To check the gas pressure at the appliance, allow the coals and the coal bed to cool and turn off the gas supply
at the isolating cock.  Remove the hexagon headed screw and connect a manometer to the pressure test point,
turn on the gas and ignite the fire, allow to heat up and check that the gas pressure is 37 mbar +/- 1 mbar - any
appreciable drop may indicate restrictions through the pipework up to the fire. The pressure test point may
also be used to check for leakage of the joints to the appliance.  Allow the coal bed to cool before replacing
the screw.

Spillage Check

Light the appliance and set to the large flame position, locate the front and fret in position and leave to warm
up for 5 minutes.  Check for satisfactory clearance of combustion products by positioning a lighted smoke
match 20mm down from edge of canopy, 80mm from either side and 45mm back from the front edge. All the
smoke must be drawn into the flue see Fig 8A.  If spillage occurs, allow a further 10 minutes. Should spillage
still occur, disconnect the appliance and examine the chimney for the fault and rectify.   If an extractor fan is
situated in the room, the test should be repeated with the fan running.  If there is a connected room, the test
should be repeated with all the doors in that room opened.

Demonstrate the lighting and extinguishing procedures to the user.

Advise that:

The curing effect of heating the coals will cause an initial odour which, although not harmful, may require
additional ventilation until the odour has disappeared.

Any debris or soot is cleaned from the appliance. Advise the customer that they should read their Users
Instructions before operating the fire and always follow the advice in the section headed ‘Removal of
Debris or Soot Deposits’. The appliance must be serviced annually by a competent person in accordance with
these instructions; at this time the appliance should be re-checked for spillage in accordance with the method
detailed in these instructions.

If the appliance is turned ‘off’ or shuts off automatically, wait for at least 3 minutes before attempting to
relight.

The appliance is fitted with an Oxy-pilot to prevent the continued operation in the event of spillage occurring.
If the fire shuts `OFF' repeatedly the appliance must be turned off and not used until an expert is consulted.

Complete the registration section at the end of this booklet. Advise that any component part of this appliance
be guaranteed against defective workmanship or faulty materials for a period of twelve months from the date
of purchase.

Any such part will be replaced free of charge on receipt of the purchasers address at the cost of postage only,
provided that:

a.

It is accompanied by the registration section cut out of the booklet, together with the original purchase

receipt, which will be returned with the replacement part.

b.

A competent person has carried out any installation, repairs or adjustments, such as the supplier’s

representative or a CORGI registered installer.

Page 7

Summary of Contents for G31

Page 1: ...0102 095 50261 6 0 1 67 1 5 USERS INSTRUCTIONS THIS CAT I3P APPLIANCE IS FOR USE ON PROPANE GAS G31 AT A SUPPLY PRESSURE OF 37 mbar IN GB IE HAND THESE INSTRUCTIONS TO THE USER DESCRIPTION ...

Page 2: ...petent person in accordance with the Gas Safety installation Use Regulations 1994 as amended or the rules in force and in accordance with the Manufacturers Installation Instructions Failure to comply could lead to prosecution The chimney or flue unless new must be swept before installation It is recommended that the appliance be serviced annually by a competent person and that the flue is checked ...

Page 3: ...t flame remains lit Refer to Fig 2 to view pilot Note For convenience the unit can be operated with the pilot only i e with the control knob set in the IGN position Push in the gas control slightly and turn anti clockwise so that the indicator dot is at the required setting Replace the fret controls cover To turn off the appliance and pilot turn the gas control clockwise from any position until th...

Page 4: ... 5 small round coals between the gaps formed in the coals laid in 1 2 above Fig 4 Cleaning the Front of the Appliance The fire must be turned off and allowed to cool The paintwork should be cleaned with a soft cloth or soapy water the brass trim has a clear lacquer coating to preserve the polished finish Spares and Service For spares and service contact your local supplier installer or direct to t...

