To check the gas pressure at the appliance, allow the coals and the coal bed to cool and turn off the gas supply
at the isolating cock. Remove the hexagon headed screw and connect a manometer to the pressure test point,
turn on the gas and ignite the fire, allow to heat up and check that the gas pressure is 37 mbar +/- 1 mbar - any
appreciable drop may indicate restrictions through the pipework up to the fire. The pressure test point may
also be used to check for leakage of the joints to the appliance. Allow the coal bed to cool before replacing
the screw.
Spillage Check
Light the appliance and set to the large flame position, locate the front and fret in position and leave to warm
up for 5 minutes. Check for satisfactory clearance of combustion products by positioning a lighted smoke
match 20mm down from edge of canopy, 80mm from either side and 45mm back from the front edge. All the
smoke must be drawn into the flue see Fig 8A. If spillage occurs, allow a further 10 minutes. Should spillage
still occur, disconnect the appliance and examine the chimney for the fault and rectify. If an extractor fan is
situated in the room, the test should be repeated with the fan running. If there is a connected room, the test
should be repeated with all the doors in that room opened.
Demonstrate the lighting and extinguishing procedures to the user.
Advise that:
The curing effect of heating the coals will cause an initial odour which, although not harmful, may require
additional ventilation until the odour has disappeared.
Any debris or soot is cleaned from the appliance. Advise the customer that they should read their Users
Instructions before operating the fire and always follow the advice in the section headed ‘Removal of
Debris or Soot Deposits’. The appliance must be serviced annually by a competent person in accordance with
these instructions; at this time the appliance should be re-checked for spillage in accordance with the method
detailed in these instructions.
If the appliance is turned ‘off’ or shuts off automatically, wait for at least 3 minutes before attempting to
relight.
The appliance is fitted with an Oxy-pilot to prevent the continued operation in the event of spillage occurring.
If the fire shuts `OFF' repeatedly the appliance must be turned off and not used until an expert is consulted.
Complete the registration section at the end of this booklet. Advise that any component part of this appliance
be guaranteed against defective workmanship or faulty materials for a period of twelve months from the date
of purchase.
Any such part will be replaced free of charge on receipt of the purchasers address at the cost of postage only,
provided that:
a.
It is accompanied by the registration section cut out of the booklet, together with the original purchase
receipt, which will be returned with the replacement part.
b.
A competent person has carried out any installation, repairs or adjustments, such as the supplier’s
representative or a CORGI registered installer.