background image

- 4 -

E4L

E4

H

L

H

L

RC210

90

68

120

68

RC220-RC265

90

110

120

110

RC270-RC280, 

RC88

100

160

130

160

RCG90-RCG100 155*

200*

185*

200*

Tabell 14pt bold 

Bold på rubriker uppe, allt under ska vara regular.

Allt utom spalten med RC-förteckningar ska vara 

centrerat i våg och lodrätt. RC-spalten ska vara 

vänsterlagd.

Strl på texten varierar beroende på utrymme men 

10pt är standard

www.rotork.com  www.remotecontrol.se

What is DEAD BAND ?

 

It’s an area/band where no action occurs due to the actuator input.

If the user inputs 12mA (50%), the actuator is supposed to stop exactly at 50% poaition. The actuator repeats from open to close in 

order to stop at 50% position at this point.

This is what we call hunting, and if the hunting effect repeatedly occurs the motor can be damage. Therefor a dead band is set to have 

some area in order to prevent this from happening.

It’s set to have 0.05mA per gradation. If it is at 1PH when shipped from the factory, it is set to have a 0.2mA dead band. If it is at 3PH, 

on the other hand, it is set to have a 0.3mA dead band.

ex) If it is set to have a 0.2mA dead band, the actuator is positioned between 11.8mA to 12.2mA. 

In case the actuator stops at the position of 12.1mA, the second least movement area will be at 12.3mA. At this position no action 
occurs even when there is the input signal.

Name

Spec.

ZERO

Close manual control button / Input module button

SPAN

Open manual control button / Input module button

ASCN

AUTO SCAN BUTTON (ACTUATOR automatic control button) delivered from 

the factory the resistance value of potentiometer may can be changed if the user 

modifies its limit setting. Please make sure to press the autoscan button for at 

least 2 seconds before operating proportional control.

1

3

2

Name

Spec.

DEAD

BAND

Mechanical steps at least

(0.2ma)

TIME

DELAY

Modulating starting time

(1sec)

What is DELAY TIME ?

 

This is when there is an instant noise or disturbance from the outside affectin the input signal and therefore the ACTUATOR can’t 

function. The delay time setting is to prevent this from happening. If the input signal does not change for more than the time set, the 

ACTUATOR will kick in. The setting for the delay time is 0.5 seconds per gradation. When shipped from the factory the delay time is set 
at 1 second.

DIP SWITCH

4

No.

Name

Spec.

1

F O

Fail Open

2

F C

Fail Close

3

A FULL

A Full

3.8 ~ 4.3

Input Fully Close

19.7 ~ 20.2

Input Fully Open

4

CH1

Discretion Setting

5

CH2

Manual Setting

6

REV

Reverse Action

INPUT SIGNAL SELECTION

5

INPUT

1

2

3

4-20mA

ON

OFF

OFF

2 - 10V

OFF

ON

OFF

0 - 5V

OFF

OFF

ON

0 - 10V

OFF

ON

ON

1 - 5V

OFF

OFF

OFF

Summary of Contents for RCEL SA

Page 1: ...scale 0 5 Output Signal 4 20mA DC Load Resistance 750 Wiring Terminals YW 396 2P 3EA 3P 5P connector Visual Indicators 4 LEDS Power Blue Fault Yellow Open Red Close Green Calibration Method ASCN Auto...

Page 2: ...Specification PCU Board A PCU Board B AC INPUT SIGNAL SELECTION AUTOSCAN SPAN ZERO TIME DELAY DEAD BAND 4 20mA DC OUTPUT SIGNAL 4 20mA DC INPUT SIGNAL OUTPUT SIGNAL CONNECTION OPEN AUTO CLOSE AC POWER...

Page 3: ...CU Board A PCU Board B DC INPUT SIGNAL SELECTION AUTOSCAN SPAN ZERO TIME DELAY DEAD BAND 4 20mA DC OUTPUT SIGNAL 4 20mA DC INPUT SIGNAL OUTPUT SIGNAL CONNECTION CCW CW OLS CLS OPEN CLOSE AUTO POWER PO...

Page 4: ...button SPAN Open manual control button Input module button ASCN AUTO SCAN BUTTON ACTUATOR automatic control button delivered from the factory the resistance value of potentiometer may can be changed i...

Page 5: ...mine the value The factory is set to 80 120 If you have not been set 80 120 please reset Refer to page 6 3 POTENTIOMETER CHECK Using the manual lever or handle to the FULL OPEN ACTUATOR then in the sa...

Page 6: ...irection to actuate the open switches AOLS OLS ACLS CLS POTENTIOMETER Setting Actuator delivered full close at 80 120 After limit setting it should check at closed 80 120 Make actuator full closed and...

Page 7: ...plug provided with the ACTUATOR Do not remove the remaining plug as it is already sealed Main Power must only be applied when the top cover is re installed on the actuator body If the main power is on...

Page 8: ...mA 0 10V or 0 5V and 6 18mA 1 9V If you want to change a current signal 1 Optional Modulation DIP SWITCH No 4 Button ON 2 6mA input Push the ZERO BUTTON ACTUATOR CLOSE 4 After the 18mA input SPAN BUTT...

Page 9: ...Limit Power input Wage terminal No 2 No 5 Jump ACTUATOR automatic close open AUTO Button push 25sec Check the resistent value of PIU The resistant value when closed 80 120 4mA Close 20mA Open 4 20mA...

Page 10: ...isengaged Check frequency of operation or JAMMED gears Wiring failure Confirm unit is properly wired per wiring diagram Main board failure Replace main board LED lights not operating LED board failure...