 6

A

A - Core Removal (See Figure 5)

1.  Remove Access panels by opening each panel and 

then releasing the spring loaded pins in the hinges by 

pinching the tabs together. 

2.  Remove the center divider panel by removing the two 

5/16

" screws at with end of the panel on the side of the 

MiniCore.

3.  Carefully slide the core outwards.

B - Filter Removal (See Figure 6)

1.  Open the Filter Access panel by opening the two 

spring loaded latches to expose filters.

2. 

Slide filters outwards.

Figure 5

Unit

A

B

C

MCV500

42 

¼

51

15 

1/2

MCV1000

20 

¾

C

B

Summary of Contents for MiniCORE MCV-500

Page 1: ...nergy by transferring heat energy across two opposing air streams using a polymer core heat exchanger This process works in the summer by rejecting the heat energy from incoming intake air and in the winter by conserving the heat energy from the exhaust air allowing outdoor ventilation rates to be increased by factors of three or more without additional energy penalty or increase in size of the he...

Page 2: ...re 3 High voltage 115V Connect the high voltage wires to L1 Hot L2 Common hook the ground wire to the provided grounding nut See Wiring Diagrams on Pages 6 7 208 230V Single phase Connect the high voltage wires to L1 Hot L2 Common connect the ground wire to the provided ground nut Check Voltage into the unit and adjust the voltage input to the transformer from 230V to 208V if necessary by switchin...

Page 3: ...read across the MiniCore Figure 4 B Air Balancing Adjustment 1 Remove plastic plugs in access panels 4 total 2 With a manometer measure pressure drop inches of water column diagonally across the MiniCore Unit CFM for 3 speed PMC motors is determined then by referring to Table 1 on Page 5 3 Repeat the same process for the other airflow vector of MiniCore 4 System can be balanced by adding dampers t...

Page 4: ...s together 2 Remove the center divider panel by removing the two 5 16 screws at with end of the panel on the side of the MiniCore 3 Carefully slide the core outwards B Filter Removal See Figure 6 1 Open the Filter Access panel by opening the two spring loaded latches to expose filters 2 Slide filters outwards Figure 5 Unit A B C MCV500 42 1 4 51 15 1 2 MCV1000 20 3 4 C B ...

Page 5: ...Static Pressure in wc 0 0 0 1 0 2 0 3 0 4 0 5 0 6 0 7 0 8 0 9 1 0 CFM Input Voltage v 2 38 3 138 80 15 4 238 182 121 52 5 339 284 226 164 101 50 6 439 386 332 275 216 164 7 539 488 438 386 331 278 227 175 123 71 19 8 640 590 543 498 446 393 347 298 249 200 151 9 740 692 649 609 561 507 467 421 375 330 284 10 741 693 650 610 562 508 456 410 373 326 291 Performance Test for MCV1000 with ECM Motor Su...

Page 6: ...6 MC500 1ERV MCV500 MCV1000 UNIT WIRING DIAGRAM Notes 1 Selective voltage terminal for proper unit voltage Mini Ventilator W Factory Installed Options 115V 230V 1 PH Unit 01 C45 C75 C150 02xH 01 21 ...

Page 7: ...e terminal for proper unit voltage 2 Omit BL 25 BL 30 for 0 10V Signal Control Wire BL 25 to TB39 1 and BL 30 to TB40 1 for low speed Wire BL 25 to TB39 2 BL 30 to TB40 2 for high speed Mini Ventilator W Factory Installed Options 115V 230V 1 PH Unit 01 C45 C75 C150 02xE 01 21 ...

Page 8: ...ation If blower motor fans are running backwards de energize power to the unit then swap reversing plug on motors to change direction Re check Perform all start up procedures outlined in the installation manual shipped with the unit Fill in the Start Up Information as outlined on the opposite side of this sheet Provide owner with information packet Explain the thermostat and unit operation START U...