Real Time Automation, Inc.
22
1-800-249-1612
3)
Select a data format for each data group. Options include: 8 Bit Int/Unit, 16 Bit Int/Uint, 32 Bit
Int/Uint, 64 Bit Int/Uint, 32/64 Bit Float, Binary 8/16/32 Bit Pack.
NOTE:
The connection parameters table will update to match the values entered in the data
groups after
Save Parameters
is pressed.
Example: Use the instances and sizes next to the I/O Type for information to connect to an EtherNet/IP
scanner/client.
•
Input Instance
or
destination for target to originator (T2O) as 100.
•
Output Instance
or destination for originator to target (O2T) as 112.
•
Configuration
Connection Instance
is always 1.
•
Data
Input Size
for target to originator as 32 bytes.
•
Data
Output Size
for Originator to Target as 32 bytes.
•
We do not make use of passing configuration data;
Config Size
is always 0.