2.5
Product Specification
Model
YT-930
Input Signal
4~20mA DC
Impedance
Max. 390
Ω @ 20mA DC
Supply Pressure
–
Output Pressure
Standard
①
0.13 ~ 0.16 MPa (1.2 ~ 1.6 bar)
–
0.02 ~ 0.1 MPa (0.2 ~ 1.0 bar)
Multi-range
②
0.14 ~ 0.16 MPa (1.4 ~ 1.6 bar)
–
0.00 ~ 0.12 MPa (0 ~ 1.2 bar)
③
0.22 ~ 0.24 MPa (2.2 ~ 2.4 bar)
–
0.04 ~ 0.2 MPa (0.4 ~ 2.0 bar)
④
0.25 ~0.27 MPa (2.5 ~ 2.7 bar)
–
0.00 ~ 0.23 MPa (0 ~ 2.3 bar)
Explosion Proof
1. Non-explosion proof
2. ATEX/IECEx : Ex ia IIC T5/T6 Gb,
Ex ia IIIC T100
°C /T85°C Db
Ambient
Temperature
Operating
-40 ~ 85
°C (-40 ~185°F)
Explosion Proof
T5
-40 ~ 60
°C (-40 ~140°F)
T6
-40 ~ 40
°C (-40 ~104°F)
Air Consumption
Below 2 LPM (sup = 0.14 MPa)
Flow Capacity
70 LPM (sup = 0.14 MPa)
Linearity
±0.5% F.S.
Hysteresis
±0.5% F.S.
Sensitivity
±0.2% F.S.
Repeatability
±0.3% F.S.
Air Connection
Rc 1/4 or 1/4 NPT
Conduit Entry
G 1/2
Ingress Protection
IP 66
Housing Material
Aluminum
Weight
1.6 kg (3.5 lb)
Painting
Polyester Powder Coating
Tested under ambient temperature of 20°C, absolute pressure of 760mmHg, and humidity of 65%.