10.1
[en] 02/2014
Installation and operating manual - NK 31
Fault
Possible cause
Remedy
See chapter
Incorrect direction of
rotation
Phases reversed
Reconnect 2 supply lines
System does not start
No electricity
Check
Combistat switches off
due to excessively high
temperature
Check oil level, cooling,
thermo-bypass
System difficult to start
Motor output insufficient
Check
Drive gear ratio „too fast“
Check
Star-delta switchover
incorrect
Set
Compressor is flooded
with oil
Check
System has not been
discharged yet
Check
Oil filling too viscous
Check viscosity
8.1.1
Differential pressure
Pressure in separator
cartridge too high with
clogged or full separator
cartridge
Replace separator
cartridge
7.5.2
Combistat switches
off due to excessively
high temperature
Oil shortage
Check oil level in
oil reservoir and top up
if necessary
7.2
Oil filter soiled
Replace oil filter cartridge
7.4.2
Thermostat defective
Replace thermostat
3.10.2
Oil cooler soiled
Clean oil cooler on air
side, clean on oil side if
necessary
Incorrect installation
a) Room ventilation
b) Exhaust air blocked
c) Thermal short circuit
Observe recommendation
on installing system
5.3
Combistat faulty or
incorrectly adjusted
Adjust combistat or
replace
Fan has failed
Check
10 Troubleshooting