Page 5: ...Page 4 Page 5 ...

Page 6: ...ddress __________________________________________________ __________________________________________________ Date of Purchase__________________________________________________ Serial Number __________________________________________________ Please return this section with any components that are faulty under guarantee MAXIMUM HEAT INPUT 6 kW 20470 Btu h Gross Royal Cozyfires are manufactured by CR...

Page 7: ...0102 095 50251 6 0 1 67 1 5 INSTALLATION and SERVICING INSTRUCTIONS THIS CAT I3P APPLIANCE IS FOR USE ON PROPANE GAS G31 AT A SUPPLY PRESSURE OF 37 mbar IN GB IE HAND THESE INSTRUCTIONS TO THE USER ...

Page 8: ...an Oxy pilot sensor O D S that will cause the appliance to shut off in the event of continued spillage occurring under hazardous or blocked flue conditions The fire bed consists of ceramic fibre components and coals all of that are removable for cleaning purposes when required It is important when relaying the coal bed and coals to follow the instructions correctly This appliance is suitable for i...

Page 9: ...a minimum open area in the fret of 20 sq cms and 60 sq cms in the front Care should be taken to prevent any damage being caused to surrounding soft furnishings or decor e g many embossed vinyl wall coverings may become discoloured if located too close to the appliance Clearances required for combustible shelves are shown in fig 1 Care should be taken to ensure that when the appliance is installed ...

Page 10: ... incorrect flue terminals must not restrict any of the above flues The flue must only service a single appliance and not have any branches or traps that may impede the natural draught Any flue damper plate or restrictors shall be removed or fixed in the fully opened positions The front and base of the fire opening must be flat and square to ensure a good seal with the appliance this is to ensure t...

Page 11: ...d tube such as bundy suitable pieces of bundy are included in the fitting kit to assist the installer Where a concealed gas supply is used the installer is reminded of the requirements of BS 6891 1988 dealing with enclosed pipes The Standard requires that when a gas pipe is fed through a wall the pipe should be enclosed in a tight sleeve to protect against failure caused by movement and shall be c...

Page 12: ...coating from the brass finish Laying the Coal Bed Fit the coal support shelf ensuring that the front edge sits behind the three tabs and the simulated coal front Fig 10 Referring to figures 10 11 12 and 13 lay the coals as follows 1 Place 4 large round coals between the simulated coal front and the support shelf Fig 12 2 Place 3 round coals between the gaps in the front row Fig 12 3 Place the 5 sm...

Page 13: ...s will cause an initial odour which although not harmful may require additional ventilation until the odour has disappeared Any debris or soot is cleaned from the appliance Advise the customer that they should read their Users Instructions before operating the fire and always follow the advice in the section headed Removal of Debris or Soot Deposits The appliance must be serviced annually by a com...

Page 14: ... below the burner assembly it has to be removed from the vent box case by disconnecting the gas supply at the inlet elbow and unscrewing the two screws on the sides of the facia panel Where the supply is fed from the right hand side across the front of the fire it will be necessary to disconnect the supply from the isolation tap elbow i TO CLEAN OR REPLACE THE INJECTOR Remove the aeration sleeve r...

Page 15: ...Page 9 ...

Page 16: ...Page 10 ...

Page 17: ...Page 11 ...

Page 18: ......

Page 19: ...Page 12 ...

Page 20: ...Page 13 ...

Page 21: ...Page 14 No Figures 13 15 On this page ...

Page 22: ...omponents that fail under guarantee Maximum Heat Input 6 kW 20470 Btu h Gross Royal Cozyfires are manufactured by CROSSLEE plc Aber Park Industrial Estate Aber Road Flint Flintshire CH6 5EX Spares Tel 01422 203963 Fax 01422 204475 Service GSA Ltd 01703 516611 Customer Service 01422 200660 Fax 01422 206304 Technical Help Line 0906 8633268 Calls charged at 50p per minute ...

Reviews: