background image

Cable used to wire between the sensor and the time
switch/controller, must be double insulated. The time
switch/controller must be isolated from the supply when making
connections to the sensor terminals.  All screw terminals must be
protected against accidental contact or damage.  Conductors
wired to them must be properly prepared in order to maintain the
finger and back of hand protection (VDE 0106).
The load applied to the output relay contacts must not exceed the
ratings shown in the technical specification.

Settings

To access all the control buttons, lift the front cover.  The six buttons, 3-
position switch and daylight level control potentiometer are shown in
figure 3.

Initial switch on

The time switch must be installed and wired in accordance with the
instructions detailed above.  On applying power to the unit, the LCD
display wil take about thirty seconds to become visible.

Erase all settings

This procedure is best followed when the time switch/daylight sensor is
first installed.
1. Press the S and OK buttons simultaneously.
2. Release the buttons.  The memories have now been erased and the

time switch is ready to accept new settings.

Setting the actual time

1. Press the 

button once.  The clock indicator will be displayed

above the numeric time display.

2. Press the S* button until the correct hour (0-23) is showing.
3. Press the OK button once.  The minute display will flash.
4. Press the S* button until the correct minutes (00-59) are showing.
5. Press the OK button once.  The day indicator will flash above day 1.
6. Press the S* button until the day indicator appears steady above the

actual day (1-7).

7. Press the 

button when the set time coincides with the actual time.

This starts the clock.
*Note: Pressing and holding in the button will cause the setting to

be advanced rapidly. This can be done until the required
setting is near. Thereafter, short duration pulses will advance
the setting more slowly until the required setting is reached.

Setting switching programmes

To assist in programming, the programme has two block settings, days
1 to 7 and days 1 to 5. Using block programmes saves time in entering
them.  It does not save programme memory. The switching commands
may also be assigned to the individual applicable days.

Choosing block or individual day programming

Repeated pressing of the 

button displays the following items:

1. Clock set.
2. Completed programmes (not applicable if clearing memory

procedure has been followed).

3. Programme by 7-day block picture, identified by day indicators

above and below all days 1 to 7.

4. Programme by 5-day block picture, identified by day indicators

above and below all days 1 to 5.

5. Programme by individual day picture, identified by no day indicators

showing.

6. Normal running.
Continuing to press the 

button displays the items again.

Individual day programming

To commence individual day programming, scroll through the items,
listed above, until the programme by individual day picture is displayed:
1. Press the S button once.  The on time hour display will flash.

Continue to press the S button to set the required on time hour (0-
23).

2. Press the OK button once.  The on time minute display will flash.

Press the S button to set the required on time minutes (00-59).

3. Press the OK button once.  The on day indicator will flash above day

1.  Now is decision time:

4. Is the on time applicable to this day?

Yes: If yes, press the OK button once and the S button once (except

when day 7 is reached).  Another on day indicator will flash
above the next day.  Proceed again from point 4.

No: If no, press the S button once (except when day 7 is reached).

An on day indicator will flash above the next day.

Proceed again from point 4 until day 7.
If the above procedure is continued beyond day 7, all entries will
cancel and will require re-entering.
5. Press the

button. The off time hour display will flash.

6. Use the S button to set  the required off time hour (0-23).
7. Press the OK button. The off time minutes display will flash.
8. Use the S button to set the required off time minutes (00-59).
9. Press the OK button. The off day indicator will flash below day 1.

Now is decision time again:

10.Is the off time applicable to this day?

Yes: If yes, press the OK button once and the S button once (except

when day 7 is reached). Another off day indicator will flash below
the next day. Proceed again from point 10).

No: If no, press the S button once (except when day 7 is reached).

An off day indicator will flash below the next day.

Proceed again from point 10 until day 7.
If the above procedure is continued beyond day 7, all entries will
cancel and will require re-entering.
11. Press the 

button. The programmed picture will be entered into

the memory and the display will return to the normal running mode.

12. If further programmes are required, proceed from the beginning of

individual day programming. Unused programming pictures will be
presented in the three programming choices:
7-day block, 5-day block, individual day.

When all eight programming pictures have been used, the display will
read full after scrolling through all the entered programmes.

Block programming

The procedure for programming by 7-day and 5-day blocks is similar to
individual day programming.  The only difference is that on/off day entry
is automatically entered.

Programme review/cancel

1. Press the 

button to review programme pictures.

2. When a picture required to be changed or deleted is displayed,

press the C button.  The programme picture will clear, permitting re-
programming.

3. After cancelling all the unwanted switching point commands, press

the 

button to return to the normal running mode.

Override facilites

Manual on/off override

This facility permits the changing of the output relay state, contrary to
the programmed position, until the next opposite command.

Example:

The time switch is programmed as follows:
on at 08:00...............off at 12:00
on at 13:00...............off at 17:00

At 10:00 the manual off override is used.  The time switch will remain
off until 13:00, the next opposite (on) command.
The programme will continue as normal thereafter.  To effect manual
override, press the + button.  Repeated pressing of this button will
cause the output relay to alternate between on and off.

V9376

2

Summary of Contents for 328-336

Page 1: ...t sensor combination are All controls easily accessed including the setting of the daylight switching levels Single pair low voltage wiring between the sensor and the time switch controller Installation The time switch controller may be snap fitted on symmetrical DIN mounting rail to BS 5584 1978 EN 50 002 DIN 46227 3 or housed in a suitable enclosure Modular enclosures permitting access to the fr...

Page 2: ... on time hour display will flash Continue to press the S button to set the required on time hour 0 23 2 Press the OK button once The on time minute display will flash Press the S button to set the required on time minutes 00 59 3 Press the OK button once The on day indicator will flash above day 1 Now is decision time 4 Is the on time applicable to this day Yes If yes press the OK button once and ...

Page 3: ...assing clouds car headlights etc Technical specification Supply voltage nominal ________________________220 240V min max limits ____________________________188 264V Power consumption __________________________________2 5VA Contact ratings type resistive cos j 1 ________________________________10A inductive cos j 0 6 ________________________________6A type ________________________________________S ...

Page 4: ...gen gelöscht wurden 3 7 Tage Block zu erkennen an den Markierungsbalken über und unter allen Wochentagen 1 7 4 5 Tage Block zu erkennen an den Markierungsbalken über und unter den Wochentagen 1 5 5 Einzeltagprogramm daran zu erkennen daß keine Tage markiert sind 6 Normaler Betrieb Wenn Sie die Taste weiter drücken werden die obigen Posten erneut durchlaufen Einzeltagprogrammierung Um Einzeltagprog...

Page 5: ...age lang 1 Drücken Sie einmal die S Taste während sich der Zeitschalter im normalen Betriebsmodus befindet Hierauf erscheint ein F Zeichen gefolgt von einer blinkenden Ziffer 1 2 Drücken Sie die S Taste bis die Anzahl der Tage ausschließlich des aktuellen Tages erscheint für die das Sonn und Feiertagsprogramm gelten soll 3 Drücken Sie einmal die OK Taste Das Programm startet um 0 00 am folgenden T...

Page 6: ...namente per mantenere la protezione delle dita e del dorso della mano VDE 0106 Il carico applicato ai contatti dei relè di uscita non deve superare i valori nominali indicati nelle specifiche tecniche Regolazioni Per accedere ai pulsanti di comando sollevare il coperchio anteriore I sei pulsanti l interruttore a 3 posizioni ed il potenziometro di controllo della luce diurna sono riportati in figur...

Page 7: ... comandi non richiesti dei punti di commutazione premere il pulsante per tornare alla modalità funzionamento normale Funzioni di esclusione Esclusione manuale inserimento disinserimento Questa funzione permette di cambiare lo stato di uscita del relè contrariamente alla posizione programmata fino al comando opposto successivo Esempio L interruttore a tempo è programmato come segue inserito alle or...

Page 8: ...uta a disinserito con livelli di luce superiori al livello impostato Il ritardo ha lo scopo di evitare commutazioni indesiderate dovute per esempio al passaggio di nuvole fari di autoveicoli ecc Specifiche tecniche Tensione di alimentazione nominale ____________________________________220 240 V limiti min max ____________________________188 264 V Consumo __________________________________________2...