4  Type Test Specifications 

 

Electrical Safety 

Levels 

Comments 

Dielectric Withstand 

2 kV rms for 1 minute 

ANSI/IEEE C37.90 (1989) 

IEC 60255-5 (Section 6) 

High Voltage Impulse 

5 kV peak 

IEC 60255-5 (Section 8) 

Insulation Resistance 

500 VDC for 1 minute 

IEC 60255-5 (Section 6 

 

Electrical Environment 

Levels 

Comments 

High Frequency Disturbance 

(Oscillatory) 

2.5 kV @ 1MHz for 2s 

ANSI/IEEE C37.90.1 

IEC 60255-22-1 

IEC Surge 

4 kV / 2 kV 

IEC 61000-4-5 

(Level 4) 

IEC Fast Transient 

2 kV / 1 kV 

IEC 61000-4-4 

(Level 4) 

ANSI/IEEE Fast Transient 

4 kV 

ANSI/IEEE C37.90.1 

IEC Radiated RFI Immunity 

10 V/m 

IEC 61000-4-3 

ANSI/IEEE Radiated RFI 

Immunity 

35 V/m 

ANSI/IEEE C37.90.2 

ESD 

(Electrostatic Discharge) 

15 kV (air discharge) 

8 kV (contact) 

IEC 61000-4-2 

(Level 4) 

 

Atmospheric Environment 

Levels 

Comments 

Temperature (Dry Cold) 

-40

°

IEC 60068-2-1 

Test Ad: 16 hrs @ -40

°

Temperature (Dry Heat) 

85

°

IEC 60068-2-2 

Test Bd: 16 hrs @ 85

°

Humidity 

95% 

Non-condensing 

IEC 60068-2-30 

Test Db: 6 cycles, 55

°

C, 95% 

Humidity 

Summary of Contents for RuggedMC RMC40

Page 1: ...ugged RuggedMC MC MC MC RMC40 RMC40 RMC40 RMC40 Installation Guide RuggedCom Inc 30 Whitmore Road Woodbridge Ontario Canada L4L 7Z4 Web http www ruggedcom com Tel 905 856 5288 Fax 905 856 1995 Toll Fr...

Page 2: ...ser s authority to operate the equipment Caution This product contains a laser system and is classified as a CLASS 1 LASER PRODUCT Caution Use of controls or adjustments or performance of procedures o...

Page 3: ...Mounting 7 2 2 Panel Mounting 8 2 3 Power Supply Wiring and Grounding 9 2 4 RJ45 Ports Signal Description 10 3 Specifications 11 3 1 Power Supply Specifications 11 3 2 Twisted Pair Port Specifications...

Page 4: ...erterTM family exceeds that of commercial media converters by having no rotating mechanical parts i e no cooling fans utilizing high temperature solid state components and incorporating the necessary...

Page 5: ...Detail Dual LC Style 100BaseFX fiber optic connector shown ITEM Activity Comments Solid Yellow Link Established RJ45 Lk Act Blinking Yellow Tx Rx Activity Solid Yellow 100Mbps Operation RJ45 100 Off 1...

Page 6: ...6 2006 RuggedCom Inc All rights reserved Rev101 1 4 RuggedMCTM Side and Bottom View Fig 1 4 1 RuggedMCTM Side and Bottom View...

Page 7: ...7 2006 RuggedCom Inc All rights reserved Rev101 2 Installation 2 1 DIN Rail Mounting Fig 2 1 1 RuggedMCTM DIN Rail Mounting...

Page 8: ...e 2 2 1 shows an example of an RMC unit panel mounted using the optional panel mount adapter The panel mount adapter can be secured to a panel with three screws The RuggedMCTM product is easily mounte...

Page 9: ...s used as the ground conductor for all surge and transient suppression circuitry internal to the RuggedMCTM Chassis Ground is connected to the Safety Ground terminal for AC inputs or the equipment gro...

Page 10: ...rom high amplitude high energy transients that can potentially damage the RMC40TM and its link partners In general RuggedCom strongly recommends limiting connections used by the RJ45 ports to those th...

Page 11: ...VAC 3 15A T 2 3 W Notes 1 This is the same power supply for both AC and DC 2 T Denotes time delay fuse CAUTION For continued protection against risk of fire replace only with same type and rating of f...

Page 12: ...5 100BaseFX MM MTRJ 1310 50 125 16 11 33 5 11 2 17 100BaseFX SM SC 1310 9 125 13 5 31 4 20 20 100BaseFX SM LC 1310 9 125 15 8 31 5 15 16 5 Notes 1 Maximum segment length is greatly dependent on factor...

Page 13: ...uggedCom Inc All rights reserved Rev101 3 5 Operational Specifications Parameter Specification Notes Conversion Type Cut Through High speed non blocking Mac Address Table Length 2048 Frame Buffer Memo...

Page 14: ...c All rights reserved Rev101 3 6 Mechanical Specifications Parameter Value Comments Dimensions 4 30 x 2 40 x 3 30 inches 110 x 61 x 84 mm Length x Width x Height Weight 1 5 lb 0 68 Kg Enclosure 18 gau...

Page 15: ...or 2s ANSI IEEE C37 90 1 IEC 60255 22 1 IEC Surge 4 kV 2 kV IEC 61000 4 5 Level 4 IEC Fast Transient 2 kV 1 kV IEC 61000 4 4 Level 4 ANSI IEEE Fast Transient 4 kV ANSI IEEE C37 90 1 IEC Radiated RFI I...

Page 16: ...CSA C22 2 No 60950 UL 60950 EN 60950 EN 61000 6 2 Approved FCC FCC Part 15 Class A Approved CISPR EN55022 Class A Approved FDA CDRH 21 CFR Chapter 1 Subchapter J Compliant IEC EN EN60825 1 1994 A11 19...

Reviews: