CK Atronik

4.2  Option Settings

Extra Relays

Atronik can accommodate four additional relay contacts with configurable functions. These are determined by DIP switches 
located on the extra relay PCB.

Switch 1

Switch 2

Switch 3

Relay 3 Function

Relay 4 Function

OFF

OFF

OFF

Open Limit

Closed Limit

OFF

OFF

ON

Torque Trip Open

Torque Trip Closed

OFF

ON

OFF

Blinker

Local Selected

OFF

ON

ON

Motor Stall

ESD Active

ON

OFF

OFF

Torque Trip

ESD Active

ON

OFF

ON

Hand Operation

ESD Active

ON

ON

OFF

Local Selected

Mid Travel

ON

ON

ON

Valve Alarm

24 VDC Power Fail

Switch 4

Switch 5

Switch 6

Relay 5 Function

Relay 6 Function

OFF

OFF

OFF

Closed Limit

Open Limit

OFF

OFF

ON

Torque Trip Closed

Torque Trip Open

OFF

ON

OFF

Mid Travel

Local Selected

OFF

ON

ON

Actuator Alarm

Hand Operation

ON

OFF

OFF

Stop Selected

Hand Operation

ON

OFF

ON

Remote Selected

Motor Running

ON

ON

OFF

Local Selected

Motor Running

ON

ON

ON

Mid Travel

Motor Running

Positioner

The positioner option for Atronik enables control of actuator position with a proportional analogue signal.  
Feedback is transmitted via 4-20 mA to provide remote intermediate position indication.

Switch No

Function

OFF

ON

SW5

6

Positioner Inverse

Control signal is:
Close = low, Open = high

Control signal is:
Close = high, Open = low

5

CPT Inverse

Feedback signal is:
Close = 4 mA, Open = 20 mA

Feedback signal is:
Close = 20 mA, Open = 4 mA

4

Signal Loss Action

SW5-3 OFF and SW5-4 OFF = Close
SW5-3 ON and SW5-4 OFF = OFF

SW5-3 ON and SW5-4 ON = Open
SW5-3 OFF and SW5-4 ON = Stayput

3
2

Input Type

SW5-1 OFF and SW5-2 OFF = 0-20 mA
SW5-1 ON and SW5-2 OFF = 0-5 V

SW5-1 ON and SW5-2 ON = 0-20 V
SW5-1 OFF and SW5-2 ON = 0-10 V

1

SW4

0 – 9

Deadband

10* position switch with incrementing values: 0.5%, 1%, 2%, 3%, 5%, 10%

SW3

0 – 9

Motion Inhibit Timer

10* position switch with incrementing values: 1s, 2s, 5s, 10s, 30s, 60s

SW1

Set Open

Inject signal for the Open position and hold SW1 for 3 seconds to set the value

SW2

Set Close

Inject signal for the Close position and hold SW2 for 3 seconds to set the value

Deadband and MIT should be adjusted to provide suitable control accuracy while still filtering out unwanted signal fluctuations and noise.
* Position 0 is the lowest setting, incrementing by one for each subsequent setting value. Surplus positions will match the highest setting 
value and are reserved for future use.

A4

US

US

A4

US

A4

US

A4

A4

US

 US

 A4

 US

 A4

A4

US

Summary of Contents for CK Atronik Series

Page 1: ...CK Range CKa CKra Atronik Start Up Guide Modular Design Electric Valve Actuators...

Page 2: ...ver 1 000 service technicians are employed by our company partners and representatives providing the necessary worldwide infrastructure to fully support actuators in the field 1 CK Valve Actuation Wor...

Page 3: ...ar 11 Serial No Code Bar 12 QR Code 13 IP Degree 14 Address Atronik Name Plate Conduit Entries Switch Mechanism Cover Protective Earth Connection M6x1p x 10 Deep Plug and socket housing Atronik Interf...

Page 4: ...move the actuator to a mid travel position and confirm that none of the switches are active before beginning the test procedure 2 Test position switches in both directions using a flat screw driver to...

Page 5: ...river remains perpendicular to the switch mechanism faceplate when adjusting the torque trip limits to avoid introducing an offset to the set value 3 Commissioning C Open Torque Adjustment Point D Clo...

Page 6: ...ct direction This is done to avoid the need to wind through the whole mechanism to reach the limit position The correct direction to approach the limit is shown by the arrow next to the Adjustment Scr...

Page 7: ...rform two checks to confirm the OPEN limit position switch has been made correctly a The feel of the Adjustment Screw will noticeably change providing more mechanical resistance at the switching point...

Page 8: ...k on the Atronik status indicators during switch testing The main power supply must be maintained during this test procedure to ensure feedback via the Atronik It is not possible to test a switch that...

Page 9: ...orientation can be adjusted through 360 in 90 increments If this is a requirement then the following instructions must be adjusted by the same increment in the same direction 1 Move the actuator to th...

Page 10: ...Screw by 1 turn whilst holding the CLOSE portion of the Position Disc 8 Rotate only the red OPEN portion of the disc so that OPEN reads horizontally and then hold both portions in place 9 Tighten the...

Page 11: ...long the shaft against the spring to allow free rotation of the cam 3 Rotate the cam to ensure the desired switch behaviour is achieved The intermediate position switches can be supplied with normally...

Page 12: ...ntil the POT cannot rotate any further Confirm the POT is triggering the Close Limit indicator on the Atronik or reading the required resistance value 6 Refit the POT assembly to the AID chassis and e...

Page 13: ...the actuator to the Closed position limit using electrical operation or the handwheel 2 Connect a powered test meter across the CPT terminals and measure the transmitted current refer to actuator wir...

Page 14: ...B ON No Priority PRIORITY B OPEN ACTION Open Action Stop on position limit Stop on torque limit CLOSE ACTION Close Action Stop on position limit Stop on torque limit LED LED Green Close Red Open Red C...

Page 15: ...edback is transmitted via 4 20 mA to provide remote intermediate position indication Switch No Function OFF ON SW5 6 Positioner Inverse Control signal is Close low Open high Control signal is Close hi...

Page 16: ...isit our website at www rotork com The name Rotork is a registered trademark Rotork recognizes all registered trademarks Published and produced in the UK by Rotork POWJB0320 Rotork plc Brassmill Lane...

Reviews: