background image

rUSKIn EFAMS ThErMAl DISpErSIon AIrFlow MEASUrIng SYSTEM InSTAllATIon InSTrUCTIonS

8

Finishing the Installation

 

Finishing the Installation 

 

 

 

1. Connect a shielded CAT5e cable between the 

Communication Port RJ45 connector on the router 

(see 

Figure 7 and Figure 8

) to the Communication 

Port RJ45 connector on the Electronic Controller 

(see 

Figure 7 and Figure 8

) .

 

 

 

 

2. Connect a shielded CAT5e cable between the Power 

Port RJ45 connector on the router (see 

Figure 7 and 

Figure 8)

 to the Power Port RJ45 connector on the 

Electronic Controller (see 

Figure 7 and Figure 8).

 

 

3. Use nylon cable clamps (included in parts bag) to 

secure RJ45 cable between the sensors and the 

router, and between the router and the Electronic 

Controler. Space cable clamps on 6 in. (152 mm) 

centers. 

4. Move the Electronic Controller’s power switch (see 

Figure 9)

 to the ON position. 

5. Use the LCD Contrast Adjustment screw (see 

Figure 9)

 to adjust the LCD contrast as desired: 

• Turn the screw clockwise to increase contrast. 

• Turn the screw counterclockwise to decrease 

contrast. 

6. Use the Options Menu to configure the Electronic 

Controller for your application. See 

Setup and 

Adjustments 

for specific instructions. 

7. After configuring the Electronic Controller, replace 

the cover. 

 

 

RUSKIN EFAMS Thermal Dispersion Airflow Measuring System Installation Instructions 

power

port

router

Fan Inlet

Sensors

Communication

port

Communication

Cable

Electronic Controller

Communication port

power port

power

Cable

Sensor Cables

Figure 8: EFAMS System Components

note: Ensure that the Fan Inlet Sensor Cables are 
plugged into the corresponding Router Sensor Ports.
1. Connect shielded CAT5e cable between the 

Communication Port RJ45 connector on the router 

(see

 Figure 8 and Figure 9) to the Communication 

Port RJ45 connector on the Electronic Controller 

(see

 Figure 8 and Figure 9).

2. Connect the included shielded CAT5e cable 

between the Power Port RJ45 connector on the 

router (see

 Figure 8 and Figure 9) to the Power 

Port RJ45 connector on the Electronic Controller 

(see

 Figure 8 and Figure 9).

3. Use nylon cable clamps (included in parts bag) 

to secure RJ45 cable between the sensors and 

the router. Space cable clamps on 6 in. (152 mm) 

centers.

4. Move the Electronic Controller’s power switch (see 

Figure 7 )  to the ON position and follow the on 

screen prompts to complete initial setup.

  Initial setup must be completed in order to use 

the Options Menu to configure the Electronic 

Controller for your application.  See Setup and 

Adjustments for specific instructions.

5. After configuring the Electronic Controller, replace 

the cover.

note: If the LCD screen displays “ERROR! CHECK 
CAT5 CABLE AND RESET” please check for a loose 
connection, a damaged cable, or an improperly ter-
minated cable.
rEQUIrED InITIAl STArTUp FIElD  
CAlIBrATIon:
The EFAMS product is designed to introduce the 
least amount of pressure drop and corresponding 
energy penalty.  The EFAMS does not sample 100% 
of the air flowing into a fan, but instead, measures an 
air flow that will track the air flow through the fan. 
For initial setup, the fan must be run at three known 
flows to complete initial installation.
Follow on screen prompts. See Balancer Field  
Calibration Mode Figure 9.

InITIAl STArTUp FIElD CAlIBrATIon

Firmware Version 8.6

The electronic fan inlet air measurement station must be field calibrated by running the fan at three increasing, known air flow 

values, Low, Medium and High, or using air flow measurements provided by a Test & Balance (T&B) contractor. It is recommend-

ed to record damper positions and drive speeds while T&B is on site to facilitate recalibration anytime measurement equipment 

must be moved or replaced. 
RESET SETTING will not delete or reset field calibration settings. 
FIELD CALIBRATION OFF will delete field calibration settings and setup steps must then be repeated to restore calibrated op-

eration. DO NOT TURN OFF FIELD CALIBRATION unless setup is being reinitiated.
ZERO CUTOFF is adjusted after completion of Field Calibration. A non-zero display is normal and expected when the fan is 

turned off after completion of field calibration. With the fan off and the dampers closed so that NO air is flowing through the fan, 

use the up or down arrow and record the highest reading displayed on any single sensor. Enter a value that is slightly greater 

than this amount as the zero cutoff value. OFFSET values when used will always be added to all subsequent readings and 

should not be used in place of a zero cutoff value.  
Field Calibration Overview:
When power is applied to the installed electronic fan inlet air measurement station and equipment is properly installed and con-

nected INITIAL STARTUP FIELD CALIBRATE is displayed. To complete the setup the fan must be able to run at low, medium 

and high air flows. With the fan running at a known Low flow value, the UP and DOWN buttons on the transmitter box will be 

used to adjust the display so that the value displayed on the transmitter box matches the actual air flow occurring at that same 

time.  The ENTER key is used to input that value and will automatically advance the display prompt to the next step. The fan 

speed and air flow must then be increased to the medium flow value before the Middle flow values is input. And finally the fan 

speed and air flow through the fan inlet must be increased to the highest expected Max flow before the Max Flow Point is en-

tered. Power will then be cycled and the calibrated air flow will be displayed while the fan is running. The ZERO CUTOFF is set 

AFTER completion of the Balancer Field Calibration steps. 

Summary of Contents for EFAMS

Page 1: ...ance Manual Model EFAMS Electronic Fan Inlet Air Temperature Measuring Station with Electronic Controller II EFAMS 818 Replaces II EFAMS 316 ALL STATED SPECIFICATIONS ARE SUBJECT TO CHANGE WITHOUT PRI...

Page 2: ...e harmful interference in which case the user will be required to correct the interference at his her own expense Only a qualified service technician should install this system To avoid unsatisfactory...

Page 3: ...0 FT 3 05 M COMMUNICATION CABLES between Router and Electronic Controller Shielded CAT5e with shielded RJ45 type connectors using simple pairing 10 FT 3 05 M Standard 20 FT 6 10 M Optional 30 FT 9 14...

Page 4: ...ct the fan inlet opening to ensure no obstructions or irregularities interfere with installation of the sensors Install the two fan inlet sensors opposite one another within the fan inlet bell Place t...

Page 5: ...size in Table A Secure the sensor cables to the back of the rods with multiple zip ties The cables must be carefully and securely attached so that they do not move when the fan is operating Sensors s...

Page 6: ...and outputs See Wiring IMPORTANT Avoid running this device s wiring in the same conduit as AC power wiring or with wiring used to suppy highly inductive loads such as motors contactors and relays Test...

Page 7: ...r applied as accidental arcing may damage the prod uct and will void the warranty Figure 7a Setup and Adjustment Figure 7b Setup and Adjustment ROUTER CONNECTIONS During Normal Operation LED s will il...

Page 8: ...amaged cable or an improperly ter minated cable REQUIRED INITIAL STARTUP FIELD CALIBRATION The EFAMS product is designed to introduce the least amount of pressure drop and corresponding energy penalty...

Page 9: ...y Increase the fan speed to the second op erating air flow point With air passing across the sensors at the middle speed adjust the transmitter display using the up and down buttons until the value di...

Page 10: ...reen clears To scroll through each of the menu options press UP and DOWN on the Electronic Controller see Figure 7 RESET SETTINGS LCD ON OFF ERROR INDICATION TEST SIGNAL UNITS GAIN OFFSET ZERO CUTOFF...

Page 11: ...y want to make note of them before you reset the Electronic Con troller The default values are denoted in Figures 11 through 21 with an asterisk Figure 11 ARE YOU SURE Figure 12 DISPLAY Figure 13 ERRO...

Page 12: ...Use UP and DOWN to select SI or IU unit systems Select SI for FPM or CFM with temperature in degrees Fahrenheit Select UI for MPS or LPS with temperature in degrees Celsius Use UP and DOWN to scroll t...

Page 13: ...put of the Electronic Controller and the test and balance report adjust the gain We recommend setting the gain to 1 and taking multiple readings to determine the difference To calculate the gain divid...

Page 14: ...culation and is applied to the 4 to 20 mA output signal only Scale Velocity mA Output Signal This option allows the user to improve the resolution of the output signals by changing the start and end p...

Page 15: ...ure Display on the Electronic Controller ON or OFF AUTO RESET ON AUTO RESET OFF TEMPERATURE ON TEMPERATURE OFF Figure 23 Temperature Display ON OFF Submenu Figure 22 Auto Reset ON OFF Submenu Figure 2...

Page 16: ...MC SPR is static safe and nonflammable Troubleshooting 3900 Dr Greaves Rd Kansas City MO 64030 816 761 7476 FAX 816 765 8955 www ruskin com Technical Specifications EFAMS Thermal Dispersion Fan Inlet...

Reviews: