background image

The two slots in the rear of the base of the firebox may be used to secure the appliance in position. Where no spacer is
used the unit will require securing at the top using the two holes in the top corner plate and the No 10 c/sk screws
provided. This is needed to effect a seal with the flue.

Vent Box Installed with Spacer frame

a. 6 holes are provided in the rear of the spacer frame with access through the front of the frame. Only 4 fixing positions
are required, 1 at the bottom of each leg and 2 others in either of the top of the left or right hand legs.

b. Holes in the side of the spacer frame for self tap screws for side fixing - 4 holes in the front flange for 16in openings
and 4 holes in the rear for 18in openings.

Installing the Appliance in Position

With the gas supply pipe laid to the position required the surround should be fitted and sealed to the chimney correctly,
this is to prevent any seepage of flue products or to prevent any ingress of air into the flue from anywhere other than the
flue outlet of the fire.  A decision would have been made earlier as to whether or not the spacer will be required. The
easier method of installation is through the 6 holes provided in the spacer frame or through the four holes in the front face
of the vent box - both methods will require drilling into the back panel of the surround.  See fig 5.  Where it is undesirable
to deface or damage the back panel, 4 fixing straps are provided which can be fastened to the inner walls of the opening
and the inner flanges. See fig 5.

If a spacer frame is not used an alternative method is to screw through the 2 slots provided in the base or rough the two
holes in the rear panel, using the countersunk woodscrews provided. In addition it may be necessary to use the top two
fixing holes in the corners of the vent box. An additional length of sealing strip is included in the fixing kit to allow an
extra thickness to be added where it is necessary to effect a seal on uneven surfaces. Remove the backing strip covering
the adhesive surface of the strip and position onto the rear of the firebox or the spacer frame where applicable.

Before offering the vent box into the opening, the hearth should be protected from damage or scratches that may occur
during installation.

Locate and secure the vent box by the method chosen ensuring that a good seal exists with the back panel. Lay a gas
supply to the location of the burner connecting elbow and place the burner into the vent box locating the feet of the rear
legs into the two tags in the base. Secure the position with the 2 x No. 8 self tap screws supplied and complete the gas
connection.

Fit the brass trim in position with the magnets provided and remove the plastic coating from the brass.

Note: The complete installation should be tested for gas soundness.

Laying the Coal Bed

The coal support shelf is positioned on the fibre support metalwork; two stops prevent the shelf sitting on the burner outlet.
Place the simulated coal front in the position shown in Fig.6. The one-piece support shelf is constructed to allow three levels
of coal support; these three levels are shown in Fig 6, the plan view of the bed.

Coal Layout (See Figs 6 - 9)

First Layer.  Position 3 large coals and 6 small coals between the front simulated coal and the lower level of the coal support
shelf. Ensure the gap indicated is left clear to view the pilot flame.

Place 3 large coals on the middle level of the coal support shelf as shown.

Second Layer. Place 4 small coals in position to fill gaps between the coals on the lower and middle level of the coal support
shelf

Place 2 small coals in position to straddle the 3 large coals on the middle level and upper level of the coal support shelf..

To obtain the best visual appearance it may be necessary to make slight adjustments to the positions of the coals.
NOTE:  If any of the coals or coal bed become damaged, lost or broken, genuine manufacturer’s replacement parts must be
obtained before the appliance is used.

Page 7

Summary of Contents for Gas Fire

Page 1: ...SS 2 FLAME SYSTEM 3 USERS Pages 2 3 INSTALLATION Pages 4 9 AND SERVICING INSTRUCTIONS THIS CAT I2H APPLIANCE IS FOR USE ON NATURAL GAS G20 AT A SUPPLY PRESSURE OF 20 mbar IN GB and IE HAND THESE INSTRUCTIONS TO THE USER ...

Page 2: ...er the firebox must have a minimum non combustible thickness of 25mm The appliance is fitted with an ODS a spillage monitoring system which operates if the evacuation of products is interrupted i e blocked or incorrect flueing If the gas fire repeatedly goes out it may indicate a problem and the installer or specialist should be informed before further use Areas of this appliance will become hot a...

Page 3: ...leaned off using a non fluffy cloth Laying the Coal Bed The coal support shelf is positioned on the fibre support metalwork ensure that the shelf sits against the two stops which are to prevent the shelf sitting on the burner outlet Place the simulated coal front in position as shown in Fig 6 three tabs are provided to locate The one piece coal support shelf is constructed to allow three levels of...

Page 4: ... 6461 Pt 1 1984 BS 715 1993 BS 1289 Pt 1 1986 BS 7566 Pts 1 4 1992 Technical Data Overall height of fire with spacer 612mm Overall height of fire without spacer 605mm Minimum height of opening required 540mm Maximum height of opening with spacer 590mm Maximum width of opening required 405mm Maximum width of opening with spacer 470mm Forward projection from opening 60mm without front and fret Forwa...

Page 5: ... must not restrict the above listed flues The flue must only service a single appliance and not have any branches or traps that may impede the natural draught Any flue damper plate or restrictor shall be removed or fixed in the fully opened position The front and base of the fire opening must be flat and square to ensure a good seal with the appliance this is to ensure that there is no reduction i...

Page 6: ...he requirements of BS 6891 1988 dealing with enclosed pipes The Standard requires that when a gas pipe is fed through a wall the pipe should be enclosed in a tight sleeve to protect against failure caused by movement It shall be constructed to prevent passage of gas either between the pipe and sleeve or sleeve and wall Where a gas supply pipe enters the box in any of the positions stated the hole ...

Page 7: ...extra thickness to be added where it is necessary to effect a seal on uneven surfaces Remove the backing strip covering the adhesive surface of the strip and position onto the rear of the firebox or the spacer frame where applicable Before offering the vent box into the opening the hearth should be protected from damage or scratches that may occur during installation Locate and secure the vent box...

Page 8: ...fan is situated in the room this test should be repeated with the fan running If there is a connected room with an extractor fan the test should be repeated with all the doors to that room opened and the extractor fan running All smoke must be drawn into the flue If spillage occurs allow a further 10 minutes Should spillage still occur examine the chimney for the fault and rectify Check for satisf...

Page 9: ...xing flange When refitting observe that the two feet at the rear of the assembly locate under the two lugs formed in the base of the box assembly i TO CLEAN OR REPLACE THE INJECTOR Unscrew the compression nut connecting the gas supply to the elbow injector while supporting the injector to prevent distortion of the framework Unscrew and remove the gas supply tube from the gas control valve hold the...

Page 10: ...Page 10 ...

Page 11: ...he surround with the sapcer fitted to satisfy the debris collection requirement Depth B is Nominally 70mm If no chairbrick is fitted the minimum distance required between the rear of the opening and the front face of the surround is 210mm without spacer frame fitted Page 11 ...

Page 12: ...Page 12 ...

Page 13: ...Page 13 ...

Page 14: ...Page 14 ...

Page 15: ...Page 15 ...

Page 16: ...Page 16 ...

Page 17: ...Page 17 ...

Reviews: