What is DEAD BAND ?
It’s an area/band where no action occurs due to the actuator input.
If the user inputs 12mA (50%), the actuator is supposed to stop exactly at 50% poaition. The actuator repeats from open to close in
order to stop at 50% position at this point.
This is what we call hunting, and if the hunting effect repeatedly occurs the motor can be damage. Therefor a dead band is set to have
some area in order to prevent this from happening.
It’s set to have 0.05mA per gradation. If it is at 1PH when shipped from the factory, it is set to have a 0.2mA dead band. If it is at 3PH,
on the other hand, it is set to have a 0.3mA dead band.
ex) If it is set to have a 0.2mA dead band, the actuator is positioned between 11.8mA to 12.2mA.
In case the actuator stops at the position of 12.1mA, the second least movement area will be at 12.3mA. At this position no action
occurs even when there is the input signal.
Name
Spec.
ZERO
Close manual control button / Input module button
SPAN
Open manual control button / Input module button
ASCN
AUTO SCAN BUTTON (ACTUATOR automatic control button) delivered from
the factory the resistance value of potentiometer may can be changed if the user
modifies its limit setting. Please make sure to press the autoscan button for at
least 2 seconds before operating proportional control.
1
3
2
Name
Spec.
DEAD
BAND
Mechanical steps at least
(0.2ma)
TIME
DELAY
Modulating starting time
(1sec)
What is DELAY TIME ?
This is when there is an instant noise or disturbance from the outside affectin the input signal and therefore the ACTUATOR can’t
function. The delay time setting is to prevent this from happening. If the input signal does not change for more than the time set, the
ACTUATOR will kick in. The setting for the delay time is 0.5 seconds per gradation. When shipped from the factory the delay time is set
at 1 second.
DIP SWITCH
4
No.
Name
Spec.
1
F O
Fail Open
2
F C
Fail Close
3
A FULL
A Full
3.8 ~ 4.3
Input Fully Close
19.7 ~ 20.2
Input Fully Open
4
CH1
Discretion Setting
5
CH2
Manual Setting
6
REV
Reverse Action
INPUT SIGNAL SELECTION
5
INPUT
1
2
3
4-20mA
ON
OFF
OFF
2 - 10V
OFF
ON
OFF
0 - 5V
OFF
OFF
ON
0 - 10V
OFF
ON
ON
1 - 5V
OFF
OFF
OFF