6
x
Parameter settings
FA ROTEX RoCon mb • 09/2017
49
6.8
Rotary switch setting: Time Program
6.9
Rotary switch setting: Remote Param
6.10 Rotary switch setting: Info
Parameters
Name
Access
Setting range
Min / Max
Factory
setting
Incre-
ment
BE
HF
Party
The heating circuit is controlled to the target room temperature set in the parameter [T-Room
1 Setpoint] for the set duration. If the time programs [Automatic 1] or [Automatic 2] are active,
the heating cycle is extended or started prematurely. (Target room temperature, see
chap. 3.4.7).
The hot water generation is not affected.
E
E
00:00 - 06:00
00:00
1 h
Away
The heating circuit is controlled to the target room temperature set in the parameter [T-Ab-
sence] for the set duration.
The hot water generation is not affected.
E
E
00:00 - 06:00
00:00
1 h
Vacation
The heating circuit is continuously (24 h per day) regulated to the target room temperature set
in the parameter [T-Absence].
A calendar function can be used to enter a time period of absence.
E
E
Date 1st day
-
Date last day
-
1 Day
Holiday
A calendar function can be used to enter a time period of presence.
During this period of time, regulation is carried out exclusively according to the settings for
"Sunday" in [HC Program 1] and [DHW Program 1].
E
E
Date 1st day
-
Date last day
-
1 Day
HC Program 1
The 1st time program for the heating circuit can be parameterised in this menu. 3 switching
cycles with a resolution of 15 minutes can be set. A separate entry for each weekday is possi-
ble. Format: (on) hh:mm - hh:mm (off)
Also, the cycles from Monday to Friday, Saturday to Sunday and Monday to Sunday can be
parametrised.
E
E
See
chap. 3.4.7
See
15 min
HC Program 2
The 2nd time program for the heating circuit can be parameterised in this menu. 3 switching
cycles with a resolution of 15 minutes can be set. A separate entry for each weekday is possi-
ble. Format: (on) hh:mm - hh:mm (off)
Also, the cycles from Monday to Friday, Saturday to Sunday and Monday to Sunday can be
parametrised.
E
E
See
chap. 3.4.7
See
15 min
DHW Program 1
In this menu, the 1st time program for hot water generation can be parametrised. 3 switching
cycles with a resolution of 15 minutes can be set. A separate entry for each weekday is possi-
ble. Format: (on) hh:mm - hh:mm (off)
Also, the cycles from Monday to Friday, Saturday to Sunday and Monday to Sunday can be
parametrised.
E
E
See
chap. 3.4.7
See
15 min
DHW Program 2
In this menu, the 2nd time program for hot water generation can be parametrised. 3 switching
cycles with a resolution of 15 minutes can be set. A separate entry for each weekday is possi-
ble. Format: (on) hh:mm - hh:mm (off)
Also, the cycles from Monday to Friday, Saturday to Sunday and Monday to Sunday can be
parametrised.
E
E
See
chap. 3.4.7
See
15 min
Circulation Time
In this menu, a timer program for the circulation pump can be parametrised. 3 switching cycles
with a resolution of 15 minutes can be set. A separate entry for each weekday is possible. For-
mat: (on) hh:mm - hh:mm (off)
Also, the cycles from Monday to Friday, Saturday to Sunday and Monday to Sunday can be
parametrised.
E
E
See
chap. 3.4.7
See
15 min
Tab. 6-10 Parameters in the "Time Program" rotary switch setting
Parameters
Description
Access
Setting range
Min / Max
Factory
setting
Incre-
ment
BE
HF
Bus - Scan
Off: No function
On: controller checks which RoCon devices are connected in the system via CAN data bus lines.
Detected devices are displayed with their type and device ID (see chap. 4.1, example: MM#8 =
mixer module with device ID 8).
The selection and confirmation of a device with the rotary button (pushing the button briefly sets
a tick in the selection box) activate the terminal function.
→
The control panel then acts as a remote control for the selected device (see chap. 3.4.9).
E
E
Off
On
Off
-
No selection
Activation switches to local device.
E
E
-
Contr BM1/BE1 #X
Activation switches to the ROTEX HPSU monobloc compact with the device ID X (see
chap. 6.12, parameter [BUS ID HS]).
E
E
-
Mix Valve #X
Activation switches to the mixer module with the device ID X (see chap. 6.13.1, parameter [HC
Assignment]).
E
E
-
Tab. 6-11 Parameters in the "Remote Param" rotary switch setting
Parameters
Description
Access
Setting range
Min / Max
Factory
setting
Incre-
ment
BE
HF
Overview
Display of different current operating data (see chap. 3.4.1).
S
S
-
-
-
Water Pressure
The current water pressure is displayed in bar.
S
S
0 - 4 bar
-
0.1 bar
T-HS
The current feed temperature (TVBH) of the heat generator in °C is displayed.
S
S
0 - 100 °C
-
1 °C
T-HS Setpoint
The current target feed temperature of the heat generator in °C is displayed (see chap. 3.6.4).
S
S
0 - 90 °C
-
0.1 °C
T-Outside
The mean outside temperature in °C is displayed.
S
S
-39 to +50 °C
0.1 °C
T-DHW
The current temperature of the hot water storage tank is displayed in °C. If no hot water function
is activated, "- - -" is displayed.
S
S
0 - 100 °C
-
0.1 °C