The following points should also be observed: 
 

  Close the parasitic circuit  

  Connect all devices to the potential equalizing cable as often as possible. Electrical 

conductors such as machine elements, metal tubes or supporting constructions should 
be integrated into the system. 

  Protect the potential-equalization cable and connections against corrosion.  

  Select the cross-section of the potential equalization cable according to the maximum 

equalization current.  

 
If these different measures do not correct the problem, a galvanic separation according to 
ISO 9549 may have to be installed. You may also want to consider the use of fiber-optic cables. 

15. Document 

releases 

 
Doc. Release 

Date 

Notes 

-10 

Jan. 16, 2007 

Original release 

 

Hardware and firmware: 

 
Firmware Version 

Date 

PCB Number 

1.0a 

Apr. 26, 2006 

Model DI-3: 66.0860.0015 
Model DI-4: 66.0862.0015 

 
 
 

Summary of Contents for HygroClip DI tal interface

Page 1: ...rf Switzerland Document code Unit Instruction Manual Document Type HygroClip DI digital interface instruction manual Document title Page 1 of 24 2007 Rotronic AG IN E HyClip DI V1_10 doc HygroClip DI...

Page 2: ...9 Ethernet local area network 18 10 RS 485 multi drop network 18 11 Specifications 20 12 Accessories 21 13 Communications protocol 21 14 Electrical Installation Guidelines 22 15 Document releases 24...

Page 3: ...r than the capacity of the PC there is no limit to the number of HygroClip DI that can be networked with the PC The main functions of the HW4 software include on line data monitoring and recording by...

Page 4: ...ted 12 VDC 100 240 VAC adapter 170 mA 4 Probes The HygroClip DI is designed for use with the ROTRONIC HygroClip digital humidity temperature probes These are highly accurate probes which are adjusted...

Page 5: ...in air max 85 C 185 F wire mesh filter HygroClip SP05 measurement in air ducts max 85 C 185 F HygroClip SC05 measurement in tight spaces max 100 C 212 F HygroClip HP28 insertion probe measurement of...

Page 6: ...le model AC1616 is not compatible with the HygroClip DI HygroClip IC 1 100mm IC 3 250mm for through wall installation max 200 C 392 F wire mesh filter HygroClip IM 1 120mm IM 3 270mm for through wall...

Page 7: ...Note use pins 3 and 4 to power multi dropped instruments with a single external 12 VDC power supply with adequate mA rating Pin 4 and the 12VDC receptacle normally used for the AC adapter are not conn...

Page 8: ...security When new software is being installed the NET framework also eliminates the potential problem of conflicting dynamic library files DLL According to Microsoft the NET framework will be used by...

Page 9: ...e manager menu bar is located at the top of the form File Open opens the device configuration directory specified in the HW4 Settings Form File Locations Tab and displays all available device configur...

Page 10: ...mation As far as possible use a unique device name RS485 address click on the underlined link to change the instrument address to be used in conjunction with an RS 485 network multi drop Each network...

Page 11: ...orm to globally change the unit system used by the instrument If the unit system offers several choices such as In Hg or PSI for pressure choose a unit by left clicking on the arrow to the right of ea...

Page 12: ...Input Name use a maximum of 12 characters Calculation Each probe input of the HygroClip DI can be set to compute one of the following psychrometric parameters Dew point Dp Frost point Fp Wet bulb tem...

Page 13: ...Alarm alarm conditions can be defined for humidity temperature and the calculated parameter Values that are below the low alarm value or above the high alarm value will trigger an alarm A value can b...

Page 14: ...ctronic signatures HW4 is designed to keep track of configuration changes and of any probe adjustment HW4 also keeps track of user events main operations performed by each user and self events softwar...

Page 15: ...al interface instruction manual Document title Page 15 of 24 2007 Rotronic AG IN E HyClip DI V1_10 doc To protect the device click on the underlined link HW4 opens the following form where a password...

Page 16: ...the underlined link HW4 opens the password form Enter the password and click on the OK button HW4 confirms that the device is now unprotected FORGOT THE PASSWORD should you forget the password used t...

Page 17: ...M33 transmitters HygroClip Alarm programmable alarm card HygroClip DI interface HygroStat MB Thermo Hygrostat IMPORTANT All devices connected to a RS 485 multi drop network master and slaves must use...

Page 18: ...0 TCP Port 2101 MAC Address 00 40 9D 28 2D 2A Firmware Release device 1 4 User Name web interface rotronic Password web interface wlan Serial Port Configuration Profile TCP Sockets Basic Serial Setti...

Page 19: ...p DI with USB port that can be directly connected to a PC depends on the number of USB ports available on the PC PC HW4 USB port Master Address 1 Address 2 Address 64 DI USB RS485 RS485 RS485 Slave Sl...

Page 20: ...00 Data bits 8 Stop bits 1 Parity none Probe inputs 2 HygroClip humidity temperature probes only Operating limits electronics 0 100 RH 40 85 C 40 185 F Measuring range 0 100 RH HygroClip probes are av...

Page 21: ...length 2 meter 6 5 ft or 5 meter 16 4 ft T7 03 B5 Adapter cable for HygroClip probes with T7 connector Cable length 3 meter 9 8 ft AC1211 AC adapter 12VDC 170mA includes adapter for US receptacles 2 1...

Page 22: ...s are tested for Electromagnetic Compatibility according to following European standards EN 61000 6 3 EN 61000 6 1 residential EN 61000 6 4 EN 61000 6 2 industrial Whenever the level of electromagneti...

Page 23: ...al the RS 485 cable should be shielded and comply with the following specifications Cable capacitance 300pF m or 90 pF ft Line impedance 100 15 Line resistance 140 km or 225 Signal lines Twisted pair...

Page 24: ...ubes or supporting constructions should be integrated into the system Protect the potential equalization cable and connections against corrosion Select the cross section of the potential equalization...

Reviews: