PEARL Owner's Manual
20
RSF Woodburning Fireplaces
The stainless steel liner should be fitted inside the clay liner all the way to the top of the masonry chimney. It is
not meant to replace the clay liner. You can use either the EXCEL liner or any other listed liner to ULC-S635,
ULC-S640 or UL-1777.
Special care is to be taken to make sure that you have a good solid connection between the EXCEL chimney and
the liner. A masonry adaptor (FO-FDM7) was designed specifically for that purpose and is available from your
RSF dealer. It will attach to the liner with 3 stainless steel rivets (provided) and to the EXCEL chimney with 3
screws (provided).
After mortaring in place, the connection between the EXCEL chimney and the liner should not be visible in order
to isolate the heat released through the liner from the fireplace enclosure.
As depicted in Figure 15, you must install at least one 18" length of EXCEL chimney after the EXCEL chimney
elbow. The uppermost part of the EXCEL chimney - where it enters the masonry chimney - must be a minimum of
12" from the ceiling.
NOTE:
If the ceiling is high enough, you can install one or more EXCEL chimney lengths directly on the
fireplace before the elbow.
If you use a flexible liner, make sure to be careful when cleaning to ensure that the stainless steel flexible liner is
not dislodged in any way.
Using an Existing Masonry Chimney
WARNING: IF YOU ARE CONSIDERING USING AN EXISTING CHIMNEY, IT MUST FIRST BE
THOROUGHLY INSPECTED BY AN AUTHORITY HAVING JURISDICTION TO DETERMINE THE
FOLLOWING:
1. The masonry chimney is well constructed and fully lined, in accordance with Local Building Codes and the
National Building Code of Canada (NBC) or National Fire Protection Association chimney standard (NFPA
211).
2. It has been thoroughly cleaned of any soot or creosote residue and inspected to determine that it is in good
working condition.
3. There is no insulation of any type in contact with the masonry chimney and there is no insulation stuffed
anywhere in the chimney.
4. All the necessary clearances around the masonry chimney, along the complete run of the chimney, are
respected as per NBC or NFPA 211. If the masonry chimney is enclosed in drywall, openings will probably be
required in order to verify clearances at all points.
5. The masonry chimney will only be used for the fireplace and no other appliance.
If major repairs are required to meet the above conditions, a new chimney should be constructed.
To make the hole through the
masonry chimney and make the
connection to the fireplace, we
recommend that you follow these
steps:
1. Sight-in and mark the outline of
where the EXCEL chimney will
penetrate the masonry chimney.
2. Using a large (¾" - 2") masonry
drill bit, drill a hole exactly in the
center of the oval outline. With a
masonry hammer and drill, slowly
enlarge the hole to the size
required. Remember to work from
the center out. Be especially
careful with the clay liner behind
the brick because three sides of it
must stay in place.
3. Bring the stainless steel liner
Figure 15 Connection to a Masonry Chimney
Mortar
Mortar
Clearances as per
NBC or NFPA 211
EXCEL liner or other listed liner to
ULC-S635, ULC-S640 or UL-1777
12" min. to
combustible ceiling
EXCEL chimney
lenght: 18" min.
EXCEL chimney
elbow
Masonry Adaptor
FO-FDM7
Metal
Firestop
Liner
Elbow
RSF
Fir
ep