Field code
Setting name
Range, step
Default value
Date
Value
Field settings table
Installer setting at variance with
default value
A.8
[2-02]
R/W
0~23 hour, step: 1 hour
23
A.8
[2-03]
R/W
[E-07]
≠
1 :
55~80°C, step: 5°C
70°C
[E-07]=1 : 60°C
60°C
A.8
[2-04]
R/W
[E-07]
≠
1: 5~60 min, step: 5 min
10 min
[E-07]=1: 40~60 min, step: 5 min
40 min
A.8
[2-05]
R/W
4~16°C, step: 1°C
12°C
A.8
[2-06]
R/W
0: Disabled
1: Enabled
A.8
[2-09]
R/W
-5~5°C, step: 0,5°C
0°C
A.8
[2-0A]
R/W
-5~5°C, step: 0,5°C
0°C
A.8
[2-0B]
R/W
-5~5°C, step: 0,5°C
0°C
A.8
[3-00]
R/W
0: No
1: Yes
A.8
[3-01]
0
A.8
[3-02]
1
A.8
[3-03]
4
A.8
[3-04]
2
A.8
[3-05]
1
A.8
[3-06]
R/W
18~30°C, step: A.3.2.4
30°C
A.8
[3-07]
R/W
12~18°C, step: A.3.2.4
12°C
A.8
[3-08]
R/W
25~35°C, step: A.3.2.4
35°C
A.8
[3-09]
R/W
15~25°C, step: A.3.2.4
15°C
A.8
[4-00]
R/W
0: Disabled
1: Enabled
2: Only DHW
A.8
[4-01]
R/W
0: None
1: BSH
2: BUH
14~35°C, step: 1°C
25°C (*5)
14~35°C, step: 1°C
35°C (*6)
A.8
[4-03]
R/W
0: Limited
1: No limit
2: Most optimum
3: Optimum
4: Only legionella
A.8
[4-04]
2
A.8
[4-05]
0
A.8
[4-06]
0/1
A.8
[4-07]
R/W
0: No
1: Yes
A.8
[4-08]
R/W
0: No limitation
1: Continuous
2: Digital inputs
A.8
[4-09]
R/W
0: Current
1: Power
A.8
[4-0A]
0
A.8
[4-0B]
R/W
1~10°C, step: 0,5°C
1°C
A.8
[4-0D]
R/W
1~10°C, step: 0,5°C
3°C
A.8
[5-00]
R/W
0: Allowed
1: Not allowed
A.8
[5-01]
R/W
-15~35°C, step: 1°C
0°C
A.8
[5-02]
R/W
0: Disabled [E-07]
≠
1
1: Enabled [E-07]=1
A.8
[5-03]
R/W
-15~35°C, step: 1°C
0°C
A.8
[5-04]
R/W
0~20°C, step: 1°C
10°C
A.8
[5-05]
R/W
0~50 A, step: 1 A
50 A
A.8
[5-06]
R/W
0~50 A, step: 1 A
50 A
A.8
[5-07]
R/W
0~50 A, step: 1 A
50 A
A.8
[5-08]
R/W
0~50 A, step: 1 A
50 A
A.8
[5-09]
R/W
0~20 kW, step: 0,5 kW
20 kW
A.8
[5-0A]
R/W
0~20 kW, step: 0,5 kW
20 kW
A.8
[5-0B]
R/W
0~20 kW, step: 0,5 kW
20 kW
A.8
[5-0C]
R/W
0~20 kW, step: 0,5 kW
20 kW
A.8
[5-0D]
R/W
0: 1P,(1/2)
1: 1P,(1/1+2) (*3)
2: 3P,(1/2)
3: 3P,(1/1+2)
4: 3PN,(1/2)
5: 3PN,(1/1+2) (*4)
A.8
[5-0E]
1
A.8
[6-00]
R/W
2~20°C, step: 1°C
2°C
A.8
[6-01]
R/W
0~10°C, step: 1°C
2°C
The temperature difference determining the heat pump OFF temperature.
What is the requested limit for DI2?
What is the requested limit for DI3?
What is the requested limit for DI4?
What type of backup heater installation is used?
--
The temperature difference determining the heat pump ON temperature.
Set point correction for domestic hot water temperature.
What is the requested limit for DI1?
What is the requested limit for DI2?
What is the requested limit for DI3?
What is the requested limit for DI4?
What is the requested limit for DI1?
Automatic cooling/heating changeover hysteresis.
Automatic cooling/heating changeover offset.
Is backup heater operation allowed above equilibrium temperature during space
heating operation?
What is the equilibrium temperature for the building?
Space heating priority.
Space heating priority temperature.
--
-- (Do not change this value)
Enable the second step of the backup heater?
Which power limitation mode is required on the system?
Which power limitation type is required?
--
A.8
[4-02]
Below which outdoor temperature is heating allowed?
R/W
Operation permission of the booster heater.
--
What is the maximum desired room temperature in heating?
What is the mimimum desired room temperature in heating?
What is the maximum desired room temperature in cooling?
What is the minimum desired room temperature in cooling?
What is the BUH operation mode?
Which electric heater has priority?
Is auto restart of the unit allowed?
--
--
--
--
--
How long must the tank temperature be maintained?
Room antifrost temperature
Room frost protection
Adjust the offset on the measured room temperature
Adjust the offset on the measured room temperature
What is the required offset on the measured outdoor temp.?
When should the disinfection function start?
What is the disinfection target temperature?