8
| MPS...E
EN
Installation, operating and maintenance instructions
9. DATA IN ACCORDANCE WITH ERP DIRECTIVE 327/2011 OF THE EUROPEAN PARLIAMENT
Units / Model
MPS 225 E2 21
MPS 250 E2 20
MPS 280 E2 20
MPS 315 E2 21
ID-number
137879
126646
126647
137079
ErP-conformity
2015
2015
2015
2015
1
Overall efficiency η
es
[%]
46,5
53,4
53,4
51,7
2
Measurement category
A
A
A
A
3
Efficiency category
Static
Static
Static
Static
4
Efficiency grade at optimum energy efficiency point N
63,1
67,6
65,3
62
5
Variable speed drive
not integrated /
has to be installed
not integrated /
has to be installed
not integrated /
has to be installed
not integrated /
has to be installed
6
Year of manufacture
see nameplate
7
Manufacturer name / Commercial registration number / Place of
establishment
ruck Ventilatoren GmbH / Local District Court Mannheim HRB 560366 /
Germany
8
Nominal motor power input at optimum energy efficiency point P
e
[kW]
0,26
0,44
0,73
1,2
9
Volumetric flow at optimum energy efficiency point q
V
[m³/h]
1104
1678
2212
2576
10
Static pressure at optimum energy efficiency point p
sf
[Pa]
424
541
681
914
11
Rotations per minute at the optimum energy efficiency point n [1/
min]
2853
2841
2725
2806
12
The specific ratio
The specific ratio is close to 1 and significantly below 1.11.
13
Information on dismantling, recycling and disposal
Observe the user manual of this product.
14
Optimal life
Observe the user manual of this product.
15
Description of additional items used when determining the fan
energy efficiency, such as ducts, that are not described in the
measurement category and not supplied with the fan.
No special items have been used for determining the fan energy efficien-
cy, except the required connection components according to the measure-
ment category.
Units / Model
MPS 400 E4 21
MPS 450 E4 20
MPS 500 E4 21
ID-number
138005
126652
138045
ErP-conformity
2015
2015
2015
1
Overall efficiency η
es
[%]
48,1
52,5
54,3
2
Measurement category
A
A
A
3
Efficiency category
Static
Static
Static
4
Efficiency grade at optimum energy efficiency point N
62
63,7
63,3
5
Variable speed drive
not integrated / has to
be installed
not integrated / has to
be installed
not integrated / has to
be installed
6
Year of manufacture
see nameplate
7
Manufacturer name / Commercial registration number / Place of
establishment
ruck Ventilatoren GmbH / Local District Court Mannheim HRB 560366 /
Germany
8
Nominal motor power input at optimum energy efficiency point P
e
[kW]
0,32
0,87
1,4
9
Volumetric flow at optimum energy efficiency point q
V
[m³/h]
2989
4365
5717
10
Static pressure at optimum energy efficiency point p
sf
[Pa]
318
399
515
11
Rotations per minute at the optimum energy efficiency point n [1/
min]
1347
1341
1380
12
The specific ratio
The specific ratio is close to 1 and significantly below 1.11.
13
Information on dismantling, recycling and disposal
Observe the user manual of this product.
14
Optimal life
Observe the user manual of this product.
15
Description of additional items used when determining the fan
energy efficiency, such as ducts, that are not described in the
measurement category and not supplied with the fan.
No special items have been used for determining the fan energy efficien-
cy, except the required connection components according to the measure-
ment category.
Summary of Contents for MPS 225 E2 21
Page 17: ...EN NOTES www ruck eu 17...