background image

 

Real Time Automation, Inc. 

63 

1-800-249-1612 

 

 

 

 

 

Mapping 

– Manual Configure Mode to Auto-Configure Mode 

To transition from Manual Configure Mode to Auto-Configure Mapping Mode, click the dropdown menu 
at the top of the Mapping Configuration page and select Auto-Configure Mappings.  

 

Click 

OK

 to proceed to delete all current mappings and go back to Auto-Configure Mappings Mode. Click 

Cancel

 to keep all mappings and remain in Manual Configure Mode.   

NOTE

: Once you revert to Auto-Configure Mapping Mode there is no way to recover the mappings you 

lost. Any mappings you previously have added will be deleted as well. 

Summary of Contents for 460PBSA-N70PB

Page 1: ...Real Time Automation Inc 1 1 800 249 1612 Firmware Version 8 7 22 460PBSA N70PB Protocol Gateway Product User Guide ...

Page 2: ...sion or limitation of incidental or consequential damages therefore the limitations set forth in this agreement may not apply to you No patent liability is assumed by Real Time Automation with respect to use of information circuits equipment or software described in this manual Government End Users If this software is acquired by or on behalf of a unit or agency of the United States Government thi...

Page 3: ...ion Auto Server Mode Default 20 Auto Configure Group by Device vs Auto Configure Group by Data Type 21 Group by Device Default Method 21 Group by Data Type 21 PROFIBUS Slave Slot Configuration Manual Mode 22 Setting up the PLC Example Using Simatic Classic Step 7 23 Setting up the PLC Example Using TIA Portal 27 ASCII Configuration 32 Receive Data 33 Receive Data Operation Mode 34 Transmit Data 35...

Page 4: ... Configure Mode 62 Mapping Manual Configure Mode to Auto Configure Mode 63 View as Text 64 Data Mapping 64 String Mapping 64 Base Triggering Data Validiation Triggering 65 Security Configuration 67 Security Configuration Security Levels 68 Security Log In 69 Security Log Out 69 Email Configuration 70 Alarm Configuration 71 Diagnostics Alarm Status 73 Alarms Active 73 Alarms Clear 74 Change of Stat...

Page 5: ...Real Time Automation Inc 5 1 800 249 1612 Save and Replace Configuration Using SD Card 87 Saving Configuration Using SD Card 87 Replacing Configuration Using SD Card 87 Utilities 88 ...

Page 6: ... 7 4 9 1 20 Features Added 1 BMS BM DFM DS DM TCP USB PBS have been ported to the latest base software 2 TCP BMS BM now Available on N2E and N2EW hardware Platform 3 New ASCII Mode Available on TCP A USB WI protocols 4 User Guides updated with more examples Bug Fixes 1 Improved Data Mapping and String Mapping performance 2 Improved functionality performance on EC ETC ES MC MS BS BC A WI PS protoco...

Page 7: ...re the 460PBSA N70PB gateway For further customization and advanced use please reference the appendices located on the CD or online at http www rtautomation com product 460 gateway support If at any time you need further assistance do not hesitate to call Real Time Automation support Support Hours are Monday Friday 8am 5pm CST Toll free 1 800 249 1612 Email support rtautomation com ...

Page 8: ...ch as LEDs For these sections be sure to identify the hardware platform you are using To find which hardware platform you are using 1 Look on the front or back label of the unit for the part number 2 On the webpage inside the gateway navigate to the dropdown menu under Other and select Utilities Click the Listing of Revisions button The full part number is displayed here Once you have the full par...

Page 9: ...nc 9 1 800 249 1612 Hardware N70PB Powering the Gateway 1 Connect a 12 24 VDC power source to the gateway a Use Barrel Connector with Center Outer Shell OR b 2 Pin Terminal power connection with Red Wire Black Wire NOT BOTH ...

Page 10: ...eters These settings must match the settings of the device s that you are connecting to When you have completed your port configuration click the Save Parameters button Note The PROFIBUS port is NOT configurable The only configuration that the PROFIBUS port requires is the Slave Address on the PROFIBUS Slave Configuration page ...

Page 11: ...e under the DIN Rail 3 While pressing the 460PBSA N70PB against the rail press up to engage the spring loaded lower clip and rotate the unit parallel to the DIN Rail 4 Release upward pressure Removing Follow these steps to remove your interface converter 1 Press up on unit to engage the spring loaded lower clip 2 Swing top of the unit away from DIN Rail DIN Rail Spring Loaded Lower Clip ...

Page 12: ...rogram from the CD ROM 3 Find unit under Select a Unit a Change Gateway s IP address to match that of your PC if DHCP has failed i You will know DHCP has failed if the gateway s IP address is AutoIP at 169 254 X Y ii If successful it will say DHCP d at ex 192 168 0 100 or however your DCHP Client is set up b If you do not see the gateway in this tool then your PC is most likely set up as a static ...

Page 13: ...efault Gateway 2 The gateway must be on the same Network Subnet as the PC whether it s setup for DHCP or Static Once you have both devices on the same network you should be able to ping the gateway using a MS DOS Command Prompt The Screenshot above shows a gateway that is currently set to a static IP Address of 192 168 0 100 If you are able to successfully ping your gateway open a browser and try ...

Page 14: ...ted after every change Multiple changes can be made before a restart but they will not be committed until the gateway is restarted When all desired changes have been made press the Restart Now button The webpage will redirect to our rebooting page shown below The reboot can take up to 20 seconds o If the IP address has not been modified the gateway will automatically redirect to the main page o If...

Page 15: ...bled Configuration cannot be changed during Running Mode If changes are needed click the Configuration Mode button shown in the green box below Configuring Mode Protocol communication is stopped and no data is transmitted Configuration is allowed Navigation green box below You can easily switch between modes and navigate between pages Configuration Diagnostics and Other pages using the buttons on ...

Page 16: ...vice Configuration The device configuration area is where you assign the device description parameter Changes can only be made when the gateway is in Configuration Mode Once you are done configuring the Description click the Save Parameters button ...

Page 17: ...e Once you are done configuring the Network Settings click the Save Parameters button If you are changing the IP Address of the gateway the change will not take effect until the unit has been rebooted After reboot you must enter the new IP Address into the URL It is recommended to leave the DNS Gateway set to 0 0 0 0 and the Ethernet Link as Auto Negotiate If configuring the gateway to use E mail ...

Page 18: ...the gateway 2 Enter a unique Slave Address for the device on the network Note To properly set communication to the PROFIBUS controller you will need to install the GSD file provided on the CD that was shipped with the unit or download from our website https www rtautomation com 460 gateway support For instructions on how to do this please see the How to import a GSD file using Simatic Step 7 Softw...

Page 19: ...gurable Options include 2 4 8 16 24 and 32 bytes 3 Data Format sets the formatting of the data Automap will use this packing size to map data to from the other protocol There are two ways to configure this protocol 1 Auto Configure Group by Device Default 2 Auto Configure Group by Data Type 3 Manual Mode NOTE You may go back and forth between modes but when reverting from Manual Mode to Auto Serve...

Page 20: ... Uint matching signs whenever possible 5 Any 32 Bit Float will be mapped as 32 Bit Float 6 Any 64 Bit Float will be mapped as 64 Bit Float 7 Any Strings will be mapped as Short String 8 Any coils or 1 8 16 32 Bit Binary Packs will be mapped as Binary 8 Bit Pack Binary 16 Bit Pack Binary 32 Bit Pack matching bit sizes whenever possible 9 The input or output direction depends on whether it is config...

Page 21: ... other protocol on the gateway and auto configures the data groups in the PROFIBUS slave for all the data points within the other protocol Another way to view this option is to say that the data points allocated are packed together so there is very little wasted data space The data is packed or optimized Example Protocol A is a master client protocol that has 2 devices with the same setup Device_1...

Page 22: ...additional data slots or you want to modify the data slot s that already exist 5 To delete the data slots that are already there and start over press Cancel 6 Input Slots Select the data size in bytes to move data from the gateway to the controller Then select the data format for that slot 7 Output Slots Select the data size in bytes to move data from the controller to the gateway Then select the ...

Page 23: ... the following example in your controller 1 In your project click the CPU and you should see the Hardware option in the right pane Double click on the Hardware icon 2 In your project click the CPU and you should see the Hardware option in the right pane Double click on the Hardware icon 3 Under Options select Install GSD Files ...

Page 24: ... GSD file 6 Select the GSD file from the box and click Install 7 When prompted to confirm installation because it cannot be undone click Yes 8 Click OK acknowledging that the install was successful 9 If you navigate to the right hand side you will see the RTA profile under PROFIBUS DP Additional Field Devices General profichip Real Time Automation 460XXPBS ...

Page 25: ...00 249 1612 10 Once found drag the Standard icon into the network line you created in Step 9 11 Double click the gateway icon to open the properties window Be sure setup the Slave address that will match the 460PBS configuration page ...

Page 26: ...guration in the 460 gateway add one 8 byte input module one 32 byte input module and one 32 byte output module to your device configuration 13 To configure the PLC to match the 460 gateway you will need to utilize 3 slots in your PLC NOTE When using a Short String Data Type the 1st byte of each slot is reserved for the Length field The remaining bytes will be used for the actual data ...

Page 27: ...rtal This is how you would set up the following example in your controller 14 In your project click the Device View tab and click your PROFIBUS card 15 IF YOU HAVE ALREADY INSTALLED THE GSD FILE SKIP TO STEP 9 OTHERWISE Under Options select Manage general station description file GSD ...

Page 28: ...shipped with the gateway or download file from our website and save off the GSD file to your desktop 17 Click and browse to where you saved the GSD file 18 Check the box to the left of the imported path and click Install 19 Click Close when it was installed successfully ...

Page 29: ... side of the screen under the Hardware catalog and you will see the RTA profile under Other field devices PROFIBUS DP General Real Time Automation profichip Real Time Automation 4 460xxPBS 460xxPBS 22 Drag the 460XXPBS next to the PLC click the Not Assigned and select the PLC to connect to 23 Click the Device View tab ...

Page 30: ...ress that will match the 460PBS configuration page 26 To configure the PLC to match the RTA gateway you will need to utilize 3 slots in your PLC NOTE When using a Short String Data Type the 1st byte of each slot is reserved for the Length field The remaining bytes will be used for the actual data ...

Page 31: ...eters button is clicked a message will appear on how many slots to configure in your controller Because PROFIBUS doesn t care about the ordering you can assign in your controller anyway so as long there are 3 slots and the input output bytes match 28 Compile download program to your PLC Terminology Note and Example I addresses refer to Input Q addresses refer to Output B refers to bytes and W refe...

Page 32: ... new ASCII device 2 The Enable check box should be selected for the device 3 Port Select which port is being used for communication This port must be configured on the Port USB or TCP IP depending on your product Configuration page If it has not yet been configured it will not display in this dropdown 4 Enter a Device Label to identify the device within the gateway 5 LED Inactivity Timeout Enter t...

Page 33: ...age Length varies in size then use a timeout to call the message complete rather than message length You can also use End Delimiters below to call a message complete 4 Number of Start Delimiters Select the number of delimiters that the gateway should look for before the gateway processes the data 5 Select Start Delimiters Select the Start Delimiters that the gateway should look for 6 Number of End...

Page 34: ...radley PLC Next time the operator scans the same barcode HelloWorld The ASCII side gathers the data but the data didn t change so it will not be sent over to the ETC portion of the RTA gateway The operator scans 1234567890 with the barcode scanner The ASCII side of the RTA gateway will process the data and since the data has changed it will be sent over to ETC and sent over to the PLC Mark Data Ne...

Page 35: ...device 4 Delay Between Messages Enter the amount of time in ms that the gateway waits before verifying a Change of State of the ASCII message OR will start the Transmit Timeout 5 Number of Start Delimiters Select the number of delimiters that will be added onto the beginning of the ASCII string 6 Select Start Delimiters Select the Start Delimiters that should be added to the ASCII string 7 Number ...

Page 36: ...e s hello Send hello again nothing will happen because of the RTA Change of State Rule b Option 2 Technology Triggering A USB TCP WI This method is chosen if the Transmit Timeout field is left at 0 and the Trigger Variables as described in ASCII Configuration Technology Triggering Method section of this manual are mapped This will disable Change of State This method is recommended if your product ...

Page 37: ...gy Triggering Method section of this manual are also mapped Example 3 From the PLC send a message of hello based on whatever gets Triggered first the 3000ms Timeout or the Trigger data point the ASCII device will get updated If the Trigger data point is not updated the then the RTA gateway will send the data every x ms to the ASCII device See below for more examples in the ASCII Configuration Tech...

Page 38: ... but messages can still be sent via the Cyclic method if configured For more information on the ASCII Triggering Methods please see the Transmit Data Triggering Methods section of this user guide How the triggering method works The example shown below is our 460PS A TCP USB 1 The mating protocol sends a numbered value to the ASCII TransTrigger diagnostic variable This value must be different from ...

Page 39: ...ransTrigger is between 1 65534 AND the value IS equal to the TransHandshake diagnostic variable then no new message will transmit until Slot 12 0 triggers again RTA460 Display Data Example d If TransTrigger is between 1 65534 AND the value IS NOT equal to the TransHandshake diagnostic variable then a new message will be transmitted The value in TransTrigger will then be moved to TransHandshake TIA...

Page 40: ...rror will be flagged if the actual number of fields is less than this value 3 Parsing Delimiter This defines the delimiter that will be used to parse an ASCII message If delimiters are not present select UNUSED and use the length fields to parse the message 4 Start Location Length a If a Parsing Delimiter is used the Start Location will be the first character of the data field The Length will be t...

Page 41: ...In this example we are separating the fields in the string 12 25 SP100 temp setpoint using the start and length parameters The first value is being parsed from the 1st character for a length of 5 and stored into a float data type The second value is being parsed from the 7th character for a length of 5 characters and stored into a string data type The third value is being parsed starting from the ...

Page 42: ... value is being parsed from the 1st character for a length of 2 and stored into an integer data type The second value is being parsed from the 3rd character of the second comma parsed field for the remainder of that field and stored into an integer data type The third value is being parsed starting from the 1st character of the third comma parsed field for that entire field and stored into a strin...

Page 43: ... appear between each of the fields select UNUSED 3 Data Type Select the data type of the parsed value a Signed and Unsigned 8 16 32 64 Bit Integers b 32 64 Bit Floating Points c String in order to use a String data type must be selected in the other protocol Cannot concatenate an Integer to a String d Constant String 4 Internal Tag Name Constant Name a If Data Type other than Constant String is se...

Page 44: ...eroes Spaces or Nothing to the remaining character placeholders The padding will occur to the left of the value 8 Add Delim Used when a Concatenating Delimiter is selected Check to add the Concatenating Delimiter to the end of that field 9 Sample Result This will display an example of how the data will output This will not display live data It provides an example of the string structure NOTE Sampl...

Page 45: ...00A0 3 Field 3 32 bit int represented as Trans_Field03 It will output as an integer with a max of 10 characters padded with spaces and a comma will be added to the end of the value o EX ____123456 shown with _ s to see spaces 4 Field 4 32 bit float represented as Trans_Field04 It will output as a float with 2 decimal places with a max of 10 characters padded with zeros and a comma will be added to...

Page 46: ...th the following delimiters then a sample result is pictured below Example 1 Sample Result This use case is sending data via 5 PLC tags Using the Concatenating setup example and the Transmit example the ASCII data will display within your ASCII device shown as the example below ...

Page 47: ...ng the Data Mapping webpage It is mapped just like the Status_XY variable described in the Data Mapping Adding Diagnostic Information section of this user guide Example For this example the other protocol in the gateway is the Allen Bradley PLC As you can see from the picture below the RecvCount for ASCII Device 1 is mapped to the first index of a PLC tag array called test_cnt The data type of thi...

Page 48: ...teway will automatically take the string data type from one protocol and map it into the other See String Auto Configure section for more details Option 3 Manual Configure Mappings If you don t want to use the Auto Configure Mappings function you must use the manual mapping feature to configure translations Option 4 Manipulation Scaling You can customize your data by using math operations scaling ...

Page 49: ...Display Data button to view how the data is mapped and what the values of each mapping are Here you will see how each data point excluding strings is mapped To view select the device from the dropdown menu and click View to generate the information regarding that device Then select either the Protocol 1 to Protocol 2 or Protocol 2 to Protocol 1 button correlating to the direction you wish to see t...

Page 50: ...I3 on BACnet NOTE If a data point is mapped twice only the first instance of it will show here EX If Modbus 400001 400040 from Slave 1 are both mapped to AI1 only 400001 will show as being mapped to AI1 If there are values of on this page it indicates that the source has not yet been validated and no data is being sent to the destination The example below reflects the Modbus to PLC flow of data Th...

Page 51: ...view the actual data mappings click the Edit Mapping button For more details see the Data Mapping Explanation section To view the data mappings purely as text click the View as Text button For more details see the View Data Mapping as Text section ...

Page 52: ...ups from a string click the dropdown menu to generate the information regarding that device The string data will be displayed in both Hex and ASCII only the ASCII data is sent The example below shows data that is coming from the source device A group will be displayed for each Parsing Concatenating String field that is configured In the Group drop down Line1 is defined on the ASCII Device configur...

Page 53: ...s Info drop down and navigating to ASCII Diagnostics page You will also have to select the port you want to view in the dropdown below ASCII To view the string mappings click the Edit Mapping button For more details see the String Mapping Explanation section NOTE Only String data types can be mapped to another String data type To view the string mappings purely as text click the View as Text butto...

Page 54: ...ion would look like my example below There are more detailed examples of what all the fields represent in the ASCII Parsing section The message is broken up into 3 Groups or Parsing fields To view the Entire message click on the Diagnostic drop down select Diagnostics Info Select ASCII click view select your Port Whole data will be in the Last Message Sent Diagnostic box ...

Page 55: ...data type If the Auto Configure function does not map the data as you want or you want to add modify the mappings you may do so by going into Manual Configure mode The following are examples of the Auto Configure function 1 This example shows a common valid setup a Both Source values were able to be mapped to a corresponding Destination value 2 This example shows how Auto Configure will make its b...

Page 56: ...t then only 1 operation is allowed c Select the Operation s to perform i Math Operations are performed in the order they are selected ii If more than one point is selected on the source the Math Operations will be performed on every point d Enter the value s for the operation Example of Add similar for Subtract Multiple Divide and MOD This will add a value of 10 to the source field before it is wr...

Page 57: ...case In this example Ram0 is scaled into Ram1 Ram1 is then increased by 5 and stored into Ram2 Ram0 and Ram2 could be considered a source or destination group 2 Temporary Ram Double a This is like the Temporary Ram Int 64 except manipulations will be conducted against the 64bit floating point to allow for large data 3 Ticks Per Second a The gateway operates at 200 ticks per second This equates to ...

Page 58: ...ays to map the NetBmpStat Option 1 Map the whole 32bit value to a destination Example below shows the NetBmpStat is going to an Analog BACnet object Using a connection of 5 Modbus Slave devices AI1 will show a value of 31 0000 Open a calculator with programmer mode and type in 31 this will represent bits 0 4 are on This mean all 5 devices are connected and running If using an AB PLC with a Tag def...

Page 59: ...ault 0x80 7 128 nonrecoverable fault For this example the ETC Status is mapped to a PLC tag called PLC_Status Example ETC Status is 0x00000013 19 decimal here is the break down Hex Bit Decimal Explanation 0x01 0 on 1 if we are a Master Client 0x02 1 on 2 connected 0 not connected 0x10 4 on 16 running usually added to connected Total 0x13 19 External Faults 0x0000FF00 bit 8 15 2nd byte Hex Bit Posi...

Page 60: ...le fault config err 0x10 28 268 435 456 Configuration Mode 0x20 29 536 870 912 No Ethernet Cable Plugged In For this example the MC Status is mapped to a PLC tag called MC_Status Example MC Status is 0x00010041 65601 decimal here is the break down we know that bytes 1 and 3 are being used so here is the break down Common Status Hex Bit Decimal Explanation 0x01 0 on 1 if we are a Master Client 0x40...

Page 61: ...e string 1 Enable red box above Check to enable mapping If not checked this mapping is skipped 2 Source Field yellow box above a Group Select the string data group you set up in the protocol config to use for this mapping b String This is the string used for this mapping 3 Destination Field green box above a Group Select the string data group you set up in the protocol config to use for this mappi...

Page 62: ...nual Configure Mode or click Cancel to remain in Auto Configure Mappings Mode Once OK is clicked there are 2 options on how to proceed from here 1 To keep the mappings that are already configured press OK a You would want this option if you are adding additional mappings or you want to modify the mapping s that already exist 2 To delete the mappings that are already there and start over press Canc...

Page 63: ...top of the Mapping Configuration page and select Auto Configure Mappings Click OK to proceed to delete all current mappings and go back to Auto Configure Mappings Mode Click Cancel to keep all mappings and remain in Manual Configure Mode NOTE Once you revert to Auto Configure Mapping Mode there is no way to recover the mappings you lost Any mappings you previously have added will be deleted as wel...

Page 64: ... at register 1 and want to see if 400011 is mapped If it is not in this text box then it is not mapped and no data will be transferred This is the text display for the example shown under the Data Mapping Adding Diagnostic Information section String Mapping The View as Text page displays the string mapping s you set up in the String Mapping section Each line on this page will read as follows Mappi...

Page 65: ...hake value is set equal to Trigger value 5 Map Handshake to reference data point Note is an internal reference to the Server Slave number you are settings up ex RTA Server Slave products can only be Trigger 1 and Handshake 1 since we are only 1 device If RTA is a Master Client then you can have a Trigger for each server slave connected too How do you set this up In this example I m using a 460MCBS...

Page 66: ...appings 4 The first mapping is going to be the Data Validation Triggering AO21 will write to the RTA MC Trigger 1 will mark data invalid 5 The second mapping the MC Handshake will increment that all data is validated and write to AI21 all data is validated The value of AI40 and AO21 should be the same ...

Page 67: ...max of 32 characters case sensitive a Re enter the Password 4 E mail In case the password was forgotten a user can have their password e mailed to them if e mail was configured 5 Hint A helpful reminder of what the password is THIS IS NOT A TOTAL SECURITY FEATURE The security feature offers a way to password protect access to diagnostics and configuration on the network The security feature does n...

Page 68: ...y can have a separate security level associated with it for each user Security Levels 1 Full Access Capability to view and configure a web page 2 View Access Capability to view a web page but cannot configure parameters 3 No Access No capability of viewing the web page and page will be removed from Navigation ...

Page 69: ...sword This is used to reset security settings Confirm reset password must be selected to confirm this action Once confirmed there is a 15 minute window to do a hard reset of the gateway by physically removing and restoring power from the gateway Once power is restored you may navigate to the IP address of the gateway as normal Security Log Out Once a user is done with a session they may click logo...

Page 70: ...o use 2 SMTP Mail Password If authentication is required enter the SMTP Server s password Optional 3 SMTP Server Enter the Name of the SMTP Server or the IP Address of the Server 4 From E mail Enter the e mail that will show up as the sender 5 To E mail Enter the e mail that is to receive the e mail 6 E mail Group Choose a group for the user This is used in other web pages Click the Save Parameter...

Page 71: ...ection a Top dropdown select the Data Group This dropdown menu will contain all groups that go from the gateway to the network b Lower dropdown select the Data Point s Specific Point This is used to select which point in the group will be monitored for alarms 4 In the Set Error Section a Select the Set Error Operation in the top dropdown menu Available options are and Change of State COS This is t...

Page 72: ...the Clear Error Value Ex Ticks Since Powerup 5000 This will clear the alarm after 5000 ticks have elapsed since the unit powered up 6 Enter an Alarm Name This will make the alarm unique and will be available in the Alarm Status page as well as in the email generated by the alarm 7 Select an email to associate this alarm with When an alarm is set it sends an email When an alarm is cleared it will a...

Page 73: ...rm 7 Status The current status of the alarm either OK or ALARM 8 of Times Active This count represents the number of times this alarm has become active If an alarm is triggered this count will increment Alarms Active While one or more alarms are active every page will display Alarms Active at the top of the page This will no longer be displayed if all active alarms have been cleared When an alarm ...

Page 74: ...When an alarm is cleared the following will occur 1 A one time notification will be sent to the email associated with the alarm a For duplicate emails to occur the alarm must become active and then be cleared again 2 Total Alarms Active will decrement Last Active Alarm will not be changed 3 Status of the Individual Alarm will be reset to OK ...

Page 75: ...This is to be used to prevent jitter Default value is 0ms This timer takes priority over the Stale Data Timer There is a separate timer per data mapping This timer is active only after the first write goes out and the first COS event occurs 3 Writes Before Reads If multiple writes are queued execute of Writes Before Reads before the next read occurs Default is 10 and should fit most applications W...

Page 76: ...Alarm that was active Common Errors 1 Destination or Source Point does not exist a Solution Re map the mapping 2 Source or Destination Pointer too small a There is not enough space on either the Source or the Destination for the data you want to copy This is typically seen when the Destination is smaller than the amount of data being transferred to it 3 Range Discard Min or Max Value a The actual ...

Page 77: ...urn all values displayed to 0 2 If Viewing PROFIBUS Slave this will only clear the values for the PROFIBUS Slave section of the gateway Device Status 1 Connected The gateway is connected to the PROFIBUS controller 2 Error Timeout a The Profibus controller has lost a connection to the gateway b The Profibus cable is not plugged in 3 Not Connected a Profibus adapter board is missing jumper b Slave a...

Page 78: ...ost a connection to the gateway b The Profibus cable is not plugged in Aux LED Status near green serial connector 1 Green ON when serial data is being transmitted by the gateway 2 Yellow ON when serial data is being received by the gateway Aux LED Status near DE9 Profibus connector 1 Green a Solid Green During Data Exchange b Flashing Green During Profibus Parameterization 2 Yellow Not used Variab...

Page 79: ...c information can be found by clicking the Help button NOTE This page will auto refresh every five seconds with the latest data Clear All Values This will only affect displayed values 1 This will reset all displayed values back to zero and clear the Status Strings Example If viewing ASCII Port this will only clear the values for Port This will reduce the All ASCII values indirectly Clear Buffers T...

Page 80: ...configured b Verify the port configured matches the port enabled LED Status This is the Status for All ASCII or the specific ASCII device selected 1 Solid Green Connected The gateway is receiving transmitting data within the inactivity period for all the ASCII devices that are configured and enabled 2 Flashing Green Not Connected First Time Scan Start up state No messages have been received or tra...

Page 81: ... Msg Timeout to be less than what you currently have set 7 Successful Parsed Messages a Number of messages that are complete and have been successfully parsed 8 Failed Parsed Messages a Number of messages that are complete but have not been parsed successfully Status Strings These are the values for All ASCII or the ASCII device selected 1 Queued Messages a The gateway will hold up to 20 configura...

Page 82: ...mplete message the gateway received from the ASCII device processed and sent to the other protocol Next Message to Send from Queue 2 This is the next complete message that the gateway has already received and processed from the ASCII device and will be sent next to the other protocol Current Message being Received from ASCII 1 The current data that the gateway is receiving Data needs to hit one of...

Page 83: ... ASCII device Note The concatenated delimiters are not displayed in this message but will be transmitted with the message Send Data from Gateway to ASCII Used for testing only Character limit of 1024 1 Enter a message to send to your ASCII device 2 Can be used to test communication and test formatting of messages ...

Page 84: ...ocol is a master client you may set the LED to represent either all slaves servers configured in the gateway or a slave server device To select a slave server device 1 Select the protocol in the left dropdown menu 2 Click Save Parameters to generate the second dropdown menu 3 Select the individual slave server in the right dropdown menu Click the Save Parameters button to commit the changes and re...

Page 85: ...ther device into the 460 gateway whenever it is in Configuration Mode Upon clicking the Choose File button you will be prompted to select a location from which to load the saved file Once the location is selected you can choose the Import Network Settings checkbox if you want to load the network settings of the configuration file or just load the configuration without the network setting If you ch...

Page 86: ...ntered an error while trying to load the saved configuration the gateway will indicate the first error it found and a brief description about it under the Load Configuration button Contact RTA Support with a screenshot of this error to further troubleshoot ...

Page 87: ...ay you wish to copy the configuration from 2 Power up the gateway you wish to copy the configuration to DO NOT INSERT SD CARD YET 3 Navigate to the webpage inside the unit 4 Navigate to the dropdown Other Utilities 5 If you are not currently in Mode Configuration go into Configuration Mode by clicking the Configuration Mode button at the top left hand side of the screen 6 Press the Revert to Manuf...

Page 88: ...stored in the Flash File System within the gateway Identify your device by clicking the Start Flashing LEDs button By clicking this button the two diagnostic LEDs will flash red and green Once you have identified which device you are working with click the button again to put the LEDs back into running mode Configure the size of the log through the Log Configuration Bring the device back to its la...

Reviews: